Plan Review Details - Permit 17100107
Plan Review Stops For Permit 17100107
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-12-21 Cont ID  
Sent By aclange Date 2017-12-21 Time 09:52 Rev Time 0.00
Received By aclange Date 2017-12-21 Time 09:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-24 Cont ID  
Sent By aclange Date 2017-10-24 Time 10:56 Rev Time 0.00
Received By aclange Date 2017-10-24 Time 09:40 Sent To  
Notes
2017-10-24 10:58:21****PLAN REVIEW COMMENTS****
  
 ART LANGE - BUILDING INSPECTOR
 561-805-6667 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA
 RESIDENTIAL CODE 2015 5TH EDITION
  
  
 1. SEE ZONING REVIEW. THIS PROPERTY IS ZONED SINGLE
 FAMILY LOW DENSITY (SF7). THIS ONLY ALLOWS ONE SINGLE
 FAMILY DWELLING.
  
 2. PRODUCT APPROVALS FOR ROOFING HAVE NOT BEEN
 PROVIDED. A SEPARATE ROOFING PERMIT IS REQUIRED.
  
 3. THE ENERGY CALCULATIONS SHOW R-13 INSULATION ON THE
 WALLS. THE PLANS SHOW R-13 WITH AN ADDITIONAL LAYER OF
 R4.1 FOIL INSULATION SEE PAGE A-301. PLEASE CLARIFY.
  
 4. PLEASE PROVIDE BBQ SPECIFICATIONS. I AM CHECKING TO
 SEE IF THIS CAN BE USED UNDER COMBUSTIBLE CONSTRUCTION.
  
 5. PLEASE REVIEW PRODUCT APPROVALS AND SPECIFICATIONS
 AND APPROVED AS REVIEWED.
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 6. PLEASE SHOW METHOD OF FLASHING AROUND DOOR AND
 WINDOW OPENINGS. R-703.8
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS.
  
 7. IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-12-20 Cont ID  
Sent By jpearson Date 2017-12-20 Time 16:28 Rev Time 0.00
Received By jpearson Date 2017-12-20 Time 16:28 Sent To  
Notes
2017-12-20 16:29:13APPROVED WITH PROVISO.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-10-31 Cont ID  
Sent By jpearson Date 2017-10-31 Time 13:37 Rev Time 0.00
Received By jpearson Date 2017-10-31 Time 13:37 Sent To  
Notes
2017-10-31 13:36:59CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. CIRCUIT 10 IN PANEL B SHOWS A SMALL APPLIANCE
 CIRCUIT ON A 15 AMP BREAKER. PROVIDE CORRECTION. FBC RE
 3703.2
 2. PROVIDE CORRECT LOAD CALCULATION. THERE SHOULD BE
 ONE LOAD CALCULATION FOR THE ENTIRE RESIDENCE. SEE FBC
 RESIDENTIAL TABLE 3602.2 FOR PROPER FORMAT. FBC RE 3602
 3. RISER DIAGRAM SHOWS (3) 3/0 WIRES IN A 2 INCH
 CONDUIT FROM MAIN BREAKER DISCONNECT TO PANEL A.
 IDENTIFY IS THIS WIRE IS COPPER OR ALUMINUM.
 ADDITIONALLY, THERE SHOULD BE AN EGC IN THIS CONDUIT.
 THIS RUN IS ALSO IDENTIFIED AS CIRCUIT A-17,19. REMOVE
 DISCREPANCY. FBC 107.2.1; FBC RE 3704.6
 4. RISER SHOWS THE CONDUIT FROM PANEL A TO PANEL B WITH
 (4) 1/0 CONDUCTORS IN 1.5 INCH CONDUIT. PLAN SHOWS SAME
 RUN WITH (4) 1/0 CONDUCTORS WITH A # 6 EGC. IDENTIFY
 WIRE TYPE. CORRECT DISCREPANCY. WHY (4) 1/0 WIRES, THIS
 IS NOT A 3 PHASE PANEL? ALSO, (4) 1/0 WIRES WITH A # 6
 EXCEEDS THE CAPACITY OF A 1.5 INCH CONDUIT. PROVIDE
 CORRECTION. FBC 107.2.1; FBC RE 3704.6, TABLES 3904
 5. WHY DOES THE RISER SHOW A SEPARATE GROUNDING
 ELECTRODE SYSTEM AT PANEL B? IS THIS A SEPARATE
 STRUCTURE? IF NOT, THERE SHOULD ONLY BE ONE GROUNDING
 ELECTRODE SYSTEM AT THE SERVICE. IF THIS IS A SEPARATE
 STRUCTURE, PANEL B WILL REQUIRE A MAIN BREAKER. CLARIFY
 AND/OR CORRECT. FBC RE 3607.1, 3607.3; FBC 107.2.1
 6. PANEL SCHEDULE DOES NOT SHOW THE 20 AMP CIRCUIT
 REQUIRED FOR THE BATHROOM RECEPTACLE OUTLET. PROVIDE
 CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE 3703.4
 7. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC CE R404.1
 8. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED
 LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT
 BE PERMITTED IN CLOTHES CLOSETS". PROVIDE CORRECTION.
 NEC 410.16; FBC RE4003.12
 9. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FLOOR PLAN OF ENTIRE RESIDENCE
 SHOWING ALL EXISTING ALARMS. IF NONE ARE EXISTING OR
 NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC R314.3, FBC
 107.2.1
 10. EXTERIOR OUTLET FOR IGNITOR IS REQUIRED TO BE GFCI
 PROTECTED. PROVIDE CORRECTION. FBC RE 3902.3
 11. PROVIDE LOCATION ON PLAN OF ALL MECHANICAL
 EQUIPMENT TO BE INSTALLED AND THE ELECTRICAL
 DISCONNECTS REQUIRED. FBC 107.2.1; FBC RE 4101.5
 12. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. NEC 210.63; FBC RE3901.12
 13. PANEL B IS SHOWN AS BEING FED FROM A 150 AMP PLUG
 IN BREAKER. NO MANUFACTURER THAT I KNOW OF MAKES A
 BREAKER THIS SIZE FOR PLUG IN USE. CLARIFY AND/OR
 CORRECT. FBC 107.2.1; NEC 110.3
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2018-01-08 Cont ID  
Sent By thunt Date 2018-01-08 Time 06:16 Rev Time 0.00
Received By thunt Date 2018-01-08 Time 06:16 Sent To  
Notes
2018-01-08 06:17:01ALL GAS HAS BEEN REMOVED FROM PLANS

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-10-21 Cont ID  
Sent By gjohnson Date 2017-10-21 Time 13:23 Rev Time 0.00
Received By gjohnson Date 2017-10-21 Time 13:23 Sent To  
Notes
2017-10-21 13:35:561ST REVIEW: FBC 2014 5TH EDITION
  
 GAS COMMENTS:
  
 1. GALVANIZED PIPING PIPING IS NOTE APPROVED FOR UNDER
 GROUND USE UNLESS INSTALLED IN PVC SLEEVE WITH BOTH
 ENDS ABOVE GROUND. PER FBC FG 404.11
  
 2. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 3. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-01-17 Cont ID  
Sent By aclange Date 2018-01-17 Time 10:51 Rev Time 0.00
Received By aclange Date 2018-01-12 Time 14:27 Sent To  
Notes
2018-01-16 14:27:37RESUB ROUTED TO ACLANGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-08 Cont ID  
Sent By thunt Date 2018-01-08 Time 06:18 Rev Time 0.00
Received By thunt Date 2017-12-12 Time 15:51 Sent To I
Notes
2017-12-13 15:51:23R27

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-22 Cont ID  
Sent By shill Date 2017-11-22 Time 11:33 Rev Time 0.00
Received By shill Date 2017-10-04 Time 15:16 Sent To I
Notes
2017-10-05 15:16:33R38

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-01-17 Cont ID  
Sent By aclange Date 2018-01-17 Time 10:46 Rev Time 0.00
Received By aclange Date 2018-01-17 Time 10:44 Sent To  
Notes
2018-01-17 10:46:47PALM BEACH COUNTY IMPACT FEES
  
 RECEIPT NO: 20180112 251 PAID $180.65
  
 TRACKING NO. MU 2018 001221 0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-12-21 Cont ID  
Sent By aclange Date 2017-12-21 Time 09:09 Rev Time 0.00
Received By aclange Date 2017-12-21 Time 09:09 Sent To  
Notes
2017-12-21 09:10:08IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-11-22 Cont ID  
Sent By shill Date 2017-11-22 Time 11:31 Rev Time 0.00
Received By shill Date 2017-11-22 Time 11:31 Sent To  
Notes
2017-11-22 11:32:28IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED
 CONTACT 561-233-5025 FOR MORE INFORMATION
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-01-02 Cont ID  
Sent By ccole Date 2018-01-02 Time 09:21 Rev Time 0.00
Received By ccole Date 2018-01-02 Time 09:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-22 Cont ID  
Sent By ccole Date 2017-11-22 Time 11:12 Rev Time 0.00
Received By ccole Date 2017-11-22 Time 11:02 Sent To  
Notes
2017-11-22 11:40:011ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL
 PERMIT #17100717
 11/22/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) TWO DIFFERENT SETS OF ENERGY AND AC CALCULATIONS
 HAVE BEEN SUBMITTED EACH SPECIFYING A DIFFERENT SYSTEM
 THAN WHAT IS SHOWN ON SHEET M101 WHICH IS A 3.0 TON
 MITSUBISHI SYSTEM. THE CALCULATIONS ARE INDICATING
 EITHER A 1-TON DAIKIN OR A 1-1/2 TON MITSUBISHI SYSTEM.
 PLEASE DISCARD WHICH EVER SETS OF CALCULATIONS ARE NOT
 RELEVANT AND CORRECT THE AC SCHEDULE ON THE PLAN TO
 MATCH.
  
 2) THE OWNER/AGENT SHALL SIGN THE ENERGY COMPLIANCE
 FORM R405-2014- SEE SECTION R103.1.1.2 FBC-14 ENERGY
 CONSERVATION.
  
 3) SUBMIT THE MIAMI-DADE NOA OR FLORIDA PRODUCT
 APPROVAL FOR THE CONDENSER TIE-DOWN CLIPS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-01-08 Cont ID  
Sent By thunt Date 2018-01-08 Time 06:16 Rev Time 0.00
Received By thunt Date 2018-01-08 Time 06:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-10-21 Cont ID  
Sent By gjohnson Date 2017-10-21 Time 13:17 Rev Time 0.00
Received By gjohnson Date 2017-10-21 Time 12:51 Sent To  
Notes
2017-10-21 13:22:571ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P-101 NOTE ON HOT WATER LINE DETAIL #1 SHOWS
 HOT WATER CONNECTED TO COLD WATER PLEASE CLARIFY.PER
 WPB AMEND TO FBC 107.2.1
  
 2. SHOW DISTANCE FROM WATER HEATER IF OVER 50' A
 RECIRCULATION SYSTEM WITH INSULATED PIPING WILL BE
 REQUIRED. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2017-12-22 Time   Rev Time 0.00
Received By pgreilic Date 2017-12-21 Time 15:18 Sent To  
Notes
2017-12-22 15:53:41PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2017-10-18 Time   Rev Time 0.00
Received By pgreilic Date 2017-10-17 Time 14:24 Sent To  
Notes
2017-10-18 10:40:57 
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]