Plan Review Details - Permit 17100173
Plan Review Stops For Permit 17100173
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-10-13 Cont ID  
Sent By jleahy Date 2017-10-13 Time 16:56 Rev Time 0.00
Received By jleahy Date 2017-10-13 Time 16:56 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-10-05 Cont ID  
Sent By jleahy Date 2017-10-05 Time 16:10 Rev Time 0.00
Received By jleahy Date 2017-10-05 Time 16:10 Sent To  
Notes
2017-10-05 16:11:09TO GET A PASSED ELECTRICAL COMPLY WITH FD COMMENTS
 JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-10-12 Cont ID  
Sent By pleduc Date 2017-10-12 Time   Rev Time 0.00
Received By pleduc Date 2017-10-11 Time 16:38 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-10-05 Cont ID  
Sent By pleduc Date 2017-10-05 Time   Rev Time 0.00
Received By pleduc Date 2017-10-05 Time 14:38 Sent To E
Notes
2017-10-05 14:49:40THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) IT IS INDICATED THAT CARD READERS ARE BEING
 INSTALLED AT THE TWO SECOND FLOOR EXIT STAIRWELL DOORS.
  
 THESE ARE REQUIRED EXITS AND THE CARD READERS AT THESE
 LOCATION IS A VIOLATION OF NFPA 101, CHAPTER 7, MEANS
 OF EGRESS.
  
 NO APPROVED LISTED HARDWARE COMPLIANT OR INDICATIONS
 THAT ALL 6 OF THE SUBSECTIONS ARE COMPLIANT WITH
 SECTION 7.2.1.5.6 IS PROVIDED/SUBMITTED.
  
 THESE DOORS CAN NOT BE LOCKED IN THE PATH OF EGRESS
 WITHOUT THE APPROVED LISTED HARDWARE AND ALL 6
 SUBSECTIONS ARE DOCUMENTED..
  
 PLEASE PROVIDE HARDWARE DETAIL AND ALL 6 SUBSECTIONS
 INFORMATION AT THESE LOCATIONS.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-13 Cont ID  
Sent By jleahy Date 2017-10-13 Time 16:56 Rev Time 0.00
Received By jleahy Date 2017-10-10 Time 09:38 Sent To  
Notes
2017-10-11 09:38:40RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-05 Cont ID  
Sent By jleahy Date 2017-10-05 Time 16:11 Rev Time 0.00
Received By jleahy Date 2017-10-05 Time 12:18 Sent To  
Notes
2017-10-05 12:18:40SENT TO FD JLEAHY 10/5/17