Plan Review Details - Permit 17100554
Plan Review Stops For Permit 17100554
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-01-08 Cont ID  
Sent By jwitmer Date 2018-01-08 Time 08:25 Rev Time 0.00
Received By jwitmer Date 2018-01-08 Time 07:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-25 Cont ID  
Sent By jwitmer Date 2017-10-25 Time 10:50 Rev Time  
Received By jwitmer Date 2017-10-25 Time 07:30 Sent To  
Notes
2017-10-25 10:50:512014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17100554
 ADD: 2101 CENTREPARK WEST DR. SUITE: 110
 CONT: DEAN MITCHELL GROUP
 TEL: 561-262-9779
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. OCT. 25/ 2017
 ACTION: DENIED
  
 1) SHEET A3 IDENTIFIES THE WALL TYPE (1/A8), THE
 STORAGE ROOM WALLS WITH A 1 HOUR FIRE RATING, PLEASE
 ALSO LABEL THE WALLS AS REQUIRED IN THE:
 2014 FBC-B 703.7 MARKING AND IDENTIFICATION.
 (3) INCLUDE LETTERING NOT LESS THAN 3 INCHES (76 MM )
 IN HEIGHT WITH A MINIMUM 3/8 INCH (9.5 MM) STROKE IN A
 CONTRASTING COLOR INCORPORATING THE SUGGESTED WORDING.
 ?FIRE AND/OR SMOKE BARRIER?PROTECT ALL OPENINGS? OR
 OTHER WORDING.
  
 2) SHEET A-11 THE LIFE SAFETY PLAN SHOWS THE CAF?, ROOM
 127 WITH 21 SEATS. PLEASE PROVIDE COMPLIANCE WITH
 SECTION 226.1 OF THE ACCESSIBILITY CODE. 1 WHERE DINING
 SURFACES ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR
 DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES AND
 STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902. 21 X 0.05= 1.05 YOU ALWAYS ROUND UP OR (2)
 ACCESSIBLE SEATS.
  
 3) SHEET A-11 THE LIFE SAFETY SHEET AND SHEET A-5
 DETAILS 2, 4 & 5 SHOW HI-TOP SEATING OF 42 INCHES TO
 THE TOP. OF THE 2 HI TOPS AND THE COMMON TABLES AT
 LEAST 1 HI-TOP AND 1 TABLE WILL NEED TO COMPLY WITH:
  
 902.1 .DINING SURFACES AND WORK SURFACES SHALL COMPLY
 WITH 902.2 AND 902.3. ADVISORY 902.1 DINING SURFACES
 INCLUDE, BUT ARE NOT LIMITED TO, BARS, TABLES, LUNCH
 COUNTERS, AND BOOTHS. EXAMPLES OF WORK SURFACES INCLUDE
 WRITING SURFACES, STUDY CARRELS, STUDENT LABORATORY
 STATIONS, BABY CHANGING AND OTHER TABLES OR FIXTURES
 FOR PERSONAL GROOMING, COUPON COUNTERS, AND WHERE
 COVERED BY THE ABA SCOPING PROVISIONS, EMPLOYEE WORK
 STATIONS.
  
 3)(A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 3)(B) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4) SHEET A6 DETAIL # 10 THE REAR ELEVATION. THE REAR
 GRAB BAR IS DIMENSIONED TO START AT 3 INCHES FROM THE
 WALL. PLEASE NOTE IN THE ACCESSIBILITY CODE SECTION
 604.5.2 THE REAR GRAB BAR NEEDS TO MEET BOTH OF THESE
 REQUIREMENTS THE SHORT END OF THE GRAB BAR MUST BE 12
 INCHES MINIMUM OF THE CENTERLINE OF THE WATER CLOSET
 AND THE LONG END A MINIMUM OF 2 FEET PAST THE
 CENTERLINE OF THE CENTERLINE OF THE WATER CLOSE.
 TO CORRECT THIS, YOU CAN EITHER MOVE THE GRAB BAR TO
 START 6 INCHES FROM THE WALL THEN THE 3-0 FOOT GRAB BAR
 WILL WORK OR TO KEEP THE GRAB BAR STARTING 3 INCHES
 FROM THE WALL THEN THE OVERALL LENGTH WOULD NEED TO BE
 A MINIMUM OF 3 FEET 3 INCHES TO MEET BOTH REQUIREMENTS.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-01-03 Cont ID  
Sent By jpearson Date 2018-01-03 Time 08:14 Rev Time 0.00
Received By jpearson Date 2018-01-03 Time 07:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-15 Cont ID  
Sent By jpearson Date 2017-11-15 Time 16:02 Rev Time 0.00
Received By jpearson Date 2017-11-15 Time 16:02 Sent To  
Notes
2017-11-15 16:02:01CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS THAT THERE ARE 200 AMP FEEDS TO
 PANELS LA, LB, LC, AND LD. HOWEVER, THESE PANELS ARE
 LISTED AS 100 AMP MAIN LUG ONLY PANELS, WITH MANY
 PHASES SHOWING A LOAD OF MORE THAN 100 AMPS. THIS MAY
 BE A TYPO IN THE PANEL SCHEDULE. CLARIFY AND/OR
 CORRECT. FBC 107.2.1
 2. PANEL LA-2,4,6 SHOWS A 100 AMP EXISTING CIRCUIT, BUT
 NO LOAD IS SHOWN FOR THIS IN THE PANEL SCHEDULE.
 CLARIFY AND/OR CORRECT. FBC 107.2.1, NEC 220
 3. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. NEC 210.63
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-12-13 Cont ID  
Sent By pleduc Date 2017-12-13 Time   Rev Time 0.00
Received By pleduc Date 2017-12-12 Time 12:34 Sent To  
Notes
2017-12-13 09:38:192ND REVIEW COMMENTS:
  
 PREVIOUS PROVISO COMMENTS RESTATED.
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET E 2.1 - PLEASE ADD AN EXIT LIGHT AT THE REAR
 DDOR OF THE OPEN OFFICE 124, DUE TO THE LOW HEADER
 OBSTRUCTING THE EXIT SIGN OVER THE DOOR.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-10-18 Cont ID  
Sent By pleduc Date 2017-10-18 Time   Rev Time 0.00
Received By pleduc Date 2017-10-18 Time 13:06 Sent To  
Notes
2017-10-18 15:15:32THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET E 2.1 - PLEASE ADD AN EXIT LIGHT AT THE REAR
 DDOR OF THE OPEN OFFICE 124, DUE TO THE LOW HEADER
 OBSTRUCTING THE EXIT SIGN OVER THE DOOR.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-01-08 Time   Rev Time 0.00
Received By lmarchan Date 2017-12-08 Time 15:32 Sent To  
Notes
2017-12-11 15:32:57C12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-17 Cont ID  
Sent By gjohnson Date 2017-11-17 Time 10:18 Rev Time 0.00
Received By gjohnson Date 2017-10-13 Time 09:12 Sent To  
Notes
2017-10-17 09:12:33C10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-10-25 Cont ID  
Sent By jwitmer Date 2017-10-25 Time 10:51 Rev Time 0.00
Received By jwitmer Date 2017-10-25 Time 09:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-12-27 Cont ID  
Sent By ccole Date 2017-12-27 Time 16:33 Rev Time 0.00
Received By ccole Date 2017-12-27 Time 16:24 Sent To  
Notes
2017-12-27 16:51:36MECHANICAL PROVISO:
  
 WIND LOAD ENGINEERING FOR TIE DOWN OF THE ROOF TOP
 CONDENSERS WILL BE A DEFERRED SUBMITTAL AS REQUESTED BY
 THE ARCHITECT OF RECORD.
 HOLD PLACED ON CO.
  
 CCOLE- 12/27/17

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-13 Cont ID  
Sent By ccole Date 2017-11-13 Time 11:41 Rev Time 0.00
Received By ccole Date 2017-11-13 Time 10:22 Sent To  
Notes
2017-11-13 12:10:511ST REVIEW FBC-2014 MECHANICAL, WPB AMENDMENTS TO THE
 FBC.
 PERMIT #17100554
 11/13/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR
 SYSTEMS OF THE 5-TON AC SYSTEMS PER SECTION 606.2.1.
 PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE
 MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS ARE NOT
 CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
 2) THREE DIFFUSERS IN CAFE 127 ARE NOT TAGGED- SECTION
 107.1
  
 3) THE KW OF THE HEAT STRIPS IN AHU'S 2, 3, 4, 5, 7, 8,
 9, 10 & 11 ARE EXCEEDING THE CALCULATED LOADS- SECTION
 C403.2.2 FBC-14 ENERGY CONSERVATION.
  
 4) ONE OF THE TWO SETS OF ENERGY AND AC CALCULATIONS IS
 MISSING CALCULATIONS FOR SYSTEMS 5-11- SECTION 107.1.
  
 5) THE REQUIRED WIND LOAD ENGINEERING FOR THE ROOFTOP
 CONDENSERS AND STANDS WAS NOT PROVIDED. PLEASE PROVIDE
 THE DESIGN CRITERIA AND PRESSURES ON THE PLANS, AND
 SUBMIT THE NOA FOR THE ROOF STAND WITH SHOP DRAWING
 APPROVAL STAMP BY THE ENGINEER OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-01-04 Cont ID  
Sent By gjohnson Date 2018-01-04 Time 09:16 Rev Time 0.00
Received By gjohnson Date 2018-01-04 Time 06:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-11-17 Cont ID  
Sent By gjohnson Date 2017-11-17 Time 09:48 Rev Time 0.00
Received By gjohnson Date 2017-11-16 Time 14:08 Sent To  
Notes
2017-11-17 10:18:281ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A-3 THE CALCULATIONS OF THE MINIMUM NUMBER OF
 PLUMBING FIXTURES ARE INCORRECT IT SHALL BE TOTAL
 OCCUPANT LOAD 135 = 67.5 MEN, 67.5 WOMEN = 3 WC MEN, 3
 WC WOMEN, 2 LAV MEN, 2 LAV WOMEN PLEASE CORRECT. PER
 FBC PL SEC 403.1.1 AND TABLE 403.1
  
 2. TOILET PAPER DISPENSERS SHALL BE 7 INCHES MINIMUM
 AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. PER FBC
 ACC 604.7
  
 3. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE. PER FBC ACC 604.5.2
  
 4. PLEASE SHOW CLEAR FLOOR SPACE, HEIGHT AND DEPTH FOR
 ACCESSIBLE URINAL. PER FBC ACC 213.3.3, 605.2 AND 605.3
  
 5. THE WALLS AROUND THE URINAL AND MOP SINK SHALL
 COMPLY WITH FBC 1210.2.2
  
 6. A BACKFLOW IS REQUIRED ON THE WATER SUPPLY'S FOR THE
 ICE MACHINE AND REFRIGERATOR ICE MACHINE. PER FBC PL
 608.3
  
 7. THE NEW WC AND FLOW DRAIN FOR ICE MACHINE SHALL BE
 VENTED. PER FBC PL 901.2, 901.2.1
  
 8.PLEASE LABEL THE HOT, COLD AND RETURN ON WATER
 ISOMETRIC. PER WPB AMEND TO FBC 107.2.1
  
 9. PLEASE LABEL PIPE SIZES ON THE DRAIN LINES FOR THE
 NEW KITCHEN AND FD. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  