Plan Review Details - Permit 17100471
Plan Review Stops For Permit 17100471
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-07-10 Cont ID  
Sent By rgathrig Date 2018-07-10 Time 12:05 Rev Time 0.00
Received By rgathrig Date   Time   Sent To  
Notes
2018-07-10 12:05:41PROVISO FOR SOUND TRANSMISSION TEST VERIFICATION WAS
 SUBMITTED/APPROVED UNDER 17110020 (REG)

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-11-01 Cont ID  
Sent By jwitmer Date 2017-11-01 Time 13:38 Rev Time 0.00
Received By jwitmer Date 2017-11-01 Time 13:23 Sent To  
Notes
2017-11-01 13:38:07W. P. B. REVISION: 17100471
 W. P. B. PERMIT: 15111020
 ADD: 1100 S. FLAGLER DR. SUITE: UNIT: 10 D
 CONT: SUFFOLK
 TEL: 561-691-4552 # 103
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 SUBJECT TO FAIR HOUSING!
  
 1ST REVIEW
 DATE: WED. NOV. 01/ 2017
 BUILDING PROVISO
  
 1) SUFFOLK CONSTRUCTION TO CONDUCT SITE TESTING FOR
 COMPLIANCE WITH THE 2010 FBC-B SECTIONS:
 FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FBC-B 2010 1207.2 AIR-BORNE SOUND.
 FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 THE SOUND TESTS WILL BE CONDUCTED ON A 10 INCH CONCRETE
 SLAB UNDER THE MAIN PERMIT (15111020) AND SUBMITTED AS
 SOON AS RESULTS ARE PRINTED AND REVIEWED BY THE
 DESIGNER OF RECORD.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-11-13 Cont ID  
Sent By jleahy Date 2017-11-13 Time 17:29 Rev Time 0.00
Received By jleahy Date 2017-11-13 Time 17:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-10-30 Cont ID  
Sent By pleduc Date 2017-10-30 Time   Rev Time 0.00
Received By pleduc Date 2017-10-30 Time 16:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-13 Cont ID  
Sent By jwitmer Date 2017-12-13 Time 12:29 Rev Time 0.00
Received By jwitmer Date 2017-12-05 Time 16:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-22 Cont ID  
Sent By lmarchan Date 2017-11-22 Time 08:16 Rev Time 0.00
Received By lmarchan Date 2017-10-27 Time 13:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-11-09 Cont ID  
Sent By ccole Date 2017-11-09 Time 11:29 Rev Time 0.00
Received By ccole Date 2017-11-09 Time 09:47 Sent To  
Notes
2017-11-09 11:30:28MECHANICAL PROVISO:
 PRIOR TO ISSUANCE OF CO, THE DESIGN PROFESSIONAL OF
 RECORD SHALL CERTIFY THE APPLICATION OF THE INTUMESCENT
 PAINT ON THE AC CLOSET DOORS.
 CCOLE- 11/9/17
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-12-13 Cont ID  
Sent By jwitmer Date 2017-12-15 Time 12:29 Rev Time 0.00
Received By jwitmer Date 2017-12-13 Time 11:58 Sent To  
Notes
2017-12-13 12:28:582010 FBC- PLUMBING PLAN REVIEW
 W. P. B. REVISION: 17100471
 W. P. B. PERMIT: 15111020
 ADD: 1100 S. FLAGLER DR. / UNIT 10D
 CONT: SUFFOLK
 TEL: 561-832-1616 / JASON KRAUS
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: WED. DEC. 13/ 2017
 ACTION: PASSEDFAIR HOUSING ACT DESIGN MANUAL PAGES
 7.39-7.40
  
 1) PLEASE SEE THE DOOR MAY SWING INTO THE CLEAR FLOOR
 SPACE AT FIXTURES, PROVIDED THERE IS SPACE TO POSITION
 A WHEELCHAIR OUTSIDE THE SWING OF THE DOOR SO IT CAN BE
 CLOSED.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-11-17 Cont ID  
Sent By gjohnson Date 2017-11-17 Time 14:16 Rev Time 0.00
Received By gjohnson Date 2017-11-17 Time 13:10 Sent To  
Notes
2017-11-17 14:30:101ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE REVISE SHT. A0-41 TO SHOW BATHROOM #4 AS THE
 SPEC B BATH PER FHA DESIGN MANUAL
  
 2. WHEN THE DOOR SWINGS INTO THE USABLE BATHROOM IT IS
 REQUIRED TO HAVE A 30" X 48" CLEAR FLOOR SPACE OUTSIDE
 THE ARC OF THE DOOR SWING, THE LAYOUT FOR BATHROOM #4
 IN UNIT 10D SHOWS THIS CLEAR FLOOR SPACE BEHIND THE
 DOOR WHEN IT IS OPEN WHICH DOES NOT ALLOW A PERSON IN A
 WHEELCHAIR TO ACCESS THIS SPACE IN ORDER TO CLOSE THE
 DOOR I SUGGEST THE DOOR TO SWING OUT INTO THE BEDROOM
 IN ORDER TO COMPLY. PER FHA DESIGN MANUAL PG. 7.39
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2017-12-15 Cont ID  
Sent By jwitmer Date 2017-12-15 Time 09:52 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2017-11-17 14:31:42PLUMB DIG SIG OK 11/17/17/ GPJ
2017-11-09 11:38:46MECH DIG/SIGS GOOD- CCOLE-11/9/17
2017-11-01 13:39:1411/01/2017. ARCHITECTURAL SHEETS REVIEWED FOR DIGITAL
 SIGNATURES. OK. JW