Plan Review Details - Permit 17100260
Plan Review Stops For Permit 17100260
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-01-22 Cont ID  
Sent By shill Date 2018-01-22 Time 14:19 Rev Time 0.00
Received By shill Date 2018-01-22 Time 14:08 Sent To I
Notes
2018-01-22 14:19:52****PROVISO****
 ****ISSUED AT APPLICANT'S RISK****
 ****ROLLUP DOORS NOT ACCEPTED AS "ACCESSIBLE" AT THIS
 TIME DUE TO LACK OF INFORMATION****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 REVISION REQUIRED; PROVIDE DETAILS TO SHOW COMPLIANCE
 WITH FBC A 404. ROLLUP DOORS ARE PROPOSED AS ACCESSIBLE
 DOORS; IT IS NOT CLEAR HOW THEY MEET ALL REQUIREMENTS
 OF FBC A 404.
  
 SOME INFORMATION WAS PROVIDED, BUT SPEC SHEET REFERS TO
 "ADA CODE" AND SECTIONS WHICH DO NOT CORRELATE WITH THE
 FLORIDA BUILDING CODE. THIS INFORMATION IS REQUIRED FOR
 CONSIDERATION BY THE BUILDING OFFICIAL.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-01-10 Cont ID  
Sent By shill Date 2018-01-10 Time 06:11 Rev Time 0.00
Received By shill Date 2018-01-05 Time 12:53 Sent To I
Notes
2018-01-10 06:13:29****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE 2014
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC A TABLE 225, REVISE PLAN TO NOTE ACCESSIBILITY
 REQUIREMENT.
  
 2ND REVIEW, THE SHOP DRAWINGS SUBMITTED FOR THE STORAGE
 UNITS HAVE ROLLUP DOORS. IT IS NOT CLEAR HOW COMPLIANCE
 WITH FBC A TABLE 225.3 HAS BEEN MET.
  
 PROVIDE THE TOTAL NUMBER OF UNITS, NUMBER OF ACCESSIBLE
 UNITS, AND A DETAIL FOR ACCESSIBLE UNITS.
  
 2. SEE MECHANICAL COMMENTS; ENERGY CALCS REQUIRED,
 BUILDING REVIEW REQUIRED FOR BUILDING COMPONENTS OF
 ENERGY CALCS.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-16 Cont ID  
Sent By shill Date 2017-10-16 Time 11:44 Rev Time 0.00
Received By shill Date 2017-10-16 Time 11:44 Sent To  
Notes
2017-10-16 11:45:03****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE 2014
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC A TABLE 225, REVISE PLAN TO NOTE ACCESSIBILITY
 REQUIREMENT.
  
 2. THIS PROPERTY (1016 CLARE AVE) IS A CONDOMINIUM.
 DECLARATION OF CONDOMIUM ON WWW.MYPALMBEACHCLERK.COM
 PROPERTY UNIT BOUNDARIES. REVISE PLAN TO SHOW LIMITS OF
 EACH CONDOMINIUM UNIT, FBC 107.
  
 3. PERMIT 17040927, WHICH APPEARS TO HAVE THE SAME
 SCOPE OF WORK AS EXPIRED REVISION 17021087, ASSOCIATED
 WITH EXPIRED PERMIT 14100520. THIS ADDRESS HAS SEVERAL
 OTHER EXPIRED PERMITS, PLEASE RESOLVE AT THIS TIME.
  
 4. REVISE PLAN TO INCLUDE EXISTING OCCUPANCY
 CLASSIFICATION OF THIS SPACE, FBC 107. IF THIS IS A
 CHANGE OF OCCUPANCY, REVISE PLAN TO SHOW COMPLIANCE
 WITH FBC EB CHAPTER 10.
  
 5. DUE TO A PREVIOUS CHANGE OF OCCUPANCY (12030117) AND
 COMPLIANCE WITH FBC B TABLE 503, ALL OCCUPANCIES
 REQUIRED TO BE SEPARATED PER FBC B 508.4. REVISE PLAN
 TO SHOW ALL REQUIRED FIRE RATED WALLS AND RATINGS.
  
 6. PERMIT 12030117, THIS BUILDING WAS DECLARED AS A
 TYPE IIA BUILDING. EITHER REVISE PLAN OR, IF BUILDING
 TYPE IS TO BE REDUCED TO IIIB (AS PER SHEET CS1),
 REVISE PLAN TO SHOW COMPLIANCE WITH FBC B TABLE 503.
  
 7. AS EXISTING USE NOT CLEAR, I CANNOT DETERMINE
 WHETHER OR NOT IMPACT FEE ASSESSMENT IS REQUIRED. IT IS
 POSSIBLE THAT, AFTER ALL PLAN REVIEWS HAVE BEEN PASSED,
 AN IMPACT FEE REVIEW BY PALM BEACH COUNTY WILL BE
 REQUIRED. THE PLANS ARE TO BE STAMPED AND A RECEIPT
 SHOWING THAT FEES DUE, IF APPLICABLE, WERE PAID ARE
 REQUIRED TO BE PROVIDED PRIOR TO PERMIT ISSUANCE.
  
 8. AN "ELEVATOR DOOR OPENING DETAIL" IS ON SHEET A1.
 CLARIFY LOCATION, CLARIFY NAME FBC 107.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-10-20 Cont ID  
Sent By jleahy Date 2017-10-20 Time 17:18 Rev Time 0.00
Received By jleahy Date 2017-10-20 Time 17:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-12-15 Cont ID  
Sent By pleduc Date 2017-12-15 Time   Rev Time 0.00
Received By pleduc Date 2017-12-15 Time 09:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-10-12 Cont ID  
Sent By pleduc Date 2017-10-12 Time   Rev Time 0.00
Received By pleduc Date 2017-10-11 Time 10:26 Sent To  
Notes
2017-10-12 14:16:22THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET CS 1 & A 1 - THERE APPEARS TO BE EXISTING
 CONSTRUCTION INFILL OF 5 OVERHEAD DOOR OPENINGS. PER
 NFPA 101 THERE IS A REQUIRED FIRE RATING SEPARATION OF
 STORAGE OCCUPANCIES AND ADJACENT OCCUPANCIES. THE
 ADJACENT OCCUPANCY IS NOT INDICATED TO DETERMINE WHAT
 IS REQUIRED AND WHAT THE CURRENT FATING OF THE EXISTING
 WALL IS.
  
 PLEASE INDICATE THE ADJACENT OCCUPANCY AND PROVIDE THE
 REQUIRE SEPARATION AND WHAT LISTING WAS USED FOR THOS
 OPENINGS.
  
  
  
 2) SHEET A 1 - THERE IS NO DETAIL INDICATED FOR THE
 STORAGE UNITS, THOUGH IT IS INDICATED BY OTHERS.
  
 PLEASE PROVIDE WHAT TYPE OF MATERIALS WILL BE USED TO
 CONSTRUCT THESE UNITS, WALL HEIGHTS, ROOF COVERINGS,
 DIMESIONS, ETC.
  
  
  
 3) SHEET A 1 - THE STORAGE UNITS BY OTHERS SHALL BE
 UNDER SEPARATE PLAN SUBMITTAL.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEGEMENT.
  
  
  
 4) SHEET A 1 - THERE ARE NO DIMENSIONS FOR ANY
 CORRIDOR.
  
 PLEASE PROVIDE ALL APPLICABLE DIMENSIONS ALL CORRIDORS.
  
  
  
 5) SHEET A 1 - THERE APPEARS TO BE AN END WALL ON THE
 EAST SIDE OF THE PROPOSED PROJECT. THE WALL IS NOT
 INDICATED AS EXISTING OR NEW AND IS NOT RATED. THE
 ADJACENT OCCUPANCY IS NOT INDICATED.
  
 PLEASE PROVIDE SPECIFIC DETAIL ON THIS WALL INCLUDING
 THE REQUIRED FIRE RATING, THE APPLICABLE LISTING AND
 THE ADJACENT OCCUPANCY.
  
  
  
 6) SHEET A 1 - THERE IS NO DOOR SCHEDULE. THOUGH THE
 DOORS MAY BE EXISITNG EACH ONE SHALL BE IDENTIFIED WITH
 TYPE AND AMATERIAL INCLUDING HARDWARE, CLOSERS, ETC.
  
 PLEASE PROVIDE A DETAILED DOOR SCHEDULE.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-01-22 Cont ID  
Sent By shill Date 2018-01-22 Time 14:51 Rev Time 0.00
Received By shill Date 2018-01-12 Time 14:09 Sent To  
Notes
2018-01-16 14:10:08RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-10 Cont ID  
Sent By shill Date 2018-01-10 Time 06:13 Rev Time 0.00
Received By shill Date 2017-12-13 Time 13:06 Sent To  
Notes
2017-12-14 13:07:08B19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-10-24 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-06 Time 15:34 Sent To  
Notes
2017-10-10 15:34:47B05

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-01-05 Cont ID  
Sent By shill Date 2018-01-05 Time 17:52 Rev Time 0.00
Received By shill Date 2018-01-05 Time 17:52 Sent To  
Notes
2018-01-05 17:52:33PLAN STAMPED, NO FEES DUE
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-10-16 Cont ID  
Sent By shill Date 2017-10-16 Time 10:47 Rev Time 0.00
Received By shill Date 2017-10-16 Time 10:47 Sent To  
Notes
2017-10-16 10:47:29SEE BUILDING REVIEW
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-01-17 Cont ID  
Sent By ccole Date 2018-01-17 Time 17:28 Rev Time 0.00
Received By ccole Date 2018-01-17 Time 17:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-12-27 Cont ID  
Sent By ccole Date 2017-12-27 Time 08:15 Rev Time 0.00
Received By ccole Date 2017-12-27 Time 07:25 Sent To  
Notes
2017-12-27 08:37:391ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 PERMIT #17100260
 12/27/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) 2ND REQUEST FOR AN ENERGY COMPLIANCE SUBMITTAL.
  
 2) THE AC CALCULATIONS INDICATE THE 3.5 TON SYSTEMS ARE
 OVERSIZED- SECTION C403.2.2 FBC-14 ENERGY CONSERVATION.
  
 3) M-1: INDICATE THE TYPE OF OUTDOOR AIR DUCTWORK TO BE
 INSTALLED PER SECTION 603. THE PLAN IS INDICATING AN 8"
 PIPE.
  
 4) M-1: PROVIDE AN AIR HANDLER INSTALLATION DETAIL-
 SECTION 304.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-10-24 Cont ID  
Sent By ccole Date 2017-10-24 Time 16:25 Rev Time 0.00
Received By ccole Date 2017-10-24 Time 16:24 Sent To  
Notes
2017-10-24 16:54:431ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION,
 EXISTING BUILDING CODES.
 PERMIT #17100260
 10/24/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE PROPOSED PROJECT INCLUDES ADDING NEW AC SYSTEMS TO
 DEAD STORAGE SPACE. THESE NEW SYSTEMS ARE NOT
 "CHANGE-OUTS" CONTRARY TO THE ARCHITECT'S NOTE ON SHEET
 A-1. THERE ARE NO BUILDING DEPARTMENT RECORDS OF ANY
 LEGALLY PERMITTED AC SYSTEMS IN THE SPACE. MECHANICAL
 PLANS ARE REQUIRED WITH THIS SUBMITTAL- SEE COMMENTS
 BELOW.
  
 1) THE PREVIOUSLY UNCONDITIONED STORAGE SPACE NOW BEING
 CONDITIONED SHALL BE BROUGHT INTO FULL COMPLIANCE WITH
 THE FBC-14 ENERGY CONSERVATION CODE- SEE SECTION
 C101.4.5. PLEASE PROVIDE AN ENERGY COMPLIANCE SUBMITTAL
 USING ONE OF THE METHODS LISTED UNDER SECTION C401.2.
  
 2) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEM- SECTION C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 3) INDICATE HOW FRESH AIR WILL BE PROVIDED TO THE SPACE
 USING EITHER NATURAL OR MECHANICAL VENTILATION- SEE
 SECTIONS 402 AND 403 AND PROVIDE CALCULATIONS.
  
 4) IF MECHANICAL VENTILATION IS TO BE PROVIDED, SHOW
 THE LOCATIONS OF THE O/A DUCTS AND PROVIDE DETAILS-
 TYPES AND SIZES OF DUCTS, INLET LOCATIONS AND CLEARANCE
 DISTANCES, TYPES OF SHUTOFF DAMPERS AND LOCATIONS.
  
 5) PROVIDE AC LAYOUT PLANS INCLUDING A DUCT LAYOUT AND
 EQUIPMENT SCHEDULES. SHOW THE CFMS AT EACH SUPPLY
 DIFFUSER AND RETURN GRILL.
  
 6) PROVIDE AN AIR DISTRIBUTION SCHEDULE.
  
 7) PROVIDE CONDENSATE DISPOSAL PLANS.
  
 8) PROVIDE WIND LOAD ENGINEERING FOR CONSTRUCTION OF
 THE CONDENSER PADS AND TIE DOWN OF THE CONDENSERS TO
 THE PADS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2017-10-16 Cont ID  
Sent By shill Date 2017-10-16 Time 10:46 Rev Time 0.00
Received By shill Date 2017-10-16 Time 10:46 Sent To  
Notes
2017-10-16 10:46:57PAPA VALUE $4,652,997; CUMULATIVE 5 YEAR IMPROVEMENTS
 $720,453
 NOT A SUBSTANTIAL IMPROVEMENT
  
  