| Plan Review Stops For Permit 17100865 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-04-02 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-04-02 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-04-02 |
Time |
15:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-01-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-01-05 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2018-01-05 |
Time |
11:58 |
Sent To |
|
|
| Notes |
| 2018-01-05 13:39:46 | 2014 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 17100865 | | | ADD: 1101 54TH ST. | | | CONT: TRITON ELECTRIC CO. | | | TEL: 321-246-8262 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: FRI. JAN. 05/2018 | | | ACTION: DENIED | | | | | | 1) PLEASE NOTE THE SHEET GS-1.0 PROVIDES THE DETAILS | | | FOR THE GENERATOR SLAB BUT THERE IS NO INFORMATION ON | | | THE ANCHORING THE GENERATOR AND DAY TANK TO THE SLAB. | | | 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL | | | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY | | | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT | | | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY | | | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. | | | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE | | | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES | | | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND | | | LOADS. | | | | | | 2) IN THE GENERAC PACKAGE IT APPEARS THE STANDARD | | | ENCLOSURE FOR A 350 KW BUT THE PACKAGE DOES NOT PROVIDE | | | THE ANCHORAGE OF THE DAY TANK TO THE SLAB NOR IS THERE | | | DETAILS OF HOW THE DAY TANK AND GENERATOR ARE TO BE | | | ANCHORED/ JOINED TOGETHER. 107.2.1.3 ADDITIONAL | | | INFORMATION IS REQUIRED. | | | | | | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. | | | WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | 2017-12-27 17:14:32 | SENT TO JW'S DESK. CT |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-01-05 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-01-05 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-01-05 |
Time |
15:55 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-11-07 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-11-07 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-11-07 |
Time |
13:16 |
Sent To |
I |
|
| Notes |
| 2017-11-07 13:13:38 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | NOTE: SUBMISSIONS FOR THIS PERMIT ARE SEPARATE FROM | | | OTHER PERMITS THAT MAY OR MAY NOT BE OPEN ON THIS JOB | | | AND REQUIRE THE FOLLOWING: | | | | | | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND | | | SEALED BY THE LICENSED DESIGN PROFESSIONAL OF RECORD | | | FOR GENERATOR INSTALLATION. FS 471.003(2)(H); 471.025; | | | FBC 107.2.1, 107.3.5 | | | 2. PROVIDE SPEC SHEET AND INSTALLATION MANUAL FOR | | | GENERATOR AND TRANSFER SWITCH. | | | 3. PROVIDE LOAD CALCULATION FOR LOADS SUPPLIED BY | | | GENERATOR TO VERIFY CAPACITY OF THE GENERATOR IS | | | SUFFICIENT. NEC 220, NEC 700.4 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2018-03-28 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-03-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-03-27 |
Time |
16:54 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-12-21 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-12-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-12-20 |
Time |
16:31 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2017-11-03 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-11-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-11-03 |
Time |
12:03 |
Sent To |
E |
|
| Notes |
| 2017-11-03 12:15:13 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) THERE IS INSUFFICIENT INFORMATION SUBMITTED TO DO A | | | COMPREHENSIVE REVIEW OF THE PROPOSES. | | | | | | IF THE WORK IS LIMITED TO TRANFET SWITCHES AND REMOTE | | | PANELS, DETAILS AND SPECIFICS SHALL BE PROVIDED TO | | | THOSE PIECES OF EQUIPMENT. DETAILS WITHIN THE ROOM/ | | | WALL/ AREA OR SPACE SHALL BE PROVIDED. | | | | | | 2) IS THIS PROJECT A NEW INSTALLED GENERATOR OR | | | MODIFICATIONS TO AN EXISTING ONE? | | | | | | PLEASE PROVIDE INFORMATION | | | | | | | | | 3) THERE IS A CONCRETE SLAB SHEET INDICATED. IS THIS | | | SLAB FOR A NEW GENERATOR INSTALL OR REPLACEMENT FOR AN | | | EXISITNG ONE? | | | | | | PLEASE PROVIDE INFORMATION | | | | | | | | | 4) THERE IS NO LOCATION INDICATED WHERE THE WORK WILL | | | BE DONE ON ANY PLAN SHEET. | | | | | | PROVIDE THE LOCATION OR AREA OF WORK. | | | | | | | | | | | | 5) THERE ARE NO EQUIPMENT SPECIFICATIONS SHEETS. | | | | | | PROVIDE SPEC SHEETS | | | | | | | | | | | | 6) WILL THIS GENERATOR BE SUPPLYING ANY LIFE SAFETY | | | EQUIPMENT? IF SO, ALL INSTALLATIONS SHALL COMPLY WITH | | | NFPA 110, STANDARD FOR EMERGENCY AND STANDBY POWER | | | SYSTEMS, 2010 EDITION.AND SHALL BE INSPECTED AND TESTED | | | PER THE CODE. | | | | | | PROVIDE AN APPLICABLE NOTE OF COMPLIANCE. | | | | | | | | | | | | 7) ALL ELECTRICAL INSTALLTIONS SHALL COMPLY WITH NFPA | | | 70?, NATIONAL ELECTRICAL CODE?, 2011 EDITION. | | | | | | | | | | | | 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-04-02 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-04-02 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-03-19 |
Time |
11:46 |
Sent To |
I |
|
| Notes |
| 2018-03-20 11:46:55 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-01-05 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-12-07 |
Time |
14:51 |
Sent To |
|
|
| Notes |
| 2017-12-07 14:52:10 | ROUTED TO PGREILIC VIA ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-11-07 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-11-07 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-10-20 |
Time |
11:06 |
Sent To |
|
|
| Notes |
| 2017-10-23 11:06:14 | ROUTED TO ZONING |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-03-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2018-03-27 |
Time |
08:57 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
PG |
Date |
2017-12-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2017-12-11 |
Time |
14:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
ES |
Date |
2017-10-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2017-10-24 |
Time |
15:47 |
Sent To |
FIRE |
|
| Notes |
|
|