Plan Review Details - Permit 17100530
| Plan Review Stops For Permit 17100530 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-12-01 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-11-29 |
Time |
12:57 |
Sent To |
|
|
| Notes |
| 2017-11-30 12:57:30 | RESUB ROUTED TO CCOLE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-11-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-11-16 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2017-11-20 11:35:21 | RESUB ROUTED TO CCOLE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-11-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-11-13 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-11-13 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2017-11-13 16:08:31 | RESUB ROUTED TO CCOLE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-10-24 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-10-13 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2017-10-16 10:31:35 | MECH <5K |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2017-12-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-12-01 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-12-01 |
Time |
11:34 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2017-11-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-11-21 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-11-21 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2017-11-21 13:33:46 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #17100530 | | | 11/16/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | COMMENTS 2-4 FROM THE 2ND REVIEW STILL EXISTS. THE | | | COMMENTS ARE REPRINTED BELOW-PLEASE COMPLY | | | | | | 1) TWO DIFFERENT SETS OF AC PLANS AND ENERGY | | | CALCULATIONS ARE IN THIS PERMIT SUBMITTAL. THE | | | CONTRACTOR MUST VOID OUT WHICHEVER SET OF PLANS AND | | | CALCULATIONS ARE TO BE DISCARDED. | | | | | | 2) PLEASE NOTE THAT THE OWNER/AGENT'S SIGNATURE SHALL | | | BE ON THE ENERGY COMPLIANCE FORM R405-2014- SECTION | | | R103.1.1.2. | | | | | | 3) THE AC PLAN BY KO ENERGY IS INDICATING A MIAMI-DADE | | | NOA OR FL. PRODUCT APPROVAL FOR CONDENSER CLIPS IS TO | | | BE PROVIDED HOWEWER THE SUBMITTAL FROM ENGINEERING | | | EXPRESS IS NEITHER ONE, AND THE DOCUMENT ALSO REQUIRES | | | A RAISED SEAL TO BE VALID AS NOTED ON THE 1ST SHEET. | | | | | | 4) NO ELECTRICAL PLAN OR SUB-PERMIT WAS SUBMITTED. IF | | | TO BE UNDER SEPARATE PERMIT PLEASE INDICATE ON THE | | | PLAN. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2017-11-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-11-16 |
Time |
10:05 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-11-16 |
Time |
10:05 |
Sent To |
|
|
| Notes |
| 2017-11-16 10:19:00 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17100530 | | | 11/16/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) TWO DIFFERENT SETS OF AC PLANS AND ENERGY | | | CALCULATIONS ARE IN THIS PERMIT SUBMITTAL. THE | | | CONTRACTOR MUST VOID OUT WHICHEVER SET OF PLANS AND | | | CALCULATIONS ARE TO BE DISCARDED. | | | | | | 2) PLEASE NOTE THAT THE OWNER/AGENT'S SIGNATURE SHALL | | | BE ON THE ENERGY COMPLIANCE FORM R405-2014- SECTION | | | R103.1.1.2. | | | | | | 3) THE AC PLAN BY KO ENERGY IS INDICATING A MIAMI-DADE | | | NOA OR FL. PRODUCT APPROVAL FOR CONDENSER CLIPS IS TO | | | BE PROVIDED HOWEWER THE SUBMITTAL FROM ENGINEERING | | | EXPRESS IS NEITHER ONE, AND THE DOCUMENT ALSO REQUIRES | | | A RAISED SEAL TO BE VALID AS NOTED ON THE 1ST SHEET. | | | | | | 4) NO ELECTRICAL PLAN OR SUB-PERMIT WAS SUBMITTED. IF | | | TO BE UNDER SEPARATE PERMIT PLEASE INDICATE ON THE | | | PLAN. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-10-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-10-24 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-10-24 |
Time |
09:43 |
Sent To |
|
|
| Notes |
| 2017-10-24 09:57:24 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17100530 | | | 10/24/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE AC CONTRACTORS SIGNATURE MUST BE ON THE PLANS: | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN- SECTION 107.2.1 | | | FBC. WPB AMENDMENTS TO THE FBC. | | | | | | 2) INDICATE HOW AIR IS BEING RETURNED TO THE AIR | | | HANDLER. IS THIS AN OPEN RETURN THOUGH THE KITCHEN OR | | | WILL A RETURN GRILL BE INSTALLED IN THE HALLWAY. PLEASE | | | NOTE THAT RETURN AIR CANNOT BE TAKEN FROM A KITCHEN- | | | SECTION 918.6. | | | | | | 3) THE 6X8 TRANSFER GRILLS IN THE BEDROOMS ARE | | | UNDERSIZED PER SECTION 601.5 EXCEPTION #2- 50 SQ. | | | INCHES PER 100 CFM REQUIRED. | | | | | | 4) PROVIDE THE AC EQUIPMENT SCHEDULE ON THE PLAN. | | | | | | 5) PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION 307. | | | | | | 5) PROVIDE AN ELECTRICAL PLAN SUB-PERMIT APPLICATION, | | | AND INCREASE THE $4500.00 VALUE LISTED ON THE MAIN | | | APPLICATION TO COVER THE ADDITIONAL EXPENSE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
|