| 2017-10-27 10:59:55 | ****PLAN REVIEW COMMENTS**** |
| | |
| | ART LANGE - BUILDING INSPECTOR |
| | 561-805-6667 [email protected] |
| | FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA |
| | RESIDENTIAL CODE 2015 5TH EDITION |
| | |
| | 1. PLEASE SHOW ON PLANS THE LEVEL OF ALTERATION PER FBC |
| | EXISTING BUILDING CODE 2014. 501.1 SCOPE. |
| | THE PROVISIONS OF THIS CHAPTER SHALL BE USED IN |
| | CONJUNCTION WITH CHAPTERS 6 THROUGH 13 AND SHALL APPLY |
| | TO THE ALTERATION, REPAIR, ADDITION AND CHANGE OF |
| | OCCUPANCY OF EXISTING STRUCTURES, INCLUDING HISTORIC |
| | AND MOVED STRUCTURES, AS REFERENCED IN SECTION 301.1.2. |
| | THE WORK PERFORMED ON AN EXISTING BUILDING SHALL BE |
| | CLASSIFIED IN ACCORDANCE WITH THIS CHAPTER. |
| | |
| | 2. PROVIDE THE WIND DESIGN DATA, FBC 1603.1.4 WIND |
| | DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCERESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | 2. RISK CATEGORY. |
| | 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. |
| | 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF |
| | (KN/M2). |
| | |
| | 3. SHOW THE TYPE OF CONSTRUCTION CLASSIFICATION. FBC |
| | 602 |
| | |
| | 4. SPECIFY ROOFING PRODUCT USED AND PROVIDE 2 COPIES OF |
| | PRODUCT APPROVALS. FAC9N-3 |
| | FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. |
| | |
| | 5. SEE DETAIL KEY LEGEND #18 AND SHOW COMPLIANCE WITH |
| | FBC- R703.6.3 STUCCO |
| | WHERE CEMENT PLASTER (STUCCO) IS TO BE APPLIED TO LATH |
| | OVER FRAME CONSTRUCTION, MEASURES SHALL BE TAKEN TO |
| | PREVENT BONDING BETWEEN THE CEMENT PLASTER AND THE |
| | WATER-RESISTIVE BARRIER: TWO LAYERS OR ONE LAYER OF AN |
| | APPROVED WATER-RESISTANT BARRIER OVER AN APPROVED |
| | PLASTIC HOUSE WRAP, OR OTHER APPROVED METHODS IN |
| | ACCORDANCE WITH THE MANUFACTURER?S INSTALLATION |
| | INSTRUCTIONS. |
| | _______________________________________________________ |
| | __________________ |
| | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| | THE PERMIT PACKAGE. |
| | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| | |
| | |