Plan Review Details - Permit 17100086
Plan Review Stops For Permit 17100086
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-10-18 Cont ID  
Sent By rmcdouga Date 2017-10-18 Time 17:39 Rev Time 0.00
Received By rmcdouga Date 2017-10-18 Time 17:20 Sent To  
Notes
2017-10-18 17:39:06REPLACE TILE ON THE WALLS AND IN THE SHOWER PAN IN
 MASTER BEDROOM AND RE-TILE TUB SURROUND IN GUEST BATH.
 NO FLOOR TILE IS BEING REPLACED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-16 Cont ID  
Sent By rmcdouga Date 2017-10-16 Time 07:44 Rev Time 0.00
Received By rmcdouga Date 2017-10-16 Time 06:50 Sent To  
Notes
2017-10-16 07:44:32PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 PROVIDE THE FOLLOWING INFORMATION FOR FLOORING
 SUBMITTALS:
  
 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK.
 > DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC 107.
 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING.
 3. TYPE OF PROPOSED HARD FLOORING (TILE, LAMINATE,
 WOOD, MARBLE, ETC.).
 4. DESCRIPTION OF EXISTING SITE CONDITIONS:
 (A) THICKNESS OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW
 (EXPOSED CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL ).
 5. PROPOSED UNDERLAYMENT.
 6. TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON
 THE EXISTING SITE CONDITIONS.
 7. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S:
 E-84, E-90 & E-492.
 8. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE.
  
 FBC 603.1 FLAME SPREAD - ASTM E 84-09
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 SUBMIT TWO COPIES OF THE TEST REPORTS FOR THE SOUND
 INSULATION INCLUDING FLAME SPREAD AND SMOKE DEVELOPED
 FOR THE APPLICABLE CONSTRUCTION CONDITIONS.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-18 Cont ID  
Sent By rmcdouga Date 2017-10-18 Time 17:39 Rev Time 0.00
Received By rmcdouga Date 2017-10-17 Time 14:23 Sent To  
Notes
2017-10-18 14:23:34RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-16 Cont ID  
Sent By rmcdouga Date 2017-10-16 Time 07:44 Rev Time 0.00
Received By rmcdouga Date 2017-10-04 Time 09:22 Sent To  
Notes
2017-10-06 09:22:42ROUTED TO PLUMBING INBOX

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-10-12 Cont ID  
Sent By thunt Date 2017-10-12 Time 07:13 Rev Time 0.00
Received By thunt Date 2017-10-12 Time 07:13 Sent To B1
Notes
***NONE***