Plan Review Details - Permit 17100128
Plan Review Stops For Permit 17100128
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-05-07 Cont ID  
Sent By kconrad Date 2018-05-07 Time 09:36 Rev Time 0.00
Received By kconrad Date 2018-05-07 Time 09:36 Sent To I
Notes
2018-05-07 09:38:22THE SUBMITTED PLAN MAY NEEED TO BE REVISED DURING THE
 TCO INSPECTION AS DISCUSSED WITH THE GC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By shill Date 2018-04-28 Time 11:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-14 Cont ID  
Sent By shill/kc Date 2017-11-14 Time 06:06 Rev Time 0.00
Received By shill Date 2017-11-09 Time 12:25 Sent To  
Notes
2017-11-14 06:11:13****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FBC B CHAPTER 10:
  
 1. SEE FIRE COMMENTS; APPLICABLE FOR BUILDING REVIEW.
  
 2. APPLICANT'S NEEDS RE: PHASED TCO PLAN ARE NOT CLEAR.
 WHAT IS THE ANTICIPATED TIMING? IT APPEARS THAT THIS
 REQUEST IS PREMATURE.
  
 3. PROVIDE A LIFE SAFETY PLAN WHICH SHOWS ACCESS TO TWO
 REMOTELY LOCATED EXITS.
  
 4. FINAL TCO PHASING APPROVAL WILL BE SUBJECT TO KEN
 CONRAD'S APPROVAL. THIS WILL REQUIRE A WALK THROUGH
 PRIOR TO THAT TIME, BUT AT A POINT CLOSER TO ACTUAL TCO
 REQUEST.
  
 5. PROVIDE THE DRY-IN PLAN REQUESTED BY KEN CONRAD.
 PLEASE PROVIDE THIS ON THE JOB SITE, AND SCHEDULE AN IN
 PROGRESS, MISCELLANEOUS, OR OTHER INSPECTION AS
 APPLICABLE.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-04-25 Cont ID  
Sent By scaldero Date 2018-04-25 Time 12:04 Rev Time 0.00
Received By scaldero Date 2018-04-25 Time 11:36 Sent To  
Notes
2018-04-25 12:03:55PERMIT # 17100128
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) APPROVAL OF THIS SUBMITTAL DOES NOT CONSTITUTE
 APPROVAL OR AUTHORIZATION TO OCCUPY THE BUILDING. A
 131-FIRE FINAL INSPECTION SHALL BE SCHEDULED, VIA THE
 CITY'S PERMIT AUTOMATED SYSTEM, AND A FULL FIRE
 INSPECTION SHALL BE CONDUCTED TO ENSURE COMPLIANCE OF
 ALL APPLICABLE FIRE CODES AND/ OR AHJ REQUIREMENTS AS A
 CONDITION OF TCO.
  
 2) APPROVAL OF THE USE OF THE CORRIDOR THAT IS PART OF
 PHASE 2, AS A SECOND MEANS OF EGRESS OF PART OF PHASE
 1, WILL REQUIRE COMPLIANCE OF THAT CORRIDOR WITH ALL
 EXIT CORRIDOR REQUIREMENTS AS LISTED IN NFPA 101,
 CHAPTER 7: MEANS OF EGRESS; PRIOR TO APPROVAL OF TCO
 FOR PHASE 1.
  
 3) USE OF THE CORRIDOR THAT IS PART OF PHASE 2, AS A
 MEANS OF EGRESS, PRESENTS A CONCERN WITH ACCESSIBILITY
 TO THE VACANT UNITS THAT WILL STILL BE UNDER
 CONSTRUCTION. WHAT MEASURES WILL BE IN PLACE TO ENSURE
 THAT THESE UNITS WILL NOT BE ACCESSIBLE TO ANYONE
 UTILIZING THE CORRIDOR AS A MEANS OF EGRESS? HOW TO WE
 MAINTAIN THE UNITS CLOSED AND SECURED AT ALL TIMES, SO
 THAT ONLY CONSTRUCTION PERSONNEL ARE ACCESSING THEM?
  
 4) STAIRWAYS # 2, 3, AND 4, SHALL BE IN FULL COMPLIANCE
 OF ALL REQUIREMENTS LISTED UNDER NFPA 101, CHAPTER 7:
 MEANS OF EGRESS; PRIOR TO APPROVAL OF TCO FOR PHASE 1.
  
 5) ALL FIRE AND LIFE SAFETY SYSTEMS FOR THE BUILDING
 SHALL BE FULLY INSTALLED, FUNCTIONAL, TESTED, AND
 APPROVED, PRIOR TO OBTAINING TCO. THIS REQUIREMENT
 INCLUDES, BUT IS NOT LIMITED TO, THE FIRE ALARM SYSTEM,
 THE FIRE SPRINKLER SYSTEM, EXIT SIGNS, EMERGENCY
 LIGHTING, FIRE EXTINGUISHERS, ETC.
  
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-10-11 Cont ID  
Sent By rlindow Date 2017-10-11 Time 07:45 Rev Time 0.00
Received By wjolin Date 2017-10-11 Time 07:37 Sent To  
Notes
2017-10-11 07:45:16410 DATURA STREET
 PERMIT #17100128
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DETAILED NARRATIVE OR ANTICIPATED DATES OF PHASING
 SUBMITTED. WHAT IS THE GOAL TRYING TO BE ACCOMPLISHED
 AND HOW WILL THIS PLAN BE EXECUTED? WHO IS RESPONSIBLE
 FOR ENSURING THIS PLAN IS BEING FOLLOWED WEEKLY/DAILY?
 HOW WILL OCCUPANTS BE RESTRICTED FROM ACCESSING FUTURE
 PHASING AREAS?
  
 PLANS LACK DETAIL FOR PROPOSED PHASED OCCUPANCY. HOW
 WILL PHASING AFFECT THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS?
  
 SOME EXIT SIGNS ARE ROUTING OCCUPANTS THROUGH AREAS
 THAT WILL NOT BE AVAILABLE UNTIL FUTURE PHASES.
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-07 Cont ID  
Sent By shill Date 2018-05-07 Time 17:50 Rev Time 0.00
Received By shill Date 2018-04-24 Time 13:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-14 Cont ID  
Sent By shill Date 2017-11-14 Time 06:11 Rev Time 0.00
Received By shill Date 2017-10-10 Time 10:26 Sent To  
Notes
***NONE***