Plan Review Details - Permit 17100607
Plan Review Stops For Permit 17100607
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-02-16 Cont ID  
Sent By jwitmer Date 2018-02-16 Time 15:37 Rev Time 0.00
Received By jwitmer Date 2018-02-16 Time 10:52 Sent To  
Notes
2018-02-16 15:37:052014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17100607
 ADD: 771 VILLAGE BLVD. SUITE: 502
 CONT: COMET CONSTRUCTION
 TEL: 561-672-8236
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. FEB. 16/ 2018
 ACTION: BUILDING PROVISO
  
 1) NEW OUTSWING STOREFRONT DOORS AND TRANSOM TO BE A
 DEFERRED SUBMITTAL. SHEET A-4 DETAIL D4/A-4 INDICATES A
 NEW STOREFRONT GLAZING SYSTEM, DOOR, TRANSOM AND FRAME.
 A FLORIDA PRODUCT APPROVAL IS TO BE REVIEWED BY THE
 DESIGN PROFESSIONAL BEFORE BEING SUBMITTED TO THE
 JURISDICTION HAVING JURISDICTION FOR APPROVAL AND
 BEFORE INSTALLATION. THIS REVIEW SHOP DRAWINGS WERE
 SUBMITTED NO PRODUCT APPROVAL.
  
 107.3.4.2 DEFERRED SUBMITTALS. DOCUMENTS FOR DEFERRED
 SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL
 REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL
 WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  
 2) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-23 Cont ID  
Sent By jwitmer Date 2017-10-23 Time 11:34 Rev Time 0.00
Received By jwitmer Date 2017-10-23 Time 07:17 Sent To  
Notes
2017-10-23 11:34:322014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17100607
 ADD: 831 VILLAGE BLVD. SUITE:
 CONT: TBD/ TO BE DETERMINED
 TEL: 954-914-9848
 E-MAIL: ???????? NO E-MAIL ADDRESS PROVIDED.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. OCT. 23/ 2017
 ACTION: DENIED
  
 1) IS THERE A SUITE NUMBER FOR THIS TENANT SPACE, NOT
 PROVIDED ON THE PERMIT APPLICATION NOR THE HEADER STRIP
 OF PLANS?
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
  
 2014 FBC-B 01.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
  
 2) THE LS1 SHEET SHOWS THE COMMON WALL BETWEEN THE
 PUBLIX GROCERY STORE AND THE NEW PUBLIX WINE & SPIRITS
 TENANT AS AN EXISTING 2 HOUR FIRE RATED WALL. SHEET A-4
 DETAIL C3 INDICATES THE USE OF A 1 ? HOUR FIRE RATED
 ACCESS DOOR ON EACH SIDE OF THE NEW PENETRATION IN THE
 FIRE RATED WALL. IN THIS SAME DETAIL IT STATES 1 HOUR
 RATED FROM EACH SIDE. THE UL LISTING U-901 PROVIDED IN
 THE LS SHEET IS FOR A 4 HOUR FIRE RATED WALL WHICH WILL
 REQUIRE A 3 HOUR OPENING PROTECTIVE. DISCREPANCY, IN
 PLANS, 107.2.1.3 ADDITIONAL DATA. PLEASE PROVIDE ALL
 DETAILS TO BE CONSISTENT.
  
 3) THE LS1 SHEET INDICATES THE REQUIREMENT FOR 2 EXITS.
 THE PLANS SHOW THE FRONT EXIT AND THE REAR GOING
 THROUGH A STORAGE OR STOCK ROOM, THE PLANS DO NOT
 DECLARE USAGE. PLEASE PROVIDE COMPLIANCE WITH:
 2014 FLORIDA BUILDING CODE 1014.2 EGRESS THROUGH
 INTERVENING SPACES.
 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE
 FOLLOWING ARE MET:
 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS
 THAT FOUND IN THE MAIN RETAIL AREA;
 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS
 THROUGH THE STOCKROOM;
 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE
 EGRESS SIDE; AND
 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118
 MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED
 WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE
 REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA
 TO THE EXIT WITHOUT OBSTRUCTIONS.
  
 4) SHEET A-1 NOTE 24 INDICATES THE INSTALLATION OF 9/16
 INCH GLASS ON DOOR. SHEET A-4 DETAIL D4/A-4 INDICATES A
 NEW STOREFRONT GLAZING SYSTEM, DOOR AND FRAME IS TO BE
 INSTALLED. PLEASE PROVIDE CONSISTENT DETAILS. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED. IF A NEW STOREFRONT
 GLAZING SYSTEM IS TO BE INSTALLED PLEASE COMPLY WITH:
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
  
 4A) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 4B) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 5A) SHEET S-1 INDICATES THE WIND DESIGN CRITERIA AS 170
 VULT, C EXPOSURE, RISK CAT. II AND ENCLOSED BUILDING.
 WHAT IS MISSING IS THE MEAN ROOF HEIGHT PER TABLE
 1609.7.2 HEIGHT AND EXPOSURE OF THE FBC-B.
  
 5B) SHEET S-1 DOES PROVIDE A PRESSURE CHART FOR
 BUILDING ZONES 1-5. THE CHART DOES NOT INDICATE IF THE
 PRESSURES ARE IN VULT OR VASD, NEED THE MEAN ROOF
 HEIGHT, NOR DO THEY PROVIDE THE TRIBUTARY AREA THEY ARE
 CALCULATED FOR, NOT ENOUGH INFORMATION. 107.2.1.3.
  
 6A) SHEET S-1 DETAIL A-5 PROVIDES A NEW A/C CURB CUT
 AND INSTALLATION OF CURB AND ATTACHMENT TO THE ROOF
 FRAMING SYSTEM BUT NOT THE CURB TO THE UNIT ITSELF. THE
 MECHANICAL SHEET M4 DETAIL C4 PROVIDES A DETAIL AND Z
 CLIP (2) PER LONG SIDE WITH ANCHORS BUT THE DETAIL DOES
 NOT INDICATE THE WIND DESIGN CRITERIA IT WAS DESIGNED
 FOR. PLEASE SHOW COMPLIANCE WITH 2014 FBC-B 2014 FBC-B
 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL MEMBERS AND
 THEIR CONNECTIONS SHALL BE DETERMINED BY METHODS OF
 STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM,
 GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH
 SHORT- AND LONG-TERM MATERIAL PROPERTIES. EVERY
 STRUCTURE SHALL BE DESIGNED TO RESIST THE OVERTURNING
 EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED IN THIS
 CHAPTER. SEE SECTION 1609 FOR WIND LOADS.
  
 6B) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
 7) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-04-02 Cont ID  
Sent By ppetty Date 2018-04-02 Time 14:25 Rev Time 0.00
Received By ppetty Date 2018-04-02 Time 14:25 Sent To  
Notes
2018-04-02 14:24:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: PASSED SEE LAST PAGE
  
 ALL PREVIOUS COMMENTS HAVE BEEN ADDRESSED
 SATISFACTORILY.
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-03-23 Cont ID  
Sent By jpearson Date 2018-03-23 Time 10:33 Rev Time 0.00
Received By jpearson Date 2018-03-23 Time 10:33 Sent To I
Notes
2018-03-23 10:33:25CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 ALL PREVIOUS COMMENTS HAVE BEEN ADDRESSED
 SATISFACTORILY. HOWEVER, SHEET E-3 IN EACH SET HAS NOT
 BEEN SIGNED AND SEALED BY THE ENGINEER OF RECORD.
 PROVIDE CORRECTION. WPB FBC 107.1
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-02-22 Cont ID  
Sent By jpearson Date 2018-02-22 Time 13:35 Rev Time 0.00
Received By jpearson Date 2018-02-22 Time 10:29 Sent To P
Notes
2018-02-22 13:35:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES.
  
 1. CORRECTED.
 2. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE FOR THE SALES FLOOR
 AREA. FBC CE 405.2.2, 405.2.2.2 (NOT SHOWN ON PLAN.)
 3. CORRECTED.
 4. TIME CLOCK SPECIFIED IS NOT ASTRONOMICAL TYPE.
 ENERGY CODE STATES: "LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH. LIGHTING DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN
 ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMMING AND
 THE TIME SETTING DURING LOSS OF POWER FOR A PERIOD OF
 AT LEAST 10 HOURS. FBC CE 405.2.4" PROVIDE CORRECTION.
 (CORRECTION NOT SHOWN ON PLAN.)
 5. RISER DIAGRAM SHOWS NOTE 3 IN PANEL LS AND STATES
 THAT THE AVAILABLE FAULT CURRENT IS 62,946 AMPS. PANEL
 LS IS RATED FOR 42,000 AIC. CLARIFY AND/OR CORRECT. FBC
 107.2.1; NEC 110.10, 110.9 (CORRECTION NOT SHOWN ON
 PLAN.)
 6. EMERGENCY LIGHT IN BATHROOM SHOULD BE ON SAME
 CIRCUIT AS THE LIGHTING IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F) (CORRECTION NOT SHOWN ON
 PLAN.)
 7. CORRECTED.
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-03 Cont ID  
Sent By jpearson Date 2017-11-03 Time 13:50 Rev Time 0.00
Received By jpearson Date 2017-11-03 Time 13:50 Sent To I
Notes
2017-11-03 13:50:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE
 CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH
 CODE. FBC CE 405.5
 2. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE FOR THE SALES FLOOR
 AREA. FBC CE 405.2.2, 405.2.2.2
 3. PROVIDE REQUIRED SHOW WINDOW OUTLET ON DEDICATED
 CIRCUIT WITH AUTOMATIC CONTROL PER ENERGY CODE. NEC
 210.62, FBC CE 405.2.2
 4. TIME CLOCK SPECIFIED IS NOT ASTRONOMICAL TYPE.
 ENERGY CODE STATES: "LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH. LIGHTING DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN
 ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMMING AND
 THE TIME SETTING DURING LOSS OF POWER FOR A PERIOD OF
 AT LEAST 10 HOURS. FBC CE 405.2.4" PROVIDE CORRECTION.
 5. RISER DIAGRAM SHOWS NOTE 3 IN PANEL LS AND STATES
 THAT THE AVAILABLE FAULT CURRENT IS 62,946 AMPS. PANEL
 LS IS RATED FOR 42,000 AIC. CLARIFY AND/OR CORRECT. FBC
 107.2.1; NEC 110.10, 110.9
 6. EMERGENCY LIGHT IN BATHROOM SHOULD BE ON SAME
 CIRCUIT AS THE LIGHTING IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
 7. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS,
 FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS,
 WALK-IN COOLERS, HOODS, ETC. FBC 105.1, 107.2.1
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-02-12 Cont ID  
Sent By pleduc Date 2018-02-12 Time   Rev Time 0.00
Received By pleduc Date 2018-02-12 Time 11:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-10-19 Cont ID  
Sent By pleduc Date 2017-10-19 Time   Rev Time 0.00
Received By pleduc Date 2017-10-18 Time 17:05 Sent To  
Notes
2017-10-19 09:35:27THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-04-02 Cont ID  
Sent By ppetty Date 2018-04-02 Time 14:25 Rev Time 0.00
Received By ppetty Date 2018-03-29 Time 13:10 Sent To  
Notes
2018-03-30 13:11:11RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-03-23 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-20 Time 15:25 Sent To  
Notes
2018-03-21 15:25:15RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-01 Cont ID  
Sent By gjohnson Date 2018-03-01 Time 07:03 Rev Time 0.00
Received By gjohnson Date 2018-02-07 Time 13:25 Sent To  
Notes
2018-02-08 13:25:37B26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-03 Cont ID  
Sent By jpearson Date 2017-11-03 Time 13:50 Rev Time 0.00
Received By jpearson Date 2017-10-16 Time 15:38 Sent To  
Notes
2017-10-17 15:38:38B25

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-10-23 Cont ID  
Sent By jwitmer Date 2017-10-23 Time 11:34 Rev Time 0.00
Received By jwitmer Date 2017-10-23 Time 07:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-02-16 Cont ID  
Sent By ccole Date 2018-02-16 Time 08:10 Rev Time 0.00
Received By ccole Date 2018-02-15 Time 17:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-10-31 Cont ID  
Sent By ccole Date 2017-10-31 Time 11:19 Rev Time 0.00
Received By ccole Date 2017-10-31 Time 11:19 Sent To  
Notes
2017-10-31 11:45:351ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17100607
 10/31/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 LENNOX AC SYSTEM- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION AND SECTION 312.1 FBC-14 MECHANICAL.
  
 2) SHEETS S-1 & M-4: INDICATE HOW THE NEW RTU CURB WILL
 BE ATTACHED TO THE STRUCTURE- SECTION 301.15.
  
 3) M-4: INDICATE FROM WHICH CODE OR STANDARD THE DUCT
 HANGER TABLE, AND THE DUCT FITTING AND CONNECTION
 DETAILS WERE DERIVED FROM.
  
 4) A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR THE
 REFRIGERATION SYSTEM- SECTION 107.2.1 WPB AMENDMENTS TO
 THE FBC
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-03-01 Cont ID  
Sent By gjohnson Date 2018-03-01 Time 07:02 Rev Time 0.00
Received By gjohnson Date 2018-03-01 Time 07:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-10-30 Cont ID  
Sent By gjohnson Date 2017-10-30 Time 07:55 Rev Time 0.00
Received By gjohnson Date 2017-10-29 Time 12:56 Sent To  
Notes
***NONE***