Plan Review Details - Permit 17100696
Plan Review Stops For Permit 17100696
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-01-18 Cont ID  
Sent By thunt Date 2018-01-18 Time 06:23 Rev Time 0.00
Received By thunt Date 2018-01-18 Time 06:23 Sent To  
Notes
2018-01-18 06:24:08MANUFACTURE INSTALLATION MANUAL'S REQUIRED TO BE ONSITE

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-10-23 Cont ID  
Sent By lcrespo Date 2017-10-23 Time 16:00 Rev Time 0.00
Received By lcrespo Date 2017-11-30 Time 15:11 Sent To  
Notes
2017-11-30 15:09:5410/23/17 DENIED FOR THE FOLLOWING REASONS
  
 1. THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SEC. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 2. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL POOL GAS HEATER EQUIPMENT
 TO VERIFY COMPLIANCE WITH FBC-2014 FUEL GAS CODE SEC.
 402.2, AND 301.3 OR 2014 FBC-RES. SEC. G2404.3. GAS
 APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1.
  
 3. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  
 PLUMB <5K

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-18 Cont ID  
Sent By thunt Date 2018-01-18 Time 06:24 Rev Time 0.00
Received By thunt Date 2018-01-12 Time 14:22 Sent To I
Notes
2018-01-16 14:23:00RESUB ROUTED TO LCRESPO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-23 Cont ID  
Sent By lcrespo Date 2017-10-23 Time 16:00 Rev Time 0.00
Received By lcrespo Date 2017-11-30 Time 15:10 Sent To  
Notes
2017-10-23 16:09:54 
  
2017-10-18 14:42:39PLUMB <5K