Plan Review Details - Permit 17100210
Plan Review Stops For Permit 17100210
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-07-10 Cont ID  
Sent By rgathrig Date 2018-07-10 Time 12:02 Rev Time 0.00
Received By rgathrig Date   Time   Sent To  
Notes
2018-07-10 12:02:40PROVISO FOR SOUND TRANSMISSION TEST VERIFICATION WAS
 SUBMITTED/APPROVED UNDER 17110020 (REG)

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-12-08 Cont ID  
Sent By jwitmer Date 2017-12-08 Time 17:14 Rev Time 0.00
Received By jwitmer Date 2017-12-08 Time   Sent To  
Notes
2017-12-08 16:59:312010 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17100210
 W. P. B. PERMIT: 15111020
 ADD: 1100 S. FLAGLER DR. SUITE: GUEST UNIT # 10
 CONT: SUFFOLK
 TEL: 561-827-3678
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 SUBJECT TO FAIR HOUSING!
  
 1ST REVIEW
 DATE: FRI. DEC. 08/ 2017
 ACTION: BUILDING PROVISO
  
 1) SUFFOLK CONSTRUCTION TO CONDUCT SITE TESTING FOR
 COMPLIANCE WITH THE 2010 FBC-B SECTIONS:
 FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FBC-B 2010 1207.2 AIR-BORNE SOUND.
 FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 THE SOUND TESTS WILL BE CONDUCTED ON A 10 INCH CONCRETE
 SLAB UNDER THE MAIN PERMIT (15111020) AND SUBMITTED AS
 SOON AS RESULTS ARE PRINTED AND REVIEWED BY THE
 DESIGNER OF RECORD.
  
 NOTE: SITE TESTING FOR FLOOR INSULATION WILL REQUIRE
 THE APPLICANT TO REQUEST (IN WRITING) UNDER THE 2010 W.
 P. B. ADMINISTRATIVE CODE SECTION 104.11 ALTERNATE
 MATERIALS, DESIGN AND METHODS OF CONSTRUCTION FOR THE
 SOUND UNDERLAYMENT. THE LETTER SHOULD BE MADE OUT TO
 THE BUILDING OFFICIAL ROBERT BROWN.
  
 SHEET: FINISHES. UNIT:
 FLOOR FINISHES. BLDG TYPE: TYPE I/ TYPE II FLOOR
 INSULATION (FBC-B 2010)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 10 INCH CONCRETE FLOOR ASSEMBLY AS PER PLAN OR PROVIDE
 ONSITE TESTING TO THE LISTED BELOW ASTM STANDARDS:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-01 Cont ID  
Sent By jwitmer Date 2017-11-01 Time 12:31 Rev Time 0.00
Received By jwitmer Date 2017-11-01 Time 11:52 Sent To  
Notes
2017-11-01 12:31:54W. P. B. REVISION: 17100210
 W. P. B. PERMIT: 15111020
 ADD: 1100 S. FLAGLER DR. SUITE: GUEST UNIT: 10
 CONT: SUFFOLK
 TEL: 561-691-4552 # 103
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 SUBJECT TO FAIR HOUSING!
  
 1ST REVIEW
 DATE: WED. NOV. 01/ 2017
  
 ACTION: DENIED
  
 1) PLEASE REVIEW SHEET 607.10-FP2-90-GS10 AND SHEET
 103.10-A2-90-GS10 CLOSET DIMENSION OF 2 FT. 5 5/8
 INCHES X 5 FOOT ? INCH OR 14.48 SQ. FT.
 THE 2010 FBC-B 403.3 AUTOMATIC SPRINKLER SYSTEM.
 BUILDINGS AND STRUCTURES SHALL BE EQUIPPED THROUGHOUT
 WITH AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 903.3.1.1.
  
 F] 903.3.1.1 NFPA 13 SPRINKLER SYSTEMS. WHERE THE
 PROVISIONS OF THIS CODE REQUIRE THAT A BUILDING OR
 PORTION THEREOF BE EQUIPPED THROUGHOUT WITH AN
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH THIS
 SECTION, SPRINKLERS SHALL BE INSTALLED THROUGHOUT IN
 ACCORDANCE WITH NFPA 13 EXCEPT AS PROVIDED IN SECTION
 903.3.1.1.1 CHAPTER 30, 30.3.5.3 THE STANDARD FOR THE
 INSTALLATION OF SPRINKLER SYSTEMS IN CLOSETS LESS THAN
 12 SQ. FT. IN AREA IN INDIVIDUAL DWELLING UNITS SHALL
 NOT BE REQUIRED TO BE FIRE SPRINKLERED. THIS CLOSET IS
 OVER 12 SQUARE FEET. L
  
 BUILDING PROVISO
  
 1) SUFFOLK CONSTRUCTION TO CONDUCT SITE TESTING FOR
 COMPLIANCE WITH THE 2010 FBC-B SECTIONS:
 FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FBC-B 2010 1207.2 AIR-BORNE SOUND.
 FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 THE SOUND TESTS WILL BE CONDUCTED ON A 10 INCH CONCRETE
 SLAB UNDER THE MAIN PERMIT (15111020) AND SUBMITTED AS
 SOON AS RESULTS ARE PRINTED AND REVIEWED BY THE
 DESIGNER OF RECORD.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-11-13 Cont ID  
Sent By jleahy Date 2017-11-13 Time 17:30 Rev Time 0.00
Received By jleahy Date 2017-11-13 Time 17:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-12-08 Cont ID  
Sent By pleduc Date 2017-12-08 Time   Rev Time 0.00
Received By pleduc Date 2017-12-08 Time 15:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-10-31 Cont ID  
Sent By pleduc Date 2017-10-31 Time   Rev Time 0.00
Received By pleduc Date 2017-10-31 Time 11:44 Sent To  
Notes
2017-10-31 11:53:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET 101.08 - THE CLOSET DIMENSIONS, 5' 1/2" X 2' 5
 5/8" INDICATE AN AREA GREATER THAN 12SQ/FT. SHEET
 606.08 DOES NOT SHOW A SPRINKLER HEAD PROTECTING THE
 CLOSET.
  
 PER NFPA 101, CHAPTER 30, NEW APARTMENT BUILDINGS.
  
 30.3.5.3* IN BUILDINGS SPRINKLERED IN ACCORDANCE WITH
 NFPA 13,
 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS,
 CLOSETS LESS
 THAN 12 FT2 (1.1 M2) IN AREA IN INDIVIDUAL DWELLING
 UNITS SHALL NOT
 BE REQUIRED TO BE SPRINKLERED. CLOSETS THAT CONTAIN
 EQUIPMENT SUCH
 AS WASHERS, DRYERS, FURNACES, OR WATER HEATERS SHALL BE
 SPRINKLERED,
 REGARDLESS OF SIZE.
  
 PLEASE JUSTIFY OR PROVIDE SPRINKLER COVERAGE IN THIS
 CLOSET.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-21 Cont ID  
Sent By cpuell Date 2017-12-21 Time 13:20 Rev Time 0.00
Received By cpuell Date 2017-12-06 Time 11:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-17 Cont ID  
Sent By gjohnson Date 2017-11-17 Time 11:46 Rev Time 0.00
Received By gjohnson Date 2017-10-27 Time 13:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-12-21 Cont ID  
Sent By ccole Date 2017-12-21 Time 13:07 Rev Time 0.00
Received By ccole Date 2017-12-21 Time 12:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-09 Cont ID  
Sent By ccole Date 2017-11-09 Time 09:28 Rev Time 0.00
Received By ccole Date 2017-11-09 Time 07:09 Sent To  
Notes
2017-11-09 09:34:561ST REVIEW FBC-2010 MECHANICAL
 PERMIT #17100210
 GUEST SUITE #10/REVISION 49
 11/9/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.90-GS10: NEW LINEAR DIFFUSER BY THE HP NOT
 IDENTIFIED AND SUPPLY CFMS NOT NOTED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-11-17 Cont ID  
Sent By gjohnson Date 2017-11-17 Time 11:44 Rev Time 0.00
Received By gjohnson Date 2017-11-17 Time 11:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2017-12-21 Cont ID  
Sent By cpuell Date 2017-12-21 Time 13:20 Rev Time 0.00
Received By cpuell Date 2017-12-21 Time 13:20 Sent To  
Notes
2017-12-21 13:07:35MECH DIG/SIG GOOD
 CCOLE-12-21/17
2017-11-17 11:45:47PLUMB DIG SIG OK 11/17/17 GPJ
2017-11-09 09:39:09MECH DIG/SIGS GOOD-CCOLE-11/9/17
2017-11-01 11:58:48ARCHITECTURAL SHEETS CHECKED FOR DIGITAL SIGNATURE. OK,
 JW.