Plan Review Details - Permit 17100865
Plan Review Stops For Permit 17100865
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-04-02 Cont ID  
Sent By cthroop Date 2018-04-02 Time 16:50 Rev Time 0.00
Received By cthroop Date 2018-04-02 Time 15:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-05 Cont ID  
Sent By jwitmer Date 2018-01-05 Time 13:39 Rev Time 0.00
Received By jwitmer Date 2018-01-05 Time 11:58 Sent To  
Notes
2018-01-05 13:39:462014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17100865
 ADD: 1101 54TH ST.
 CONT: TRITON ELECTRIC CO.
 TEL: 321-246-8262
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JAN. 05/2018
 ACTION: DENIED
  
 1) PLEASE NOTE THE SHEET GS-1.0 PROVIDES THE DETAILS
 FOR THE GENERATOR SLAB BUT THERE IS NO INFORMATION ON
 THE ANCHORING THE GENERATOR AND DAY TANK TO THE SLAB.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 2) IN THE GENERAC PACKAGE IT APPEARS THE STANDARD
 ENCLOSURE FOR A 350 KW BUT THE PACKAGE DOES NOT PROVIDE
 THE ANCHORAGE OF THE DAY TANK TO THE SLAB NOR IS THERE
 DETAILS OF HOW THE DAY TANK AND GENERATOR ARE TO BE
 ANCHORED/ JOINED TOGETHER. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
2017-12-27 17:14:32SENT TO JW'S DESK. CT

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-01-05 Cont ID  
Sent By jpearson Date 2018-01-05 Time 15:55 Rev Time 0.00
Received By jpearson Date 2018-01-05 Time 15:55 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-07 Cont ID  
Sent By jpearson Date 2017-11-07 Time 13:16 Rev Time 0.00
Received By jpearson Date 2017-11-07 Time 13:16 Sent To I
Notes
2017-11-07 13:13:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 NOTE: SUBMISSIONS FOR THIS PERMIT ARE SEPARATE FROM
 OTHER PERMITS THAT MAY OR MAY NOT BE OPEN ON THIS JOB
 AND REQUIRE THE FOLLOWING:
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE LICENSED DESIGN PROFESSIONAL OF RECORD
 FOR GENERATOR INSTALLATION. FS 471.003(2)(H); 471.025;
 FBC 107.2.1, 107.3.5
 2. PROVIDE SPEC SHEET AND INSTALLATION MANUAL FOR
 GENERATOR AND TRANSFER SWITCH.
 3. PROVIDE LOAD CALCULATION FOR LOADS SUPPLIED BY
 GENERATOR TO VERIFY CAPACITY OF THE GENERATOR IS
 SUFFICIENT. NEC 220, NEC 700.4
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-03-28 Cont ID  
Sent By pleduc Date 2018-03-28 Time   Rev Time 0.00
Received By pleduc Date 2018-03-27 Time 16:54 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-12-21 Cont ID  
Sent By pleduc Date 2017-12-21 Time   Rev Time 0.00
Received By pleduc Date 2017-12-20 Time 16:31 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-11-03 Cont ID  
Sent By pleduc Date 2017-11-03 Time   Rev Time 0.00
Received By pleduc Date 2017-11-03 Time 12:03 Sent To E
Notes
2017-11-03 12:15:13THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE IS INSUFFICIENT INFORMATION SUBMITTED TO DO A
 COMPREHENSIVE REVIEW OF THE PROPOSES.
  
 IF THE WORK IS LIMITED TO TRANFET SWITCHES AND REMOTE
 PANELS, DETAILS AND SPECIFICS SHALL BE PROVIDED TO
 THOSE PIECES OF EQUIPMENT. DETAILS WITHIN THE ROOM/
 WALL/ AREA OR SPACE SHALL BE PROVIDED.
  
 2) IS THIS PROJECT A NEW INSTALLED GENERATOR OR
 MODIFICATIONS TO AN EXISTING ONE?
  
 PLEASE PROVIDE INFORMATION
  
  
 3) THERE IS A CONCRETE SLAB SHEET INDICATED. IS THIS
 SLAB FOR A NEW GENERATOR INSTALL OR REPLACEMENT FOR AN
 EXISITNG ONE?
  
 PLEASE PROVIDE INFORMATION
  
  
 4) THERE IS NO LOCATION INDICATED WHERE THE WORK WILL
 BE DONE ON ANY PLAN SHEET.
  
 PROVIDE THE LOCATION OR AREA OF WORK.
  
  
  
 5) THERE ARE NO EQUIPMENT SPECIFICATIONS SHEETS.
  
 PROVIDE SPEC SHEETS
  
  
  
 6) WILL THIS GENERATOR BE SUPPLYING ANY LIFE SAFETY
 EQUIPMENT? IF SO, ALL INSTALLATIONS SHALL COMPLY WITH
 NFPA 110, STANDARD FOR EMERGENCY AND STANDBY POWER
 SYSTEMS, 2010 EDITION.AND SHALL BE INSPECTED AND TESTED
 PER THE CODE.
  
 PROVIDE AN APPLICABLE NOTE OF COMPLIANCE.
  
  
  
 7) ALL ELECTRICAL INSTALLTIONS SHALL COMPLY WITH NFPA
 70?, NATIONAL ELECTRICAL CODE?, 2011 EDITION.
  
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-04-02 Cont ID  
Sent By cthroop Date 2018-04-02 Time 16:51 Rev Time 0.00
Received By cthroop Date 2018-03-19 Time 11:46 Sent To I
Notes
2018-03-20 11:46:55RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-01-05 Time   Rev Time 0.00
Received By lmarchan Date 2017-12-07 Time 14:51 Sent To  
Notes
2017-12-07 14:52:10ROUTED TO PGREILIC VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-07 Cont ID  
Sent By jpearson Date 2017-11-07 Time 13:16 Rev Time 0.00
Received By jpearson Date 2017-10-20 Time 11:06 Sent To  
Notes
2017-10-23 11:06:14ROUTED TO ZONING

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2018-03-27 Time   Rev Time 0.00
Received By pgreilic Date 2018-03-27 Time 08:57 Sent To FIRE
Notes
2018-03-27 08:58:22 
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By PG Date 2017-12-20 Time   Rev Time 0.00
Received By ajones Date 2017-12-11 Time 14:18 Sent To  
Notes
2017-12-20 12:11:45PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By ES Date 2017-10-30 Time   Rev Time 0.00
Received By ajones Date 2017-10-24 Time 15:47 Sent To FIRE
Notes
2017-10-31 08:53:27PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]