| 2017-10-11 11:24:13 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A 201 - THERE IS CONFUSION AS TO WHAT THIS |
| | PROJECT CONSISTS OF IN THE DESCRIPTION OF WORK. |
| | INTERIOR WORK IS INDICATED TO AN EXISTING SPACE. |
| | |
| | IS THE PROPOSED BUILDING BEING BUILT ON VACANT LAND? |
| | |
| | IS THE PROPOSED BUILDING A WAREHOUSE AND THEN LATER |
| | CONVERTED TO A RESTAURANT? |
| | |
| | IF SO, THE OCCUPANCY SHOULD BE WAREHOUSE WHICH IS |
| | STATED; HOWEVER, SEPARATE PERMITS AND INTERIOR |
| | BUILD-OUT WOULD BE REQUIRED TO CHANGE IT FROM WAREHOUSE |
| | TO ASSEMBLY. |
| | |
| | PLEASE CORRECT THE OCCUPANCY OR THE DESCRIPTION OF WORK |
| | ACCORDINGLY OR PROVIDE INTERIOR DRAWINGS FOR THE |
| | RESTAURANT. |
| | |
| | THIS PERMIT CAN NOT BE APPROVED FOR A RESTAURANT |
| | ASSEMBLY/MERCANTILE UNLESS THE ENTIRE INTERIOR |
| | BUILD-OUT IS INDICATED. |
| | |
| | |
| | |
| | 2) SHEET A 201 - THE REAR EXIT DOES NOT APPEAR TO LEAD |
| | TO A PUBLIC WAY. THERE IS INSUFFICIENT SITE PLAN AND |
| | THE SURROUNDING AREA TO DETERMINE THE EXIT LEADS TO A |
| | PUBLIC WAY. |
| | |
| | PER NFPA 101, CHAPTER 7, MEANS OF EGRESS: |
| | |
| | 7.7 DISCHARGE FROM EXITS. |
| | 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE |
| | DIRECTLY, AT A PUBLIC WAY OR AT AN EXTERIOR EXIT |
| | DISCHARGE, UNLESS OTHERWISE PROVIDED IN 7.7.1.2 THROUGH |
| | 7.7.1.4. |
| | 7.7.1.1 YARDS, COURTS, OPEN SPACES, OR OTHER PORTIONS |
| | OF THE EXIT DISCHARGE SHALL BE OF THE REQUIRED WIDTH |
| | AND SIZE TO PROVIDE ALL OCCUPANTS WITH A SAFE ACCESS TO |
| | A PUBLIC WAY. |
| | |
| | PLEASE PROVIDE A DETAILED SITE PLAN INDICATING |
| | COMPLIANCE WITH THE CODE. |
| | |
| | |
| | |
| | 3) A DOOR SCHEDULE IS NOT INDICATED FOR AND DOOR OR |
| | DOOR HARDWARE, INCLUDING EXIT DOORS. |
| | |
| | PER NFPA 101, CHAPTER 7, MEANS OF EGRESS: |
| | |
| | 7.2 MEANS OF EGRESS COMPONENTS. |
| | 7.2.1 DOOR OPENINGS. |
| | 7.2.1.1 GENERAL. |
| | 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL |
| | CONFORM TO THE GENERAL REQUIREMENTS OF SECTION 7.1 AND |
| | TO THE SPECIAL REQUIREMENTS OF 7.2.1. |
| | 7.2.1.1.2 EVERY DOOR OPENING AND EVERY PRINCIPAL |
| | ENTRANCE THAT IS REQUIRED TO SERVE AS AN EXIT SHALL BE |
| | DESIGNED AND CONSTRUCTED SO THAT THE PATH OF EGRESS |
| | TRAVEL IS OBVIOUS AND DIRECT. WINDOWS THAT,BECAUSE OF |
| | THEIR PHYSICAL CONFIGURATION OR DESIGN AND THE |
| | MATERIALS USED IN THEIR CONSTRUCTION, HAVE THE |
| | POTENTIAL TO BE MISTAKEN FOR DOOR OPENINGS SHALL BE |
| | MADE INACCESSIBLE TO THE OCCUPANTS BY BARRIERS OR |
| | RAILINGS. |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS |
| | OCCUPIED. |
| | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| | TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER |
| | EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE |
| | LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR |
| | OPERATION FROM THE EGRESS SIDE. |
| | |
| | 7.2.1.5.5 KEY-OPERATED LOCKS. |
| | 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED |
| | TO HAVE KEYOPERATED LOCKS FROM THE EGRESS SIDE, |
| | PROVIDED THAT ALL OF THE FOLLOWINGCRITERIA ARE MET: |
| | (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 |
| | THROUGH 43 FOR THE SPECIFIC OCCUPANCY. |
| | (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS |
| | THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND |
| | THAT READS AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE |
| | DOOR LEAF: THIS DOOR TO REMAIN UNLOCKED WHEN THE |
| | BUILDING IS |
| | OCCUPIED. |
| | (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY |
| | DISTINGUISHABLE AS LOCKED. |
| | (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT |
| | INSIDE THE BUILDING WHEN IT IS LOCKED. |
| | |
| | PLEASE PROVIDE A DOOR SCHEDULE INCLUDING EXIT DOOR |
| | HARDWARE IN COMPLIANCE WITH THE CODE. |
| | |
| | |
| | 4) SHEET A 301 - LIGHTWEIGHT ROOF TRUSSES ARE |
| | INDICATED. |
| | |
| | PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR |
| | STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION. |
| | ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT |
| | RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES |
| | HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE |
| | CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A |
| | MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND |
| | 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR. |
| | THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO |
| | THE LEFT OF THE MAIN ENTRY DOOR. |
| | A. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| | MARKED WITH THE LETTER "R". |
| | B. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| | SHALL BE MARKED WITH THE LETTER "F". |
| | C. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| | |
| | PLEASE PROVIDE A NOTE INDICATING COMPLIANCE WITH THE |
| | CODE. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |