Plan Review Details - Permit 17100530
Plan Review Stops For Permit 17100530
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2017-12-01 Time   Rev Time 0.00
Received By lmarchan Date 2017-11-29 Time 12:57 Sent To  
Notes
2017-11-30 12:57:30RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-11-21 Time   Rev Time 0.00
Received By lmarchan Date 2017-11-16 Time 11:35 Sent To  
Notes
2017-11-20 11:35:21RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-16 Cont ID  
Sent By ccole Date 2017-11-13 Time 10:06 Rev Time 0.00
Received By ccole Date 2017-11-13 Time 10:21 Sent To  
Notes
2017-11-13 16:08:31RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-10-24 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-13 Time 10:31 Sent To  
Notes
2017-10-16 10:31:35MECH <5K

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-12-01 Cont ID  
Sent By ccole Date 2017-12-01 Time 11:34 Rev Time 0.00
Received By ccole Date 2017-12-01 Time 11:34 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-11-21 Cont ID  
Sent By ccole Date 2017-11-21 Time 13:25 Rev Time 0.00
Received By ccole Date 2017-11-21 Time 13:25 Sent To  
Notes
2017-11-21 13:33:463RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17100530
 11/16/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS 2-4 FROM THE 2ND REVIEW STILL EXISTS. THE
 COMMENTS ARE REPRINTED BELOW-PLEASE COMPLY
  
 1) TWO DIFFERENT SETS OF AC PLANS AND ENERGY
 CALCULATIONS ARE IN THIS PERMIT SUBMITTAL. THE
 CONTRACTOR MUST VOID OUT WHICHEVER SET OF PLANS AND
 CALCULATIONS ARE TO BE DISCARDED.
  
 2) PLEASE NOTE THAT THE OWNER/AGENT'S SIGNATURE SHALL
 BE ON THE ENERGY COMPLIANCE FORM R405-2014- SECTION
 R103.1.1.2.
  
 3) THE AC PLAN BY KO ENERGY IS INDICATING A MIAMI-DADE
 NOA OR FL. PRODUCT APPROVAL FOR CONDENSER CLIPS IS TO
 BE PROVIDED HOWEWER THE SUBMITTAL FROM ENGINEERING
 EXPRESS IS NEITHER ONE, AND THE DOCUMENT ALSO REQUIRES
 A RAISED SEAL TO BE VALID AS NOTED ON THE 1ST SHEET.
  
 4) NO ELECTRICAL PLAN OR SUB-PERMIT WAS SUBMITTED. IF
 TO BE UNDER SEPARATE PERMIT PLEASE INDICATE ON THE
 PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-11-16 Cont ID  
Sent By ccole Date 2017-11-16 Time 10:05 Rev Time 0.00
Received By ccole Date 2017-11-16 Time 10:05 Sent To  
Notes
2017-11-16 10:19:002ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17100530
 11/16/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) TWO DIFFERENT SETS OF AC PLANS AND ENERGY
 CALCULATIONS ARE IN THIS PERMIT SUBMITTAL. THE
 CONTRACTOR MUST VOID OUT WHICHEVER SET OF PLANS AND
 CALCULATIONS ARE TO BE DISCARDED.
  
 2) PLEASE NOTE THAT THE OWNER/AGENT'S SIGNATURE SHALL
 BE ON THE ENERGY COMPLIANCE FORM R405-2014- SECTION
 R103.1.1.2.
  
 3) THE AC PLAN BY KO ENERGY IS INDICATING A MIAMI-DADE
 NOA OR FL. PRODUCT APPROVAL FOR CONDENSER CLIPS IS TO
 BE PROVIDED HOWEWER THE SUBMITTAL FROM ENGINEERING
 EXPRESS IS NEITHER ONE, AND THE DOCUMENT ALSO REQUIRES
 A RAISED SEAL TO BE VALID AS NOTED ON THE 1ST SHEET.
  
 4) NO ELECTRICAL PLAN OR SUB-PERMIT WAS SUBMITTED. IF
 TO BE UNDER SEPARATE PERMIT PLEASE INDICATE ON THE
 PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-10-24 Cont ID  
Sent By ccole Date 2017-10-24 Time 09:43 Rev Time 0.00
Received By ccole Date 2017-10-24 Time 09:43 Sent To  
Notes
2017-10-24 09:57:241ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17100530
 10/24/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC CONTRACTORS SIGNATURE MUST BE ON THE PLANS:
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN- SECTION 107.2.1
 FBC. WPB AMENDMENTS TO THE FBC.
  
 2) INDICATE HOW AIR IS BEING RETURNED TO THE AIR
 HANDLER. IS THIS AN OPEN RETURN THOUGH THE KITCHEN OR
 WILL A RETURN GRILL BE INSTALLED IN THE HALLWAY. PLEASE
 NOTE THAT RETURN AIR CANNOT BE TAKEN FROM A KITCHEN-
 SECTION 918.6.
  
 3) THE 6X8 TRANSFER GRILLS IN THE BEDROOMS ARE
 UNDERSIZED PER SECTION 601.5 EXCEPTION #2- 50 SQ.
 INCHES PER 100 CFM REQUIRED.
  
 4) PROVIDE THE AC EQUIPMENT SCHEDULE ON THE PLAN.
  
 5) PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION 307.
  
 5) PROVIDE AN ELECTRICAL PLAN SUB-PERMIT APPLICATION,
 AND INCREASE THE $4500.00 VALUE LISTED ON THE MAIN
 APPLICATION TO COVER THE ADDITIONAL EXPENSE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  