Plan Review Details - Permit 17100783
Plan Review Stops For Permit 17100783
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-12-05 Cont ID  
Sent By jwitmer Date 2017-12-05 Time 11:58 Rev Time 0.00
Received By jwitmer Date 2017-12-05 Time 11:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-24 Cont ID  
Sent By jwitmer Date 2017-10-24 Time 06:50 Rev Time 0.00
Received By jwitmer Date 2017-10-24 Time 05:59 Sent To  
Notes
2017-10-24 06:42:34TENANT DATA: IB/SPRINK/B/2433 SQ. FT./24/ 1 RESTROOM
  
  
 2014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17100783
 ADD: 480 HIBISCUS ST. SUITE: 115
 CONT: IBS CONSTRUCTION
 TEL: 305-527-8303
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. OCT. 24/ 2017
 ACTION: DENIED
  
 1) THE ARCHITECTURAL SHEETS ALL HAVE STAMPED AND COPIED
 SIGNATURE. PLANS ARE TO BE SIGNED WITH A FULL SIGNATURE
 FROM THE ARCHITECT OF RECORD PER 481.221 WITH A MINIMUM
 OF FIRST AND LAST NAME AS SHOWN ON THE ARCHITECTS'
 LICENSE, FAC 61G1-16.003.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-12-04 Cont ID  
Sent By jpearson Date 2017-12-04 Time 07:53 Rev Time 0.00
Received By jpearson Date 2017-12-04 Time 07:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-07 Cont ID  
Sent By jpearson Date 2017-11-07 Time 08:15 Rev Time 0.00
Received By jpearson Date 2017-11-07 Time 08:15 Sent To I
Notes
2017-11-07 08:15:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS,
 FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS,
 WALK-IN COOLERS, HOODS, ETC. FBC 105.1, 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2018-06-19 Cont ID  
Sent By jpearson Date 2018-06-19 Time 15:49 Rev Time 0.00
Received By jpearson Date 2018-06-19 Time 15:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-12-01 Cont ID  
Sent By pleduc Date 2017-12-01 Time   Rev Time 0.00
Received By pleduc Date 2017-12-01 Time 10:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-10-23 Cont ID  
Sent By pleduc Date 2017-10-23 Time   Rev Time 0.00
Received By pleduc Date 2017-10-23 Time 11:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-07 Cont ID  
Sent By thunt Date 2017-12-07 Time 15:43 Rev Time 0.00
Received By thunt Date 2017-11-30 Time 13:10 Sent To  
Notes
2017-11-30 13:13:38B10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-07 Cont ID  
Sent By jpearson Date 2017-11-07 Time 08:16 Rev Time 0.00
Received By jpearson Date 2017-10-18 Time 13:49 Sent To  
Notes
2017-10-20 13:49:08B10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-10-24 Cont ID  
Sent By jwitmer Date 2017-10-24 Time 06:50 Rev Time 0.00
Received By jwitmer Date 2017-10-24 Time 06:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-12-01 Cont ID  
Sent By ccole Date 2017-12-01 Time 15:51 Rev Time 0.00
Received By ccole Date 2017-12-01 Time 14:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-01 Cont ID  
Sent By ccole Date 2017-11-01 Time 14:36 Rev Time 0.00
Received By ccole Date 2017-11-01 Time 14:36 Sent To  
Notes
2017-11-01 14:39:181ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17100783
 11/1/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE MIAMI-DADE NOA'S FOR THE AC STAND AND
 THE O/A INTAKE AND EXHAUST LOUVERS- RULE 9N-3 FAC.
 PLEASE NOTE THAT THE CONDENSER MOUNTING DETAIL #6 ON
 M5.1 IS CALLING OUT NOA #13-1017.09 FOR ATTACHMENT
 DETAILS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-12-07 Cont ID  
Sent By thunt Date 2017-12-07 Time 15:43 Rev Time 0.00
Received By thunt Date 2017-12-07 Time 15:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-11-03 Cont ID  
Sent By gjohnson Date 2017-11-03 Time 11:29 Rev Time 0.00
Received By gjohnson Date 2017-11-03 Time 09:58 Sent To  
Notes
2017-11-03 11:54:241ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A001 UNDER SCOPE OF WORK IT LISTS UNITS 105-110
 THE PLAN AND PERMIT APP SHOWS UNIT 115 PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 2. THE KITCHEN SINK SHALL COMPLY WITH FBC ACC 606 SHT.
 A-801 DETAIL #2 SHOWS 36" TO TOP OF COUNTER THAT DOES
 NOT COMPLY PLEASE CLARIFY.
  
 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7
 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS.
 DISPENSERS SHALL NOT BE OF A TYPE THAT CONTROLS
 DELIVERY OR THAT DOES NOT ALLOW CONTINUOUS PAPER FLOW.
  
 4. WALLS AROUND THE JANITORS SINK SHALL COMPLY WITH FBC
 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF
 A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 5. THE KITCHEN SINK SHALL BE SUPPLIED WITH HOT WATER
 MIN 110DEG. THE LAVATORY REQUIRES TEMPERED WATER UNDER
 110DEG. THE KITCHEN SHALL NOT BE SUPPLIED THROUGH THE
 WATER TEMPERATURE LIMITING DEVICE USED FOR TEMPERED
 WATER. PER FBC PL 607.1 AND 416.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  