Plan Review Details - Permit 17100228
Plan Review Stops For Permit 17100228
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-11-03 Cont ID  
Sent By shill Date 2017-11-03 Time 15:41 Rev Time 0.00
Received By shill Date 2017-11-03 Time 15:41 Sent To  
Notes
2017-11-03 15:42:09OK PER CT (RESTAMP)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-10-17 Cont ID  
Sent By cthroop Date 2017-10-17 Time 09:44 Rev Time 0.00
Received By cthroop Date 2017-10-17 Time 09:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-11-03 Cont ID  
Sent By jleahy Date 2017-11-03 Time 10:10 Rev Time 0.00
Received By jleahy Date 2017-11-03 Time 10:10 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-10-16 Cont ID  
Sent By jleahy Date 2017-10-16 Time 07:13 Rev Time 0.00
Received By jleahy Date 2017-10-16 Time 07:13 Sent To B
Notes
2017-10-16 07:16:19FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PROVIDE DISCONNECT SWITCH AT SIGN LOCATION. NEC 600.6
  
 PROVIDE DEDICATED CIRCUIT AND CONTROL FOR SIGN. NEC
 600.5; FBC CE 405.2.4
  
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 405.1 SHALL
 HAVE AUTOMATIC CONTROLS TO
 TURN OFF AT DAYLIGHT OR WHEN NOT REQUIRED. CONTROLS
 SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING
 PROGRAMING DURING A LOSS OF POWER FOR A MINIMUM OF 10
 HOURS. FBC-EC 405.2.4
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-03 Cont ID  
Sent By shill Date 2017-11-03 Time 15:42 Rev Time 0.00
Received By shill Date 2017-10-25 Time 10:27 Sent To  
Notes
2017-10-27 10:28:14RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-17 Cont ID  
Sent By cthroop Date 2017-10-17 Time 09:44 Rev Time 0.00
Received By cthroop Date 2017-10-06 Time 11:29 Sent To  
Notes
2017-10-10 11:29:57ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2017-11-03 Cont ID  
Sent By LL Date 2017-11-03 Time   Rev Time 0.00
Received By llouie Date 2017-10-31 Time 11:22 Sent To E
Notes
2017-11-03 09:12:54NOTES:
  
 - MAXIMUM SIGN AREA PERMITTED = 58.60 SQ. FT.
 - SIGN AREA PROPOSED = 17.02 SQ. FT.

Review Stop Z ZONING
Rev No 1 Status F Date 2017-10-12 Cont ID  
Sent By njwira Date 2017-10-12 Time 17:46 Rev Time 0.00
Received By njwira Date 2017-10-11 Time 16:51 Sent To E
Notes
2017-10-12 17:46:3510/12/17- FAILED
  
 WHAT ARE THE DIMENSIONS OF THE SIGN?
  
  
 PLEASE CONTACT
 NATHAN WIRA- ZONING TECHNICIAN
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy