Plan Review Details - Permit 17100351
Plan Review Stops For Permit 17100351
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-12-01 Cont ID  
Sent By pleduc Date 2017-12-01 Time   Rev Time 0.00
Received By pleduc Date 2017-12-01 Time 10:46 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-11-21 Cont ID  
Sent By pleduc Date 2017-11-21 Time   Rev Time 0.00
Received By pleduc Date 2017-11-21 Time 11:04 Sent To M
Notes
2017-11-21 13:27:57THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE PIZZA OVEN AS PROPOSED AND INSTALLED SHALL ONLY
 BE USED TO PREPARE PIZZA. ANY ADDITIONAL FOOD ITEMS
 THAT PRODUCE GREASE LADON VAPORS, INCLUDING, BUT NOT
 LIMITED TO, CHICKEN, CHICKEN WINGS, HAMBURGERS, HOT
 DOGS, AND RIIBS IS NOT APPROVED WITHOUT A INSTALLED
 FIRE SUPPRESSION SYSTEM.
  
 2) FUTURE FINDINGS OF THESE ITEMS OR THE BUILD-UP OF
 GREASE LADON VAPORS TO DANGEROUS LEVELS MAY CAUSE A
 CEASE AND DESIST OF THE PIZZA OVEN USE UNTIL
 CORRECTIONS ARE MADE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-10-11 Cont ID  
Sent By pleduc Date 2017-10-11 Time   Rev Time 0.00
Received By pleduc Date 2017-10-11 Time 15:16 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-12-04 Time   Rev Time 0.00
Received By lmarchan Date 2017-11-29 Time 15:05 Sent To  
Notes
2017-11-30 15:06:01RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-11-28 Time   Rev Time 0.00
Received By lmarchan Date 2017-11-16 Time 13:43 Sent To I
Notes
2017-11-20 13:43:54RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-10-27 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-10 Time 10:55 Sent To  
Notes
2017-10-11 10:55:58ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-12-04 Cont ID  
Sent By ccole Date 2017-12-04 Time 13:15 Rev Time 0.00
Received By ccole Date 2017-12-04 Time 13:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-11-27 Cont ID  
Sent By ccole Date 2017-11-27 Time 17:05 Rev Time 0.00
Received By ccole Date 2017-11-27 Time 17:05 Sent To I
Notes
2017-11-27 17:23:092ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17100351
 11/27/17
  
 THE PLANS HAVE BEEN FAILED FOR A SECOND TIME DUE TO THE
 FOLLOWING OMMISSIONS AND DEFICIENCIES.
  
 1) SHEETS "DUCT" AND "DUCT-2": THE REVISED DRAWINGS DO
 NOT SHOW THE DUCT SIZES, SEGMENT LENGTHS, TEES, WYES,
 ETC. THE PREVIOUSLY SUBMITTED SHOP DRAWINGS SUBMITTED
 ON SHEET "DUCT" HAD SPECIFIED ALL COMPONENTS OF THE
 VENT ASSEMBLIES. PLEASE PROVIDE THE DRAWING OR MODIFY
 THE CURRENT DRAWING.
  
 2) SHEET DUCT-2, WIND LOAD ENGINEERING: PROVIDE MISSING
 FASTENING DETAILS- DUCT TO FAN, AND DUCT BRACKET TO
 ROOF STRUCTURE.
  
 3) SHEET DUCT-2, ELEVATION VIEW: THE DRAWING DOES NOT
 SHOW THE FAN AND CURB, AND THE DISCHARGE HEIGHT OF THE
 EXHAUST FAN ABOVE THE ROOF.
  
 4) SHEETS DUCT AND DUCT-2: PROVIDE THE SLOPE OF THE
 DUCT.
  
 5) SUBMIT A CUT SHEET FOR THE CAPTIVE AIRE FANS.
  
 6) THE EXHAUST DUCTS RUNNING THROUGH THE PLENUM ARE NOT
 PERMITTED UNLESS MEETING ONE OF THE EXCEPTIONS LISTED
 UNDER SECTION 601.4. PLEASE VERIFY COMPLIANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-10-26 Cont ID  
Sent By ccole Date 2017-10-26 Time 16:50 Rev Time 0.00
Received By ccole Date 2017-10-26 Time 16:50 Sent To  
Notes
2017-10-26 18:21:271ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17100351
 10/26/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO PAGE 5 OF THE SUBMITTED JERMIAS EXHAUST
 SYSTEM INSTALLATION INSTRUCTIONS FOR MODEL DWKL. THE
 PIZZA OVEN EXHAUST DUCTS ARE REQUIRED TO BE ENCLOSED IN
 NON-COMBUSTIBLE CONSTRUCTION HAVING A FIRE RATING EQUAL
 TO OR GREATER THAN THAT OF THE WALL OR CEILING THROUGH
 WHICH IT PASSES. THE SUBMITTED PLAN DOES NOT DEPICT
 ACTUAL FIELD CONDITIONS BUT THE APPROVED PLANS FOR THE
 RESTAURANT UNDER PERMIT #17020623 APPEAR TO SHOW THE
 DUCTS VERTICALLY PENETRATING THE DRYWALL CEILING, AND
 THEN RUNNING HORIZONTALLY ABOVE THE CEILING TO THE
 FIRE-RATED SHAFT. PROVIDE DRAWINGS AND DETAILS THAT
 INDICATE HOW THE DUCT WILL BE ENCLOSED AS REQUIRED BY
 THE MANUFACTURER AND THE UL 1978 LISTING. PLEASE NOTE
 THAT THE JERMIAS DWKL EXHAUST DUCT BEARS ONLY THE UL
 1978 LISTING WHICH MAKES IT SUITABLE FOR USE AS A
 "GREASE DUCT" BUT DOES NOT HAVE THE UL 2221 LISTING AS
 A GREASE DUCT ENCLOSURE- PLEASE SEE SECTIONS 506.3.1.1
 AND 506.3.11.3 FBC-14 MECHANICAL.
  
 2) REFER TO TABLE 1-2 ON PAGE 5 OF THE INSTRUCTIONS:
 THE EXHAUST DUCTS ARE REQUIRED TO HAVE MINIMUM 2 INCHES
 OF CLEARANCE TO COMBUSTIBLE CONSTRUCTION. PLEASE NOTE
 THAT THE APPROVED M1.1 PLAN SHEET FOR THE RESTAURANT
 UNDER PERMIT #17020623 INDICATES THE GREASE DUCT TO BE
 A "ZERO CLEARANCE". ZERO CLEARANCE DUCTS TYPICALLY HAVE
 THE UL 2221 LISTING WHICH CLASSIFIES THOSE GREASE DUCTS
 AS "ENCLOSURES". PLEASE SUBMT A REVISED M1.1 PLAN SHEET
 THAT SHOWS THE CORRECT EXHAUST DUCTS TPO BE USED.
  
 3) SHOW THE LOCATIONS OF REQUIRED CLEANOUTS ON THE
 VERTICAL AND HORIZONTAL EXHAUST DUCT RUNS, AND PROVIDE
 ACCESS PANEL DETAILS FOR BOTH THE DUCTS AND THE DUCT
 ENCLOSURES- SEE PAGE 6 OF THE INSTALLATION
 INSTRUCTIONSA, AND SECTION 506.3.8 & 506.3.9.
  
 4) THE WIND LOAD ENGINEERING FOR ATTACHING THE GREASE
 DUCTS TO THE ROOF AND THE FANS TO THE DUCTS IS
 INCOMPLETE. THE CALCULATIONS AND ENGINEERING SHOW HOW
 THE FANS AND CURBS WILL BE ATTACHED TO THE STRUCTURE,
 HOWEVER THERE ARE NO DETAILS INDICATING HOW THE FANS
 WILL BE ATTACHED TO THE DUCTS AND HOW THE THE ENTIRE
 ASSEMBLIES INCLUDING THE DUCTS WILL BE ATTACHED TO THE
 ROOF STRUCTURE. PLEASE PROVIDE DETAILS THAT DEPICT THE
 ACTUAL FIELD CONDITIONS.
  
 5) PROVIDE UL TESTED AND APPROVED FIRESTOPPING
 ASSEMBLIES FOR SEALING THE EXHAUST DUCT PENETRATIONS-
 SECTION 506.3.11.3.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  