| 2017-10-27 15:59:12 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE SHOW COMPLIANCE WITH FBC ACC 606.3 HEIGHT. |
| | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR |
| | COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF |
| | THE REFLECTING SURFACE 35 INCHES |
| | (890 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7 |
| | DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR |
| | |
| | 4. PLEASE PROVIDE INSIDE DIMENSION OS SHOWERS SHALL |
| | COMPLY WITH FBC ACC 608.2.1 / 608.2.2 / 608.2.3 |
| | |
| | 5. PLEASE PROVIDE CLEAR FLOOR SPACE FOR SHOWER IN UNIT |
| | 110 PER FBC ACC 608.2.2.1 A 30 INCH WIDE MINIMUM BY 60 |
| | INCH LONG MINIMUM CLEARANCE SHALL BE PROVIDED ADJACENT |
| | TO THE OPEN FACE OF THE SHOWER COMPARTMENT. |
| | |
| | 6. PLEASE SHOW COMPLIANCE WITH FBC ACC 608.5.1 / |
| | 608.5.2 / 608.5.3 |
| | |
| | 7. SHT. A801.2 DETAIL #2 THE KITCHENETTE SINK SHALL |
| | COMPLY WITH FBC ACC 606.3 HEIGHT. |
| | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 8. ARE THE GRAB BARS IN THE BATHROOM ENTERED INTO |
| | THROUGH A PRIVATE OFFICE GOING TO BE INSTALLED IF NOT |
| | PLEASE PROVIDE DETAIL SHOWING THE BACKING MOUNTING |
| | HEIGHT. PER FBC ACC 604.5 EXCEPTION 1. |
| | |
| | 9. THE WATTS LFMMV THERMOSTATIC MIXING VALVE THAT IS |
| | SHOWN ON THE PLAN AT WATER HEATER CANNOT BE USED TO |
| | SUPPLY TEMPERED BY ITSELF TO THE LAVATORY'S TO MEET THE |
| | REQUIREMENT OF TEMPERED WATER. PER MANUFACTURE |
| | SPECIFICATION WARNING. |
| | |
| | 10. A BACKFLOW IS REQUIRED ON REFRIGERATOR ICE MACHINE |
| | WATER SUPPLY PER FBC PL 608.3 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |