Plan Review Details - Permit 17100299
Plan Review Stops For Permit 17100299
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-04-09 Cont ID  
Sent By shill Date 2018-04-09 Time 17:21 Rev Time 0.00
Received By shill Date 2018-04-09 Time 08:16 Sent To  
Notes
2018-04-09 17:24:31****PROVISOS****
  
 1. PROVIDE 2 SETS OF TRUSS DRAWINGS WITH THE ENGINEER
 OF RECORD APPROVAL AT INSPECTION.
  
 2. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF
 RECORD. AFTER THAT REVIEW, SUBMIT FOR REVIEW BY THE
 BUILDING DIVISION.
  
 3. WINDOW AND DOOR OPENINGS ARE TO COMPLY WITH R703.8
 FLASHING.
 APPROVED CORROSION-RESISTANT FLASHING SHALL BE APPLIED
 SHINGLE-FASHION IN A MANNER TO PREVENT ENTRY OF WATER
 INTO THE WALL CAVITY OR PENETRATION OF WATER TO THE
 BUILDING STRUCTURAL FRAMING COMPONENTS. SELF-ADHERED
 MEMBRANES USED AS FLASHING SHALL COMPLY WITH AAMA 711.
 ALL EXTERIOR FENESTRATION PRODUCTS SHALL BE SEALED AT
 THE JUNCTURE WITH THE BUILDING WALL WITH A SEALANT
 COMPLYING WITH AAMA 800 OR ASTM C 920 CLASS 25 GRADE NS
 OR GREATER FOR PROPER JOINT EXPANSION AND CONTRACTION,
 ASTM C 1281, AAMA 812, OR OTHER APPROVED STANDARD AS
 APPROPRIATE FOR THE TYPE OF SEALANT. THE FLASHING SHALL
 EXTEND TO THE SURFACE OF THE EXTERIOR WALL FINISH.
  
 PROVIDE A DETAIL AT INSPECTION. SUBJECT TO INSPECTOR'S
 DISCRETION, A REVISION (WITH FEES) MAY BE REQUIRED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-03-12 Cont ID  
Sent By aclange Date 2018-03-12 Time 12:35 Rev Time 0.00
Received By aclange Date 2018-03-12 Time 10:39 Sent To  
Notes
2018-03-12 12:35:37****PLAN REVIEW COMMENTS****
  
 ART LANGE - BUILDING INSPECTOR
 561-805-6667 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA
 RESIDENTIAL CODE 2015 5TH EDITION
  
 SECOND REVIEW:
  
  
 1. PARTIALLY ADDRESSED, DESIGNER OF RECORD HAS NOT
 APPROVED THE TRUSS DOCUMENTS.
  
 PROVIDE 2 SETS OF TRUSS DRAWINGS WITH THE ENGINEER OF
 RECORD APPROVAL.
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS.
  
  
 2. OK ADDRESSED.
  
 IMPACT FEES
  
  
 3. PARTIALLY ADDRESSED.
  
 A. MULLION PRODUCT APPROVAL NOT PROVIDED.
 B. THE DESIGNER OF RECORD HAS NOT APPROVED THE PRODUCT
 APPROVALS.
 C. SELECT THE ASSEMBLY USED FOR THE CERTAIN TEED
 ROOFING TO BE USED. ONCE THE ASSEMBLY IS SELECTED, SEE
 THE LIMITATIONS ON PAGE 19. IF LIMITATION NUMBER 7 IS
 APPLICABLE ADDITIONAL ENHANCED UPLIFT CALCULATIONS WILL
 BE REQUIRED.
  
 PROVIDE TWO SETS OF PRODUCT APPROVALS FOR THE
 FOLLOWING:
 ROOFING PRODUCTS, DOORS, WINDOWS AND MULLIONS AND
 SHUTTERS IF APPLICABLE.
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR
 SUBMITTALS.
  
 4. OK. ADDRESSED PERMIT VALUE ADJUSTED AS SUBMITTED.
  
 PLEASE ADJUST THE PERMITTED VALUE TO INCLUDE ALL
 MATERIALS AND LABOR.
  
  
 5. NOT ADDRESSED. INCLUDE THIS ON THE TYPICAL WALL
 SECTION ON A 301.
 SHOW HOW THE WINDOW AND DOOR OPENINGS WILL COMPLY WITH
 THIS SECTION.
 R703.8 FLASHING.
 APPROVED CORROSION-RESISTANT FLASHING SHALL BE APPLIED
 SHINGLE-FASHION IN A MANNER TO PREVENT ENTRY OF WATER
 INTO THE WALL CAVITY OR PENETRATION OF WATER TO THE
 BUILDING STRUCTURAL FRAMING COMPONENTS. SELF-ADHERED
 MEMBRANES USED AS FLASHING SHALL COMPLY WITH AAMA 711.
 ALL EXTERIOR FENESTRATION PRODUCTS SHALL BE SEALED AT
 THE JUNCTURE WITH THE BUILDING WALL WITH A SEALANT
 COMPLYING WITH AAMA 800 OR ASTM C 920 CLASS 25 GRADE NS
 OR GREATER FOR PROPER JOINT EXPANSION AND CONTRACTION,
 ASTM C 1281, AAMA 812, OR OTHER APPROVED STANDARD AS
 APPROPRIATE FOR THE TYPE OF SEALANT. THE FLASHING SHALL
 EXTEND TO THE SURFACE OF THE EXTERIOR WALL FINISH.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 *********************
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
 *********************
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-26 Cont ID  
Sent By aclange Date 2017-10-26 Time 16:07 Rev Time 0.00
Received By aclange Date 2017-10-26 Time 14:17 Sent To  
Notes
2017-10-26 16:08:57****PLAN REVIEW COMMENTS****
  
 ART LANGE - BUILDING INSPECTOR
 561-805-6667 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA
 RESIDENTIAL CODE 2015 5TH EDITION
  
 1. PROVIDE 2 SETS OF TRUSS DRAWINGS WITH THE ENGINEER
 OF RECORD APPROVAL.
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS.
  
  
 2. IMPACT FEES
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
 3. PROVIDE TWO SETS OF PRODUCT APPROVALS FOR THE
 FOLLOWING:
 ROOFING PRODUCTS, DOORS, WINDOWS AND MULLIONS AND
 SHUTTERS IF APPLICABLE.
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR
 SUBMITTALS.
  
 4. PLEASE ADJUST THE PERMITTED VALUE TO INCLUDE ALL
 MATERIALS AND LABOR.
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 5. SHOW HOW THE WINDOW AND DOOR OPENINGS WILL COMPLY
 WITH THIS SECTION.
 R703.8 FLASHING.
 APPROVED CORROSION-RESISTANT FLASHING SHALL BE APPLIED
 SHINGLE-FASHION IN A MANNER TO PREVENT ENTRY OF WATER
 INTO THE WALL CAVITY OR PENETRATION OF WATER TO THE
 BUILDING STRUCTURAL FRAMING COMPONENTS. SELF-ADHERED
 MEMBRANES USED AS FLASHING SHALL COMPLY WITH AAMA 711.
 ALL EXTERIOR FENESTRATION PRODUCTS SHALL BE SEALED AT
 THE JUNCTURE WITH THE BUILDING WALL WITH A SEALANT
 COMPLYING WITH AAMA 800 OR ASTM C 920 CLASS 25 GRADE NS
 OR GREATER FOR PROPER JOINT EXPANSION AND CONTRACTION,
 ASTM C 1281, AAMA 812, OR OTHER APPROVED STANDARD AS
 APPROPRIATE FOR THE TYPE OF SEALANT. THE FLASHING SHALL
 EXTEND TO THE SURFACE OF THE EXTERIOR WALL FINISH.
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-26 Cont ID  
Sent By ppetty Date 2018-03-26 Time 13:05 Rev Time 0.00
Received By ppetty Date 2018-03-26 Time 12:57 Sent To  
Notes
2018-03-26 13:03:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 PASSED
  
 1. CORRECTED
 2. CORRECTED
 3. CORRECTED
 4. CORRECTED
 5. CORRECTED
 6. CORRECTED
 7. CORRECTED
 8. CORRECTED
 9. CORRECED
  
 SINCERELY,
  
 PHIL PETTY
 CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-06 Cont ID  
Sent By jpearson Date 2017-11-06 Time 15:50 Rev Time 0.00
Received By jpearson Date 2017-11-06 Time 15:50 Sent To  
Notes
2017-11-06 15:50:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30 FBC RE3706.1, RE3608.1, RE3609.3; FBC
 107.2.1
 2. NOTE 13 STATES THAT WIRING TO BEDROOMS SHOULD BE
 AFCI PROTECTED. THIS IS NOT THE FULL EXTENT OF THE CODE
 REQUIREMENT: "ALL 120-VOLT, SINGLE PHASE, 15 AND 20
 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN DWELLING
 UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS,
 LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS,
 CLOSETS, HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL
 HAVE AFCI PROTECTION". PROVIDE CORRECTION IN NOTES,
 PANEL SCHEDULE, AND PLAN. NEC 210.12; FBC RE3902.12
 3. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC R315.1
 4. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE ENTIRE FLOOR PLAN SHOWING ALL
 EXISTING ALARMS. IF NONE ARE EXISTING OR NOT TO CODE,
 SHOW AS NEW INSTALLATIONS. FBC R314.3, FBC 107.2.1
 5. PROVIDE ACCURATE LOAD CALCULATION. THE FIRST 10KW
 SHOULD BE FIGURED AT 100%, NOT 10%. VOLTAGE FOR SINGLE
 PHASE SERVICE TO A RESIDENCE IS 240 VOLT. PROVIDE
 CORRECTIONS. NEC 220; FBC RE 3602.2; FBC 107.2.1
 6. A GFCI PROTECTED OUTLET ON A 20 AMP CIRCUIT IS
 REQUIRED WITHIN 3 FEET OF EACH BASIN. PROVIDE
 CORRECTION. THE BATH MARKED ROOM 104 DOES NOT SHOW THIS
 REQUIRED RECEPTACLE. PROVIDE CORRECTION. NEC
 210.11(C)(3), 210.52(D); FBC RE 3703.4, 3901.6
 7. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
 8. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC CE R404.1
 9. KITCHEN COUNTER RECEPTACLE OUTLETS REQUIRE A MINIMUM
 OF TWO SMALL APPLIANCE CIRCUITS. PANEL SCHEDULE ONLY
 SHOWS ONE. PROVIDE CORRECTION. FBC RE 3703.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-09 Cont ID  
Sent By shill Date 2018-04-09 Time 18:28 Rev Time 0.00
Received By shill Date 2018-03-06 Time 11:43 Sent To  
Notes
2018-03-08 11:43:51R21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-27 Cont ID  
Sent By aclange Date 2017-11-27 Time 11:32 Rev Time 0.00
Received By aclange Date 2017-10-10 Time 14:58 Sent To  
Notes
2017-10-11 14:58:59R34

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-03-12 Cont ID  
Sent By aclange Date 2018-03-12 Time 10:54 Rev Time 0.00
Received By aclange Date 2018-03-12 Time 10:53 Sent To  
Notes
2018-03-12 10:55:15PALM BEACH COUNTY IMPACT FEE PAID
 MU 2017 30737
 NOVEMBER 8, 2017
 $236.59 RECEIPT NO 2017 1127 263

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-11-27 Cont ID  
Sent By aclange Date 2017-11-27 Time 11:31 Rev Time 0.00
Received By aclange Date 2017-11-27 Time 11:31 Sent To  
Notes
2017-11-27 11:31:53BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-04-09 Cont ID  
Sent By hmoser Date 2018-04-09 Time 10:20 Rev Time 0.00
Received By hmoser Date 2018-04-09 Time 10:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-27 Cont ID  
Sent By ccole Date 2017-11-27 Time 10:28 Rev Time 0.00
Received By ccole Date 2017-11-27 Time 10:28 Sent To  
Notes
2017-11-27 11:26:451ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL
 PERMIT #17100299
 11/27/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: THE PLAN DOES NOT CLEARLY SHOW HOW AIR
 WILL BE RETURNED TO THE AIR HANDLER IN THE ATTIC- SEE
 SECTION M1602.4.
  
 2) PROVIDE AN ATTIC HATCH FOR ACCESS TO THE AIR
 HANDLER- SECTION M1305.1.3. SHOW THE LOCATION AND
 DIMENSIONS OF THE HATCH ON THE PLAN.
  
 3) REFER TO SECTION R403.2.4 FBC-14 ENERGY
 CONSERVATION: AIR HANDLING UNITS SHALL NOT BE INSTALLED
 IN THE ATTIC WHEN A HOME IS BROUGHT INTO CODE
 COMPLIANCE BY SECTION R402. AIR-HANDLING UNITS SHALL BE
 ALLOWED IN ATTICS FOR COMPLIANCE BY SECTION R405 ONLY
 IF THE FOLLOWING CONDITIONS ARE MET:
  
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE
 UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD.
  
 4) THE AC SIZING CALCULATIONS ARE INDICATING THE FRONT
 DOOR FACING NORTH, HOWEVER THE FRONT DOOR TO THE HOUSE
 IS FACING SOUTH. PLEASE REVISE THE CALCULATIONS BASED
 ON THE CORRECT ORIENTATION.
  
 5) THE ENERGY COMPLIANCE FORM R405 APPEARS TO BE
 SHOWING DIRECTIONAL ORIENTATIIONS FOR THE WINDOWS IN
 THE COMPLIANCE DATA THAT DO NOT MATCH THE DIRECTIONAL
 ORIENTATIONS OF THE HOUSE- PLEASE REVISE.
  
 6) THE OWNER/AGENT MUST SIGN FORM R405- SECTION
 R103.1.1.2.
  
 7) SUBMIT SPEC SHEETS FOR THE COOK TOP AND RANGE HOOD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-03-27 Cont ID  
Sent By thunt Date 2018-03-27 Time 14:14 Rev Time 0.00
Received By thunt Date 2018-03-27 Time 14:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-11-02 Cont ID  
Sent By tklarge Date 2017-11-02 Time 10:14 Rev Time 0.00
Received By tklarge Date 2017-11-02 Time 06:29 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2018-04-09 Cont ID  
Sent By shill Date 2018-04-09 Time 17:24 Rev Time 0.00
Received By shill Date 2018-04-09 Time 17:24 Sent To  
Notes
2018-04-09 17:35:11PROVISO:
  
 PRODUCT APPROVAL, REVIEWED BY DESIGNER OF RECORD, IS TO
 BE SUBMITTED WITH ROOF PERMIT APPLICATION.
  
 THE PROPOSED ASSEMBLY IS TO BE PROVIDED AND, IF
 REQUIRED, ENGINEERING FOR ENHANCED FASTENING IS TO BE
 PROVIDED.
  

Review Stop Z ZONING
Rev No 1 Status P Date 2017-10-18 Cont ID  
Sent By ajones Date 2017-10-18 Time 15:00 Rev Time 0.00
Received By ajones Date 2017-10-17 Time 13:51 Sent To  
Notes
***NONE***