Plan Review Details - Permit 17100493
Plan Review Stops For Permit 17100493
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-11-22 Cont ID  
Sent By cthroop Date 2017-11-22 Time 16:51 Rev Time 0.00
Received By cthroop Date 2017-11-21 Time 09:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-11-01 Cont ID  
Sent By jpearson Date 2017-11-01 Time 07:56 Rev Time 0.00
Received By jpearson Date 2017-11-01 Time 07:56 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-11-03 Cont ID  
Sent By destabro Date 2017-11-03 Time 13:31 Rev Time 0.00
Received By destabro Date 2017-11-03 Time 13:31 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-12-15 Cont ID  
Sent By skennedy Date 2017-12-15 Time 16:06 Rev Time 0.00
Received By skennedy Date 2017-12-13 Time 13:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-11-30 Time   Rev Time 0.00
Received By lmarchan Date 2017-11-27 Time 15:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-22 Cont ID  
Sent By cthroop Date 2017-11-22 Time 16:51 Rev Time 0.00
Received By cthroop Date 2017-10-18 Time 12:37 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-12-15 Cont ID  
Sent By skennedy Date 2017-12-15 Time 16:06 Rev Time 0.00
Received By skennedy Date 2017-12-15 Time 16:06 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-11-22 Cont ID  
Sent By cthroop Date 2017-11-22 Time 16:49 Rev Time 0.00
Received By cthroop Date 2017-11-21 Time 09:20 Sent To  
Notes
2017-11-22 16:50:58BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE FLOOR PLAN WITH PALM BEACH COUNTY IMPACT FEE
 OFFICE STAMP WITH AMOUNT PAID.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-12-15 Cont ID  
Sent By skennedy Date 2017-12-15 Time 16:06 Rev Time 0.00
Received By skennedy Date 2017-12-15 Time 16:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-11-30 Cont ID  
Sent By ccole Date 2017-11-30 Time 16:03 Rev Time 0.00
Received By ccole Date 2017-11-30 Time 16:03 Sent To  
Notes
2017-11-30 16:09:072ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17100493
 11/30/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE OWNER OR AGENT MUST SIGN AND DATE THE ENERGY
 FORM R405-2014.
  
 2) THE PLAN SHOWS AN OUTSIDE AIR DUCT FOR THE AC
 SYSTEM. PLEASE PROVIDE THE COMPLIANCE DATA FOR
 MECHANICAL VENTILATION ON PAGE 4 OF ENERGY FORM
 R405-2014.
  
 3) PLEASE SUBMIT THE FLORIDA PRODUCT APPROVAL FOR THE
 BMP CONDENSER TIE-DOWN CLIPS.
  
 4) THE AC CALCULATIONS ARE BASED ON THE FRONT DOOR
 FACING NORTH, HOWEVER HE SITE PLAN INDICATES THE FRONT
 DOOR OF THE HOUSE FACES SOUTH- PLEASE CORRECT THE
 CALCULATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-22 Cont ID  
Sent By ccole Date 2017-11-22 Time 12:12 Rev Time 0.00
Received By ccole Date 2017-11-22 Time 12:12 Sent To  
Notes
2017-11-22 12:31:071ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL, ENERGY
 CONSERVATION
 PERMIT #17100493
 11/22/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEM- SECTION R403.6.1 FBC-14 ENERGY CONSERVATION.
  
 2) COMPLIANCE WITH THE RESIDENTIAL PROVISION OF THE
 ENERGY CODE IS REQUIRED PER SECTION R101.5. BECAUSE THE
 AIR HANDLER IS TO BE LOCATED IN THE ATTIC, THE NEW HOME
 CANNOT BE BROUGHT INTO COMPLIANCE USING FORM R402 WHICH
 IS THE PRESCRIPTIVE METHOD - SEE SECTION R403.2.4.
 THEREFORE THE PERFORMANCE BASED METHOD SHALL BE APPLIED
 USING THE ENERGYGAUGE R405-2014 SOFTWARE PRINTOUT.
 PLEASE SUBMIT THE COMPLIANCE REPORT.
  
 3) SUBMIT THE FLORIDA PRODUCT APPROVAL FOR THE BMP
 CONDENSER TIE-DOWN CLIPS.
  
 4) PLEASE VERIFY COMPLIANCE WITH THE FOLLOWING
 PROVISIONS OF SECTION R403.2.4 AIR HANDLING UNITS:
  
 AIR HANDLING UNITS SHALL NOT BE INSTALLED IN THE ATTIC
 WHEN A HOME IS BROUGHT INTO CODE COMPLIANCE BY SECTION
 R402. AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS FOR
 COMPLIANCE BY SECTION R405 ONLY IF THE FOLLOWING
 CONDITIONS ARE MET:
  
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
  
 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE
 UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
  
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
  
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD.
  
 5) PLEASE NOTE THAT A BLOWER DOOR TEST IS MANDATORY.
 PLEASE REVIEW SECTION R405.4.1.2 FOR MORE INFORMATION
 ABOUT TESTING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-10-19 Cont ID  
Sent By gjohnson Date 2017-10-19 Time 14:54 Rev Time 0.00
Received By gjohnson Date 2017-10-19 Time 14:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-11-03 Cont ID  
Sent By destabro Date 2017-11-03 Time 13:31 Rev Time 0.00
Received By destabro Date 2017-11-03 Time 13:31 Sent To B
Notes
***NONE***