| 2017-10-21 06:30:30 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17100291 |
| | ADD: 515 N. FLAGLER DR. SUITE : 800 |
| | CONT: CHANDLER CONSTRUCTION |
| | TEL: 561-791-6934 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. OCT. 21/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A4.0.1 DETAIL # 10 THE KITCHEN SHOWS A |
| | MICROWAVE SITTING ON A SHELF 4 FOOT 8 INCHES ABOVE THE |
| | FINISH FLOOR. THIS IS WELL OUT OF THE REACH RANGES AND |
| | OPERABLE PARTS SEE THE 2014 FBC-ACCESSIBILITY CODE |
| | SECTIONS: |
| | 1A) 308 REACH RANGES |
| | 308.2 FORWARD REACH./ 308.2.1 UNOBSTRUCTED/ 308.2.2 |
| | OBSTRUCTED HIGH REACH. |
| | 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 |
| | OBSTRUCTED HIGH REACH. |
| | |
| | 1B) 309 OPERABLE PARTS |
| | 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE |
| | OR MORE OF THE REACH RANGES SPECIFIED IN 308. |
| | 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH |
| | ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, |
| | PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED |
| | TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS (22.2 N) |
| | MAXIMUM. |
| | |
| | 2) SHEET A4.0.1 DETAIL # 2 & 3 THE RECEPTION DESK, |
| | COUNTERTOP, FINISH ELEVATION IS GIVEN TO BE 3 FOOT 8 ? |
| | INCHES DOES NOT COMPLY WITH ACCESSIBILITY SECTION |
| | 904.3.3 FOR CHECK WRITING SURFACES COMPLYING WITH 902.3 |
| | OR 904.4 FOR ACCESSIBLE SERVICE COUNTER. |
| | |
| | 3) SHEET A1.1.1 AT DOOR # 801 SHOWS THE PROPOSED NEW |
| | CORRIDOR WALL TO BE A 1 HOUR FIRE RATED WALL AND THE |
| | NEW TENANT DOOR TO BE 45 MINUTE RATED. IT WOULD APPEAR |
| | THAT THE BUILDING STANDARD IS TO MAINTAIN THE 1 HOUR |
| | FIRE RATING WHICH IT WAS BUILT UNDER OR THE DESIGNER |
| | PREFERENCE SINCE IT IS CALLED OUT TO BE A 1 HOUR RATED |
| | WALL. SHEET A.2.0.1. DOOR SCHEDULE DOOR # 800 IS SHOWN |
| | TO BE A HERCULITE ALL GLASS DOOR WITH A WATER CURTAIN |
| | ON BOTH SIDES. PLEASE NOTE WATER CURTAINS ARE NOT |
| | ALLOWED ON DOORS, THE ONLY TIME YOU SEE THE USE OF A |
| | WATER CURTAIN IS IN SECTION 404.6 OF THE FBC-B THIS |
| | SECTION DEALS STRICTLY WITH ATRIUM SEPARATION AND THE |
| | GLAZING NEEDING TO BE A GASKETED FRAME, IN A GLASS |
| | WALL. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |