Plan Review Details - Permit 17100342
Plan Review Stops For Permit 17100342
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-01-26 Cont ID  
Sent By jwitmer Date 2018-01-26 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2018-01-26 Time 06:30 Sent To  
Notes
2018-01-26 07:55:102014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17100342
 ADD: 2701 OKEECHOBEE BLVD.
 CONT: RJS CONSTRUCTION GROUP
 TEL: 561-795-4712
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: FRI. JAN. 26/ 2018
 ACTION: BUILDING PROVISO
  
 1A) DEFERRED SUBMITTAL: NEW 2ND FLOOR EXIT DOOR
 REQUIRES PRODUCT APPROVAL, PLEASE SHOW COMPLIANCE WITH
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31)(A) EXTERIOR DOORS.
  
 1B) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL ADMINISTRATIVE CODE. 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
2018-01-26 07:18:46 
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-12-11 Cont ID  
Sent By jwitmer Date 2017-12-11 Time 07:56 Rev Time 0.00
Received By jwitmer Date 2017-12-11 Time 06:56 Sent To  
Notes
2017-12-11 07:56:212014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17100342
 ADD: 2701 OKEECHOBEE BLVD.
 CONT: RJS CONSTRUCTION GROUP
 TEL: 561-795-4712
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. 11/ 2017
 ORIGINAL STRUCTURE BUILT/ C.O. 1963
 ACTION: DENIED
  
  
 1-2) COMPLIED.
 3) PLEASE NOTE THIS BUILDING WAS BUILT IN 1963 AND WITH
 AN ELEVATOR SINCE A PORTION OF THE BUILDING IS A 4
 STORY BUILDING. THE VALUE OF THIS PERMIT IS STATED AT
 $105,000.00 DOLLARS. WORK IS CURRENTLY ONLY SHOWING ON
 THE 2ND FLOOR LEVEL BUT THE VIOLATION OCCURS ON FLOORS
 2-4, NO AREA OF REFUGE. THE ACCESSIBILITY CODE
 CAN REQUIRE UP TO 20% OF THE CONTRACT VALUE FOR
 ACCESSIBILITY UPGRADES ($21,000.00) SEE :
  
 2014 FBC-EXISTING BUILDING CODE SECTION 806.1
 ABUILDING, FACILITY OR ELEMENT THAT IS ALTERED SHALL
 COMPLY WITH THE PROVISIONS OF THE FLORIDA BUILDING
 CODE, ACCESSIBILITY.
  
 202.4 ALTERATIONS AFFECTING PRIMARY FUNCTION AREAS AND
 SEE IN THE EVENT OF DISPROPORTIONALITY.
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY. WHEN THE COST OF ALTERATIONS
 NECESSARY TO MAKE THE PATH OF TRAVEL TO THE ALTERED
 AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO THE COST
 OF THE OVERALL ALTERATION, THE PATH OF TRAVEL SHALL BE
 MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE MADE
 ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE COSTS. IN
 CHOOSING WHICH ACCESSIBLE ELEMENTS TO PROVIDE, PRIORITY
 SHOULD BE GIVEN TO THOSE ELEMENTS THAT WILL PROVIDE THE
 GREATEST ACCESS, IN THE FOLLOWING ORDER: (I) AN
 ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (III) AT LEAST ONE ACCESSIBLE RESTROOM
 FOR EACH SEX OR A SINGLE UNISEX RESTROOM; (IV)
 ACCESSIBLE TELEPHONES; (V) ACCESSIBLE DRINKING
 FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 ON THE 2ND FLOOR LEVEL THE PLANS DO NOT SHOW AN AREA OF
 REFUGE. THE 2014 ACCESSIBILITY CODE DOES REFER BACK TO
 THE 2003 IBC-B SECTION 1007. 207.1. MEANS OF EGRESS
 SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION) (INCORPORATED BY
 REFERENCE, SEE ?REFERENCED STANDARDS? IN CHAPTER 1).
  
 3A) 2ND REQUEST. 2003 IBC-B 1007.6.1. SIZE. EACH AREA
 OF REFUGE SHALL BE SIZED TO ACCOMMODATE ONE WHEEL CHAIR
 SPACE OF 30 X 48 INCHES FOR EACH 200 OCCUPANTS.
  
 3B) 2ND REQUEST. 2003 IBC-B 1007.6.2. SEPARATION. EACH
 AREA OF REFUGE SHALL BE SEPARATED FROM THE REMAINDER OF
 THE STORY BY A SMOKE BARRIER COMPLYING WITH 709. EACH
 AREA OF REFUGE SHALL BE DESIGNED TO MINIMIZE THE
 INTRUSION OF SMOKE.
  
 3C) 2ND REQUEST. 2003 IBC-B 1007.6 .3 TWO-WAY
 COMMUNICATION. AREAS OF REFUGE SHALL BE PROVIDED WITH
 TWO-WAY COMMUNICATION SYSTEM BETWEEN THE AREA OF REFUGE
 AND A CONTROL POINT. IF THE CENTRAL CONTROL POINT IS
 NOT CONSTANTLY ATTENDED, THE AREA OF REFUGE SHALL ALSO
 HAVE CONTROLLED ACCESS TO A PUBLIC TELEPHONE SYSTEM.
 LOCATION OF THE CENTRAL CONTROL POINT SHALL BE APPROVED
 BY THE FIRE DEPARTMENT. TWO-WAY COMMUNICATION SYSTEM
 SHALL INCLUDE BOTH AUDIBLE AND VISIBLE SIGNALS.
  
 3D)2ND REQUEST. 1007.6.4 INSTRUCTIONS. IN AREAS OF
 REFUGE THAT HAVE A TWO-WAY EMERGENCY COMMUNICATIONS
 SYSTEM, INSTRUCTIONS ON THE USE OF THE AREA UNDER
 EMERGENCY CONDITIONS SHALL BE POSTED ADJOINING THE
 COMMUNICATIONS SYSTEM. THE INSTRUCTIONS SHALL INCLUDE
 ALL OF THE FOLLOWING;
 1) DIRECTIONS TO FIND OTHER MEANS OF EGRESS.
 2) PERSONS ABLE TO USE THE EXIT STAIRWAY DO SO AS SOON
 AS POSSIBLE, UNLESS THEY ARE ASSISTING OTHERS.
 3) INFORMATION ON THE PLANNED AVAILABILITY OF
 ASSISTANCE IN THE USE OF STAIRS OR SUPERVISED OPERATION
 OF ELEVATORS AND HOW TO SUMMON SUCH ASSISTANCE. 4)
 DIRECTIONS FOR THE USE OF THE EMERGENCY COMMUNICATIONS
 SYSTEM.
  
 3E) 2ND REQUEST. 1007.6.5 IDENTIFICATION. EACH DOOR
 PROVIDING ACCESS TO AN AREA OF REFUGE FROM AN ADJACENT
 FLOOR AREA SHALL BE IDENTIFIED BY A SIGN COMPLYING WITH
 ICC A117., STATING AREA OF REFUGE, AND INCLUDING THE
 INTERNATIONAL SYMBOL OF ACCESSIBILITY. WHERE EXIT SIGN
 ILLUMINATION IS REQUIRED BY SECTION 1011.2, THE AREA OF
 REFUGE SIGN SHALL BE ILLUMINATED. ADDITIONALLY, TACTILE
 SIGNAGE COMPLYING WITH ICC A117.1 SHALL BE LOCATED AT
 EACH DOOR TO AN AREA OF REFUGE.
  
 3F) 2ND REQUEST. 1007.7. SIGNAGE. AT EXITS AND
 ELEVATORS SERVING A REQUIRED ACCESSIBLE SPACE BUT NOT
 PROVIDING AN APPROVED ACCESSIBLE MEANS OF EGRESS,
 SIGNAGE SHALL BE INSTALLED INDICATING THE LOCATION OF
 ACCESSIBLE MEANS OF EGRESS.
  
 4-6) COMPLIED.
  
 7) SEMI-COMPLIED. THE NEW HANDRAIL AND GUARDRAIL SYSTEM
 STOPS SHORT OF THE FLOOR LEVEL, BOTH STOP ATOP THE 1ST
 STEP ON THE LEVEL SURFACE. THE PLANS HAVE A NOTE TO
 MAINTAIN 4 FOOT MINIMUM BETWEEN THE TEMPERED GLASS WALL
 AND THE GUARDRAIL/ HANDRAIL. PLEASE CONSIDER PUTTING
 THE STAIRS BEHIND THE LIFT, SWOOP POSITIONS, THEN THE
 HANDRAIL ARE TO CONTINUE THE SLOPE ONE TREAD DISTANCE
 PAST THE FIRST RISER, NO HORIZONTAL EXTENSION IS
 REQUIRED, THE LIFT IS THE ACCESSIBLE MEANS OF EGRESS TO
 THE UPPER LEVEL. SEE 1012.6 HANDRAILS.
  
 1ST ROUND OF COMMENTS. SHEET A2.0 IN NOTE 10 INDICATES
 A NEW 42 INCH HIGH RAILING, THE PLAN DOES NOT INDICATE
 A GUARD RAIL AND NO INDICATION OF A HANDRAIL.
  
 7A) THE GUARDRAIL IS INDICTED TO START ON TOP OF THE
 FIRST RISER. PLEASE REFER TO THE 2014 FBC-B 1013.3
 HEIGHT. REQUIRED GUARDS SHALL NOT BE LESS THAN 42
 INCHES HIGH, MEASURED VERTICALLY AS FOLLOWS ;
 (1) FROM THE ADJACENT WALKING SURFACE, THE GUARDRAIL
 SHOULD CONTINUE OUT PAST THE STAIR THE WIDTH OF THE
 STAIR.
  
 7B THE NEW EXTERIOR DESIGN DOES NOT INDICATE THE TYPE
 OF STAIR CONCRETE OR STEEL, LIVE LOADS REQUIRED (TABLE
 1607.1) THE HEIGHT OF THE TOTAL RISE, RISE AND RUN OF
 THE TREAD OR RISER NOR THE WIND DESIGN CRITERIA FOR THE
 EXTERIOR STAIR NOR NOTAGE FOR THE REQUIREMENTS FOR THE
 HANDRAILS UNDER FBC-B 1012 OR GUARDS UNDER SECTION 1013
 FOR GUARDS. . PLEASE NOTE THERE IS NO FOUNDATION NOTE
 OR ANCHORING FOR THE NEW EXTERIOR STAIR. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRE.
  
 7C)COMPLIED. SHEET A2.1 DOES SHOW AN APPROVED GUARDRAIL
 SYSTEM FOR THE ROOF TOP EQUIPMENT.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-21 Cont ID  
Sent By jwitmer Date 2017-10-21 Time 09:57 Rev Time 0.00
Received By jwitmer Date 2017-10-21 Time 06:59 Sent To  
Notes
2017-10-21 09:57:062014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17100342
 ADD: 2701 OKEECHOBEE BLVD.
 CONT: RJS CONSTRUCTION GROUP
 TEL: 561-795-4712
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. OCT. 21/ 2017
 ORIGINAL STRUCTURE BUILT/ C.O. 1963
 ACTION: DENIED
  
  
 1) PLEASE VIEW THE ADDRESS ON THE SITE PLAN SHEET A1.0,
 IT STATES OKEECHOBEE ROAD WHERE AS THE PERMIT
 APPLICATION STATES 2701 OKEECHOBEE BLVD. AND THE
 CORRESPONDING PROPERTY CONTROL NUMBER
 74-43-43-19-01-000-0022 ALL INDICATE THE OKEECHOBEE
 BLVD LOCATION AS WELL AS THE PALM BEACH COUNTY
 PICTOMETRY OF THE BUILDING AND SITE LOCATION.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK?
  
 2) PLEASE REFER TO SHEET A2.0 THE EXISTING LOFT, PLEASE
 DEFINE THE OCCUPANCY OF THIS AREA, WORK IS SHOWN TO
 OCCUR IN THIS AREA. THE LOFT AREA STILL IS A 2ND STORY
 MID-LEVEL STORY. THERE ARE 2 CODE SECTIONS TO LOOK AT,
 COMMON PATH OF TRAVEL AND AREAS OF STORIES WITH ONLY
 ONE ACCESS TO AN EXIT.
  
 2A) COMMON PATH OF TRAVEL SEE 2014 FBC-B TABLE 1014.3
 FOR BOTH BUSINESS & STORAGE OCCUPANCIES WHEN THE
 OCCUPANT LOAD IS LESS THAN 30/ NON-SPRINKLERED BUILDING
 IS 100 FEET. THE TRAVEL DISTANCE IN THE FURTHEST POINT
 OF THE LOFT AREA IS APPROXIMATELY 148 FEET TO WHERE YOU
 HAVE A CHOICE OF EXITS. THE OTHER ISSUE IS IF THIS
 SPACE IS TO BE DECLARED AS AN OCCUPANCY THEN THE
 OVERALL DIAGONAL DISTANCE (1/2 OF THE OVERALL DIAGONAL
 IS INCREASED FBC-B 1015.2.1.) WHICH YOU DO NOT HAVE ON
 THIS FLOOR. I DO NOT BELIEVE THIS AREA WAS TO BE USED
 EXCEPT FOR EXCESS TO A/C EQUIPMENT, ATTIC SPACE.
  
 2B) UNDER THE FBC-B TABLE 1021.2(2) STORIES WITH ONE
 EXIT OR ACCESS TO ONE EXIT FOR A SECOND FLOOR FOR
 BUSINESS AND STORAGE OCCUPANCIES IT IS LIMITED TO 75
 FEET AND 29 OCCUPANTS, THE 75 FEET IS A MORE
 RESTRICTIVE REQUIREMENT AND BE THE ONE WE WOULD NEED TO
 USE.
  
 3) PLEASE NOTE THIS BUILDING WAS BUILT IN 1963 AND WITH
 AN ELEVATOR SINCE A PORTION OF THE BUILDING IS A 4
 STORY BUILDING. THE VALUE OF THIS PERMIT IS STATED AT
 $105,000.00 DOLLARS. WORK IS CURRENTLY ONLY SHOWING ON
 THE 2ND FLOOR LEVEL BUT THE VIOLATION OCCURS ON FLOORS
 2-4, NO AREA OF REFUGE. THE ACCESSIBILITY CODE
 CAN REQUIRE UP TO 20% OF THE CONTRACT VALUE FOR
 ACCESSIBILITY UPGRADES ($21,000.00) SEE :
  
 2014 FBC-EXISTING BUILDING CODE SECTION 806.1
 ABUILDING, FACILITY OR ELEMENT THAT IS ALTERED SHALL
 COMPLY WITH THE PROVISIONS OF THE FLORIDA BUILDING
 CODE, ACCESSIBILITY.
  
 202.4 ALTERATIONS AFFECTING PRIMARY FUNCTION AREAS AND
 SEE IN THE EVENT OF DISPROPORTIONALITY.
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY. WHEN THE COST OF ALTERATIONS
 NECESSARY TO MAKE THE PATH OF TRAVEL TO THE ALTERED
 AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO THE COST
 OF THE OVERALL ALTERATION, THE PATH OF TRAVEL SHALL BE
 MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE MADE
 ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE COSTS. IN
 CHOOSING WHICH ACCESSIBLE ELEMENTS TO PROVIDE, PRIORITY
 SHOULD BE GIVEN TO THOSE ELEMENTS THAT WILL PROVIDE THE
 GREATEST ACCESS, IN THE FOLLOWING ORDER: (I) AN
 ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (III) AT LEAST ONE ACCESSIBLE RESTROOM
 FOR EACH SEX OR A SINGLE UNISEX RESTROOM; (IV)
 ACCESSIBLE TELEPHONES; (V) ACCESSIBLE DRINKING
 FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 ON THE 2ND FLOOR LEVEL THE PLANS DO NOT SHOW AN AREA OF
 REFUGE. THE 2014 ACCESSIBILITY CODE DOES REFER BACK TO
 THE 2003 IBC-B SECTION 1007. 207.1. MEANS OF EGRESS
 SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION) (INCORPORATED BY
 REFERENCE, SEE ?REFERENCED STANDARDS? IN CHAPTER 1).
  
 3A) 2003 IBC-B 1007.6.1. SIZE. EACH AREA OF REFUGE
 SHALL BE SIZED TO ACCOMMODATE ONE WHEEL CHAIR SPACE OF
 30 X 48 INCHES FOR EACH 200 OCCUPANTS.
  
 3B) 2003 IBC-B 1007.6.2. SEPARATION. EACH AREA OF
 REFUGE SHALL BE SEPARATED FROM THE REMAINDER OF THE
 STORY BY A SMOKE BARRIER COMPLYING WITH 709. EACH AREA
 OF REFUGE SHALL BE DESIGNED TO MINIMIZE THE INTRUSION
 OF SMOKE.
  
 3C) 2003 IBC-B 1007.6 .3 TWO-WAY COMMUNICATION. AREAS
 OF REFUGE SHALL BE PROVIDED WITH TWO-WAY COMMUNICATION
 SYSTEM BETWEEN THE AREA OF REFUGE AND A CONTROL POINT.
 IF THE CENTRAL CONTROL POINT IS NOT CONSTANTLY
 ATTENDED, THE AREA OF REFUGE SHALL ALSO HAVE CONTROLLED
 ACCESS TO A PUBLIC TELEPHONE SYSTEM. LOCATION OF THE
 CENTRAL CONTROL POINT SHALL BE APPROVED BY THE FIRE
 DEPARTMENT. TWO-WAY COMMUNICATION SYSTEM SHALL INCLUDE
 BOTH AUDIBLE AND VISIBLE SIGNALS.
  
 3D) 1007.6.4 INSTRUCTIONS. IN AREAS OF REFUGE THAT HAVE
 A TWO-WAY EMERGENCY COMMUNICATIONS SYSTEM, INSTRUCTIONS
 ON THE USE OF THE AREA UNDER EMERGENCY CONDITIONS SHALL
 BE POSTED ADJOINING THE COMMUNICATIONS SYSTEM. THE
 INSTRUCTIONS SHALL INCLUDE ALL OF THE FOLLOWING;
 1) DIRECTIONS TO FIND OTHER MEANS OF EGRESS.
 2) PERSONS ABLE TO USE THE EXIT STAIRWAY DO SO AS SOON
 AS POSSIBLE, UNLESS THEY ARE ASSISTING OTHERS.
 3) INFORMATION ON THE PLANNED AVAILABILITY OF
 ASSISTANCE IN THE USE OF STAIRS OR SUPERVISED OPERATION
 OF ELEVATORS AND HOW TO SUMMON SUCH ASSISTANCE. 4)
 DIRECTIONS FOR THE USE OF THE EMERGENCY COMMUNICATIONS
 SYSTEM.
  
 3E) 1007.6.5 IDENTIFICATION. EACH DOOR PROVIDING ACCESS
 TO AN AREA OF REFUGE FROM AN ADJACENT FLOOR AREA SHALL
 BE IDENTIFIED BY A SIGN COMPLYING WITH ICC A117.,
 STATING AREA OF REFUGE, AND INCLUDING THE INTERNATIONAL
 SYMBOL OF ACCESSIBILITY. WHERE EXIT SIGN ILLUMINATION
 IS REQUIRED BY SECTION 1011.2, THE AREA OF REFUGE SIGN
 SHALL BE ILLUMINATED. ADDITIONALLY, TACTILE SIGNAGE
 COMPLYING WITH ICC A117.1 SHALL BE LOCATED AT EACH DOOR
 TO AN AREA OF REFUGE.
  
 3F) 1007.7. SIGNAGE. AT EXITS AND ELEVATORS SERVING A
 REQUIRED ACCESSIBLE SPACE BUT NOT PROVIDING AN APPROVED
 ACCESSIBLE MEANS OF EGRESS, SIGNAGE SHALL BE INSTALLED
 INDICATING THE LOCATION OF ACCESSIBLE MEANS OF EGRESS.
  
 4) SHEET A2.0. PLEASE ALSO NOTE THIS NEXT CODE
 VIOLATION EXIST ON THE 3RD AND 4TH FLOORS IF THE
 ELEVATOR AND STAIRWAY SHARE THE SAME LANDING AS THE 2ND
 FLOOR CURRENTLY DOES. IN BOTH TODAYS CODE AND THE CODE
 THIS BUILDING WAS BUILT, BUILT IN 1963, UNDER THE 1957
 SOTHERN STANDARD BUILDING CODE THERE WAS REQUIRED
 SEPARATION BETWEEN AN VERTICAL EXIT STAIRWELL AND
 ELEVATOR LANDING. IN THE 1957 STANDARD BUILDING CODE
 SECTION 701.3 STATES ELEVATORS COUNTED AS AN EXIT SHALL
 NOT BE IN THE COMMON ENCLOSING SHAFT WITH A STAIRWAY,
 (WHICH THEY DON?T THEY ARE SEPARATE SHAFTS) AND THE
 PATH OF TRAVEL FROM ONE FLIGHT TO THE NEXT SHALL NOT
 PASS DIRECTLY IN FRONT OF THE ELEVATOR DOORS, WHICH IT
 DOES.
  
 2014 FBC-B 1022.4 OPENINGS. ELEVATORS SHALL NOT OPEN
 INTO INTERIOR EXIT STAIRWAYS AND RAMPS.
 PLEASE REFER TO THE 2014 FBC-EXISTING BUILDING CODE
 SECTION 101.4.2 BUILDINGS PREVIOUSLY OCCUPIED. THE
 LEGAL OCCUPANCY OF ANY BUILDING EXISTING ON THE DATE OF
 ADOPTION OF THIS CODE SHALL BE PERMITTED TO CONTINUE
 WITHOUT CHANGE, EXCEPT AS IS SPECIFICALLY COVERED IN
 THIS CODE, THE FLORIDA FIRE PREVENTION CODE, OR AS IS
 DEEMED NECESSARY BY THE CODE OFFICIAL FOR THE GENERAL
 SAFETY AND WELFARE OF THE OCCUPANTS AND THE PUBLIC.
  
 5) SHEET A2.0 THE 2ND FLOOR ELEVATOR LANDING AND 2ND
 FLOOR STAIRWELL LANDING (SHARED) ALSO HOUSES IN THE
 VERTICAL EXIT, AN EXISTING MAINTENANCE ROOM; IS THIS
 THE ELEVATOR MACHINE ROOM? AGAIN IN TODAYS CODE AS WELL
 AS THE 1957 SSBC YOU CANNOT HAVE EITHER A MAINTENANCE
 ROOM OR ELEVATOR MACHINE ROOM WITH IN THE VERTICAL
 EXIT. UNDER THE 1957 SSBC 701.2 NO OPENINGS SHALL BE
 PERMITTED EXCEPT AS IN SECTION 703.6. IN STAIR
 ENCLOSURE WALLS OR PARTITIONS PROTECTING THE STAIR FROM
 THE INTERIOR OF THE BUILDING, NO OPENINGS EXCEPT THE
 NECESSARY DOORWAYS SHALL BE PERMITTED.
  
 2014 FBC-B 1022.4 OPENINGS. OPENINGS IN INTERIOR EXIT
 STAIRWAYS AND RAMPS OTHER THAN UNPROTECTED EXTERIOR
 OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EXIT
 ACCESS TO THE ENCLOSURE FROM NORMALLY OCCUPIED SPACES
 AND FOR EGRESS FROM THE ENCLOSURE.
 ELEVATORS SHALL NOT OPEN INTO INTERIOR EXIT STAIRWAYS
 AND RAMPS.
  
 PLEASE REFER TO THE 2014 FBC-EXISTING BUILDING CODE
 SECTION 101.4.2 BUILDINGS PREVIOUSLY OCCUPIED. THE
 LEGAL OCCUPANCY OF ANY BUILDING EXISTING ON THE DATE OF
 ADOPTION OF THIS CODE SHALL BE PERMITTED TO CONTINUE
 WITHOUT CHANGE, EXCEPT AS IS SPECIFICALLY COVERED IN
 THIS CODE, THE FLORIDA FIRE PREVENTION CODE, OR AS IS
 DEEMED NECESSARY BY THE CODE OFFICIAL FOR THE GENERAL
 SAFETY AND WELFARE OF THE OCCUPANTS AND THE PUBLIC.
  
 6) SHEET A2.0 THE DOOR SEPARATING THE VERTICAL EXIT
 STAIRWAY, ON THE 2ND FLOOR 4 STORIES, 2 HOUR FIRE
 RATED, INDICATES THEY ARE REMOVING AND REPLACING THE
 3080 TEMPERED GLASS, PLEASE PROVIDE COMPLIANCE WITH
 2014 FBC-B TABLE 716.5 OPENING PROTECTIVES.
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 7) SHEET A2.0 IN NOTE 10 INDICATES A NEW 42 INCH HIGH
 RAILING, THE PLAN DOES NOT INDICATE A GUARD RAIL AND NO
 INDICATION OF A HANDRAIL.
  
 7A) THE GUARDRAIL IS INDICTED TO START ON TOP OF THE
 FIRST RISER. PLEASE REFER TO THE 2014 FBC-B 1013.3
 HEIGHT. REQUIRED GUARDS SHALL NOT BE LESS THAN 42
 INCHES HIGH, MEASURED VERTICALLY AS FOLLOWS ;
 (1) FROM THE ADJACENT WALKING SURFACE, THE GUARDRAIL
 SHOULD CONTINUE OUT PAST THE STAIR THE WIDTH OF THE
 STAIR.
  
 7B) THERE IS NO MENTION OF A HANDRAIL, DETAIL ,ETC.?
 FBC-B 012.6 HANDRAIL EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT STAIR FLIGHT OR RAMP RUN. WHERE HANDRAILS ARE
 NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL
 EXTEND HORIZONTALLY AT LEAST 12 INCHES (305 MM) BEYOND
 THE TOP RISER AND CONTINUE TO SLOPE FOR THE DEPTH OF
 ONE TREAD BEYOND THE BOTTOM RISER. AT RAMPS WHERE
 HANDRAILS ARE NOT CONTINUOUS BETWEEN RUNS, THE
 HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE LANDING
 12 INCHES (305 MM) MINIMUM BEYOND THE TOP AND BOTTOM OF
 RAMP RUNS. THE EXTENSIONS OF HANDRAILS SHALL BE IN THE
 SAME DIRECTION OF THE STAIR FLIGHTS AT STAIRWAYS AND
 THE RAMP RUNS AT RAMPS.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-02-02 Cont ID  
Sent By jpearson Date 2018-02-02 Time 12:36 Rev Time 0.00
Received By jpearson Date 2018-02-02 Time 11:06 Sent To  
Notes
2018-02-02 12:36:35REVIEWED PER COMMENTS AND APPROVED WITH PROVISO ON
 PLAN.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-12-07 Cont ID  
Sent By jleahy Date 2017-12-07 Time 16:39 Rev Time 0.00
Received By jleahy Date 2017-12-07 Time 16:39 Sent To  
Notes
2017-12-07 16:40:09FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 SEE FIRST REVIEW FOR COMMENTS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-02 Cont ID  
Sent By jleahy Date 2017-11-02 Time 16:12 Rev Time 0.00
Received By jleahy Date 2017-11-02 Time 16:12 Sent To I
Notes
2017-11-02 16:27:45FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PANEL SCHEDULE TO GENERIC FOR CIRCUITS. (LIGHTS,
 RECEPTACLES???)
  
 PROVIDE RISER DIAGRAM SHOWING MAIN FOR PANEL AND
 LOCATION.
  
 IS THIS THE FIRST FLOOR OR SECOND FLOOR?

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-01-24 Cont ID  
Sent By pleduc Date 2018-01-24 Time   Rev Time 0.00
Received By pleduc Date 2018-01-23 Time 16:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-12-12 Cont ID  
Sent By wjolin Date 2017-12-12 Time 14:20 Rev Time 0.00
Received By wjolin Date 2017-12-12 Time 14:12 Sent To  
Notes
2017-12-12 14:20:44SEE BUILDING REVIEW COMMENTS REGARDING AN AREA OF
 REFUGE FOR AN UNSPRINKLERED BUILDING.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-10-12 Cont ID  
Sent By wjolin Date 2017-10-12 Time 10:33 Rev Time 0.00
Received By wjolin Date 2017-10-12 Time 10:21 Sent To  
Notes
2017-10-12 10:33:442701 OKEECHOBEE BOULEVARD
 PERMIT #17100342
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLANS INDICATE THE ADDRESS OF THE PROJECT IS
 OKEECHOBEE ROAD AND THE PERMIT APPLICATION INDICATES
 THE ADDRESS IS OKEECHOBEE BOULEVARD. PLEASE COORDINATE
 THE CORRECT ADDRESS.
  
 LOFT SPACE RESULTS IN A COMMON PATH OF TRAVEL WITH
 TRAVEL DISTANCES EXCEEDING THOSE LIMITS PERMITTED BY
 THE FLORIDA FIRE PREVENTION CODE. BELOW ARE THE OPTIONS
 PERMITTED BY THE FFPC:
  
 38.2.4 NUMBER OF MEANS OF EGRESS.
 38.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE
 FOLLOWING, EXCEPT AS OTHERWISE PERMITTED BY 38.2.4.2
 THROUGH 38.2.4.6:
 (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH SECTION 7.4.
 (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED
 ON EVERY STORY.
 (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE
 ACCESSIBLE FROM EVERY PART OF EVERY STORY.
 38.2.4.2 EXIT ACCESS, AS REQUIRED BY 38.2.4.1(3), SHALL
 BE PERMITTED TO INCLUDE A SINGLE EXIT ACCESS PATH FOR
 THE DISTANCES PERMITTED AS COMMON PATHS OF TRAVEL BY
 38.2.5.3.
 38.2.4.3 A SINGLE EXIT SHALL BE PERMITTED FOR A ROOM OR
 AREA WITH A TOTAL OCCUPANT LOAD OF LESS THAN 100
 PERSONS, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA
 ARE MET:
 (1) THE EXIT SHALL DISCHARGE DIRECTLY TO THE OUTSIDE AT
 THE LEVEL OF EXIT DISCHARGE FOR THE BUILDING.
 (2) THE TOTAL DISTANCE OF TRAVEL FROM ANY POINT,
 INCLUDING TRAVEL WITHIN THE EXIT, SHALL NOT EXCEED 100
 FT (30 M).
 (3) THE TOTAL DISTANCE OF TRAVEL SPECIFIED IN
 38.2.4.3(2) SHALL BE ON THE SAME STORY, OR, IF
 TRAVERSING OF STAIRS IS NECESSARY, SUCH STAIRS SHALL
 NOT EXCEED 15 FT (4570 MM) IN HEIGHT, AND BOTH OF THE
 FOLLOWING ALSO SHALL APPLY:
 (A) INTERIOR STAIRS SHALL BE PROVIDED WITH COMPLETE
 ENCLOSURES TO SEPARATE THEM FROM ANY OTHER PART OF THE
 BUILDING, WITH NO DOOR OPENINGS THEREIN.
 (B) A SINGLE OUTSIDE STAIR IN ACCORDANCE WITH 7.2.2
 SHALL BE PERMITTED TO SERVE ALL STORIES PERMITTED
 WITHIN THE 15 FT (4570 MM) VERTICAL TRAVEL LIMITATION.
  
 38.2.4.4 ANY BUSINESS OCCUPANCY THREE OR FEWER STORIES
 IN HEIGHT, AND NOT EXCEEDING AN OCCUPANT LOAD OF 30
 PEOPLE PER STORY, SHALL BE PERMITTED A SINGLE SEPARATE
 EXIT TO EACH STORY, PROVIDED THAT ALL OF THE FOLLOWING
 CRITERIA ARE MET:
 (1) THE EXIT SHALL DISCHARGE DIRECTLY TO THE OUTSIDE.
 (2) THE TOTAL TRAVEL DISTANCE TO THE OUTSIDE OF THE
 BUILDING SHALL NOT EXCEED 100 FT (30 M).
 (3) INTERIOR EXIT STAIRS SHALL BE ENCLOSED IN
 ACCORDANCE WITH 7.1.3.2, AND BOTH OF THE FOLLOWING ALSO
 SHALL APPLY:
 (A) THE STAIR SHALL SERVE AS AN EXIT FROM NO OTHER
 STORIES.
 (B) A SINGLE OUTSIDE STAIR IN ACCORDANCE WITH 7.2.2
 SHALL BE PERMITTED TO SERVICE ALL STORIES.
  
 38.2.4.5 A SINGLE MEANS OF EGRESS SHALL BE PERMITTED
 FROM A MEZZANINE WITHIN A BUSINESS OCCUPANCY, PROVIDED
 THAT THE COMMON PATH OF TRAVEL DOES NOT EXCEED 75 FT
 (23 M), OR 100 FT (30 M) IF PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH 9.7.1.1(1).
  
 38.2.4.6 A SINGLE EXIT SHALL BE PERMITTED FOR A
 SINGLE-TENANT SPACE OR BUILDING TWO OR FEWER STORIES IN
 HEIGHT, PROVIDED THAT BOTH OF THE FOLLOWING CRITERIA
 ARE MET:
 (1) THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH 9.7.1.1(1).
 (2) THE TOTAL TRAVEL TO THE OUTSIDE DOES NOT EXCEED 100
 FT (30 M).
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-02-14 Time 07:15 Rev Time 0.00
Received By lmarchan Date 2018-02-12 Time 14:25 Sent To  
Notes
2018-02-13 14:26:04ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-02-06 Cont ID  
Sent By gjohnson Date 2018-02-06 Time 10:56 Rev Time 0.00
Received By gjohnson Date 2018-01-19 Time 17:30 Sent To  
Notes
2018-01-22 17:30:54B10

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-19 Cont ID  
Sent By gjohnson Date 2017-12-19 Time 18:51 Rev Time 0.00
Received By gjohnson Date 2017-12-01 Time 13:02 Sent To  
Notes
2017-12-04 13:02:26B09

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-02 Cont ID  
Sent By jleahy Date 2017-11-02 Time 16:27 Rev Time 0.00
Received By jleahy Date 2017-10-10 Time 12:36 Sent To  
Notes
2017-10-11 12:36:56B09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status N Date 2018-02-14 Cont ID  
Sent By jwitmer Date 2018-02-14 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2018-02-14 Time 06:56 Sent To  
Notes
2018-02-14 07:01:06PLANS STAMPED BY PALM BEACH COUNTY IMPACT FEE OFFICE,
 NO FEES DUE. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2018-01-26 Cont ID  
Sent By jwitmer Date 2018-01-26 Time 07:17 Rev Time 0.00
Received By jwitmer Date 2018-01-26 Time 06:30 Sent To  
Notes
2018-01-26 07:19:23IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-12-11 Cont ID  
Sent By jwitmer Date 2017-12-11 Time 07:11 Rev Time 0.00
Received By jwitmer Date 2017-12-11 Time 06:56 Sent To  
Notes
2017-12-11 07:11:501) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-10-21 Cont ID  
Sent By jwitmer Date 2017-10-21 Time 09:57 Rev Time 0.00
Received By jwitmer Date 2017-10-21 Time 06:59 Sent To  
Notes
2017-10-21 09:57:481) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2017-12-11 Cont ID  
Sent By ccole Date 2017-12-11 Time 13:57 Rev Time 0.00
Received By ccole Date 2017-12-11 Time 13:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-10-25 Cont ID  
Sent By ccole Date 2017-10-25 Time 12:55 Rev Time 0.00
Received By ccole Date 2017-10-25 Time 12:55 Sent To  
Notes
2017-10-25 12:57:591ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17100343
 10/25/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE MECHANICAL PLANS SHOWING ALL ALTERATIONS TO
 THE EXISTING AC SYSTEMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status N Date 2018-02-06 Cont ID  
Sent By gjohnson Date 2018-02-06 Time 10:53 Rev Time 0.00
Received By gjohnson Date 2018-02-06 Time 10:53 Sent To  
Notes
2018-02-06 10:55:54NO PLUMBING INDICATED ON PLAN.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-12-19 Cont ID  
Sent By gjohnson Date 2017-12-19 Time 18:49 Rev Time 0.00
Received By gjohnson Date 2017-12-19 Time 18:49 Sent To  
Notes
2017-12-19 18:51:012ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: COMPLY WITH BUILDINGS COMMENTS
  
 PREVIOUS COMMENTS NOT COMPLIED
  
 2014 FBC-EXISTING BUILDING CODE SECTION 806.1 A
 BUILDING, FACILITY OR ELEMENT THAT IS ALTERED SHALL
 COMPLY WITH THE PROVISIONS OF THE FLORIDA BUILDING
 CODE, ACCESSIBILITY.
  
 202.4 ALTERATIONS AFFECTING PRIMARY FUNCTION AREAS AND
 SEE IN THE EVENT OF DISPROPORTIONALITY.
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY. WHEN THE COST OF ALTERATIONS
 NECESSARY TO MAKE THE PATH OF TRAVEL TO THE ALTERED
 AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO THE COST
 OF THE OVERALL ALTERATION, THE PATH OF TRAVEL SHALL BE
 MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE MADE
 ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE COSTS. IN
 CHOOSING WHICH ACCESSIBLE ELEMENTS TO PROVIDE, PRIORITY
 SHOULD BE GIVEN TO THOSE ELEMENTS THAT WILL PROVIDE THE
 GREATEST ACCESS, IN THE FOLLOWING ORDER: (I) AN
 ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (III) AT LEAST ONE ACCESSIBLE RESTROOM
 FOR EACH SEX OR A SINGLE UNISEX RESTROOM; (IV)
 ACCESSIBLE TELEPHONES; (V) ACCESSIBLE DRINKING
 FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 1. PLEASE PROVIDE A COST BREAK DOWN SHOWING HOW YOUR
 MEETING THE REQUIREMENTS OF THE ABOVE MENTIONED CODE.
 PER WPB AMEND TO FBC 107.2.1
  
 2. PLEASE PROVIDE DRAWING SHOWING THE DIMENSIONS AND
 POSITION OF THE GRAB BARS IN THE ACCESSIBLE BATHROOM.
 FBC ACC 604.5.1- 604.5.2 - 609.4
  
 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-10-25 Cont ID  
Sent By gjohnson Date 2017-10-25 Time 07:52 Rev Time 0.00
Received By gjohnson Date 2017-10-24 Time 16:43 Sent To E
Notes
2017-10-25 07:52:181ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
  
 2014 FBC-EXISTING BUILDING CODE SECTION 806.1 A
 BUILDING, FACILITY OR ELEMENT THAT IS ALTERED SHALL
 COMPLY WITH THE PROVISIONS OF THE FLORIDA BUILDING
 CODE, ACCESSIBILITY.
  
 202.4 ALTERATIONS AFFECTING PRIMARY FUNCTION AREAS AND
 SEE IN THE EVENT OF DISPROPORTIONALITY.
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY. WHEN THE COST OF ALTERATIONS
 NECESSARY TO MAKE THE PATH OF TRAVEL TO THE ALTERED
 AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO THE COST
 OF THE OVERALL ALTERATION, THE PATH OF TRAVEL SHALL BE
 MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE MADE
 ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE COSTS. IN
 CHOOSING WHICH ACCESSIBLE ELEMENTS TO PROVIDE, PRIORITY
 SHOULD BE GIVEN TO THOSE ELEMENTS THAT WILL PROVIDE THE
 GREATEST ACCESS, IN THE FOLLOWING ORDER: (I) AN
 ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (III) AT LEAST ONE ACCESSIBLE RESTROOM
 FOR EACH SEX OR A SINGLE UNISEX RESTROOM; (IV)
 ACCESSIBLE TELEPHONES; (V) ACCESSIBLE DRINKING
 FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 1. PLEASE PROVIDE A COST BREAK DOWN SHOWING HOW YOUR
 MEETING THE REQUIREMENTS OF THE ABOVE MENTIONED CODE.
 PER WPB AMEND TO FBC 107.2.1
  
 2. PLEASE PROVIDE DRAWING SHOWING THE DIMENSIONS AND
 POSITION OF THE GRAB BARS IN THE ACCESSIBLE BATHROOM.
 FBC ACC 604.5.1- 604.5.2 - 609.4
  
 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  