Plan Review Details - Permit 17100735
Plan Review Stops For Permit 17100735
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-11-01 Cont ID  
Sent By jleahy Date 2017-11-01 Time 07:05 Rev Time 0.00
Received By jleahy Date 2017-11-01 Time 07:05 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-07-09 Time   Rev Time 0.00
Received By lmarchan Date 2018-06-29 Time 16:01 Sent To  
Notes
2018-07-02 16:01:55RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-04-09 Time   Rev Time 0.00
Received By lmarchan Date 2018-04-03 Time 10:08 Sent To  
Notes
2018-04-04 10:08:42RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-01 Cont ID  
Sent By jleahy Date 2017-11-01 Time 07:06 Rev Time 0.00
Received By jleahy Date 2017-10-18 Time 11:12 Sent To  
Notes
2017-10-19 11:12:30ROUTED TO MECH <5K

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-07-09 Cont ID  
Sent By ccole Date 2018-07-09 Time 09:20 Rev Time 0.00
Received By ccole Date 2018-07-09 Time 08:22 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-04-09 Cont ID  
Sent By ccole Date 2018-04-09 Time 09:45 Rev Time 0.00
Received By ccole Date 2018-04-09 Time 09:45 Sent To I
Notes
2018-04-09 09:58:362ND REVIEW FBC-2014 MECHANICAL
 PERMIT 17100735
 4/9/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENT #2 FROM THE PREVIOUS REVIEW STILL EXISTS. IT
 IS REPRINTED BELOW- PLEASE COMPLY.
  
 THE PREVIOUSLY UNCONDITIONED BUILDING NOW BEING
 CONDITIONED REQUIRES COMPLIANCE WITH THE FLORIDA ENERGY
 CONSERVATION CODE. PLEASE SEE SECTIONS R101.4.5 AND
 R101.5.1.1, AND SUBMIT AN ENERGY EFFICIENCY COMPLIANCE
 REPORT FOR THE NEW CONDITIONED SPACE.
  
 2) THE MODEL NUMBER FOR THE AC CONDENSER SHOWN IN THE
 AC SCHEDULE MODEL NOT MATCH THE MODEL NUMBER ON THE
 AHRI CERTIFICATE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-10-27 Cont ID  
Sent By ccole Date 2017-10-27 Time 14:26 Rev Time 0.00
Received By ccole Date 2017-10-27 Time 14:22 Sent To  
Notes
2017-10-27 14:45:361ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL
 PERMIT #17100735
 10/27/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE WORK DESCRIPTION ON THE PERMIT APPLICATION IS
 INCORRECT- THIS IS NEW AC INSTALLATION AND NOT A CHANGE
 OUT.THE PALM BEACH COUNTY PROPERTY APPRAISOR'S REPORT
 SHOWS NO HEATING OR AC FOR THE RESIDENCE, AND THERE IS
 NO RECORD OF AN AC PERMIT IN THE BUILDING DEPARTMENT
 RECORDS.
  
 2) THE PREVIOUSLY UNCONDITIONED BUILDING NOW BEING
 CONDITIONED REQUIRES COMPLIANCE WITH THE FLORIDA ENERGY
 CONSERVATION CODE. PLEASE SEE SECTIONS R101.4.5 AND
 R101.5.1.1, AND SUBMIT AN ENERGY EFFICIENCY COMPLIANCE
 REPORT FOR THE NEW CONDITIONED SPACE.
  
 3) PROVIDE ENGINEERED DETAILS FOR ATTACHING THE
 CONDENSER TO THE CONCRETE PAD- SECTIONS M1305.1.4.1 &
 M1401.4 FBC-14 RESIDENTIAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  