| 2017-10-23 11:34:32 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17100607 |
| | ADD: 831 VILLAGE BLVD. SUITE: |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: 954-914-9848 |
| | E-MAIL: ???????? NO E-MAIL ADDRESS PROVIDED. |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. OCT. 23/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) IS THERE A SUITE NUMBER FOR THIS TENANT SPACE, NOT |
| | PROVIDED ON THE PERMIT APPLICATION NOR THE HEADER STRIP |
| | OF PLANS? |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED. |
| | |
| | 2014 FBC-B 01.2 ADDRESS IDENTIFICATION. NEW AND |
| | EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED |
| | ADDRESS IDENTIFICATION. |
| | |
| | 2) THE LS1 SHEET SHOWS THE COMMON WALL BETWEEN THE |
| | PUBLIX GROCERY STORE AND THE NEW PUBLIX WINE & SPIRITS |
| | TENANT AS AN EXISTING 2 HOUR FIRE RATED WALL. SHEET A-4 |
| | DETAIL C3 INDICATES THE USE OF A 1 ? HOUR FIRE RATED |
| | ACCESS DOOR ON EACH SIDE OF THE NEW PENETRATION IN THE |
| | FIRE RATED WALL. IN THIS SAME DETAIL IT STATES 1 HOUR |
| | RATED FROM EACH SIDE. THE UL LISTING U-901 PROVIDED IN |
| | THE LS SHEET IS FOR A 4 HOUR FIRE RATED WALL WHICH WILL |
| | REQUIRE A 3 HOUR OPENING PROTECTIVE. DISCREPANCY, IN |
| | PLANS, 107.2.1.3 ADDITIONAL DATA. PLEASE PROVIDE ALL |
| | DETAILS TO BE CONSISTENT. |
| | |
| | 3) THE LS1 SHEET INDICATES THE REQUIREMENT FOR 2 EXITS. |
| | THE PLANS SHOW THE FRONT EXIT AND THE REAR GOING |
| | THROUGH A STORAGE OR STOCK ROOM, THE PLANS DO NOT |
| | DECLARE USAGE. PLEASE PROVIDE COMPLIANCE WITH: |
| | 2014 FLORIDA BUILDING CODE 1014.2 EGRESS THROUGH |
| | INTERVENING SPACES. |
| | 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH |
| | STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE |
| | FOLLOWING ARE MET: |
| | 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS |
| | THAT FOUND IN THE MAIN RETAIL AREA; |
| | 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS |
| | THROUGH THE STOCKROOM; |
| | 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE |
| | EGRESS SIDE; AND |
| | 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118 |
| | MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED |
| | WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE |
| | REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA |
| | TO THE EXIT WITHOUT OBSTRUCTIONS. |
| | |
| | 4) SHEET A-1 NOTE 24 INDICATES THE INSTALLATION OF 9/16 |
| | INCH GLASS ON DOOR. SHEET A-4 DETAIL D4/A-4 INDICATES A |
| | NEW STOREFRONT GLAZING SYSTEM, DOOR AND FRAME IS TO BE |
| | INSTALLED. PLEASE PROVIDE CONSISTENT DETAILS. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. IF A NEW STOREFRONT |
| | GLAZING SYSTEM IS TO BE INSTALLED PLEASE COMPLY WITH: |
| | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | |
| | 4A) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 4B) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 5A) SHEET S-1 INDICATES THE WIND DESIGN CRITERIA AS 170 |
| | VULT, C EXPOSURE, RISK CAT. II AND ENCLOSED BUILDING. |
| | WHAT IS MISSING IS THE MEAN ROOF HEIGHT PER TABLE |
| | 1609.7.2 HEIGHT AND EXPOSURE OF THE FBC-B. |
| | |
| | 5B) SHEET S-1 DOES PROVIDE A PRESSURE CHART FOR |
| | BUILDING ZONES 1-5. THE CHART DOES NOT INDICATE IF THE |
| | PRESSURES ARE IN VULT OR VASD, NEED THE MEAN ROOF |
| | HEIGHT, NOR DO THEY PROVIDE THE TRIBUTARY AREA THEY ARE |
| | CALCULATED FOR, NOT ENOUGH INFORMATION. 107.2.1.3. |
| | |
| | 6A) SHEET S-1 DETAIL A-5 PROVIDES A NEW A/C CURB CUT |
| | AND INSTALLATION OF CURB AND ATTACHMENT TO THE ROOF |
| | FRAMING SYSTEM BUT NOT THE CURB TO THE UNIT ITSELF. THE |
| | MECHANICAL SHEET M4 DETAIL C4 PROVIDES A DETAIL AND Z |
| | CLIP (2) PER LONG SIDE WITH ANCHORS BUT THE DETAIL DOES |
| | NOT INDICATE THE WIND DESIGN CRITERIA IT WAS DESIGNED |
| | FOR. PLEASE SHOW COMPLIANCE WITH 2014 FBC-B 2014 FBC-B |
| | 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL MEMBERS AND |
| | THEIR CONNECTIONS SHALL BE DETERMINED BY METHODS OF |
| | STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM, |
| | GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH |
| | SHORT- AND LONG-TERM MATERIAL PROPERTIES. EVERY |
| | STRUCTURE SHALL BE DESIGNED TO RESIST THE OVERTURNING |
| | EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED IN THIS |
| | CHAPTER. SEE SECTION 1609 FOR WIND LOADS. |
| | |
| | 6B) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS |
| | REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| | INSPECTION. |
| | 2014 FBC-B 2204.1 WELDING |
| | 2014 FBC-B 2204.2 BOLTING. |
| | |
| | 7) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |