Plan Review Details - Permit 17100064
Plan Review Stops For Permit 17100064
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2017-10-05 Cont ID  
Sent By squinone Date 2017-10-05 Time   Rev Time 0.00
Received By squinone Date 2017-10-05 Time   Sent To M
Notes
2017-10-05 15:40:201. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED FROM THE FOLLOWING WEBSITE LINK:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 2. PLEASE SUBMIT THE LATEST VERSION OF THE 'AUTO-CALC
 CERTIFIED COST ESTIMATE FORM' FOR SUBMISSION TO CITY OF
 WEST PALM BEACH PUBLIC WORKS DEPARTMENT FOR ADDITIONAL
 WORK PROPOSED. THIS FORM CAN BE DOWNLOADED FROM THE
 FOLLOWING LINK:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 3. PLEASE INCLUDE THE LATEST VERSION OF THE APPLICABLE
 CITY OF WEST PALM BEACH STANDARD UTILITY DETAILS TO THE
 DETAIL SHEET/S DURING SUBMISSION OF THE FINAL
 ENGINEERING PLANS. CONTACT THE ENGINEERING SERVICES
 DEPARTMENT FOR THE LATEST REVISED DETAILS IN CAD
 FORMAT. CITY'S STANDARD DETAILS (IN PDF FILE FORMAT)
 CAN BE DOWNLOADED FROM THE FOLLOWING SITE: HTTP://WPB.O
 RG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PERMITS-
 APPLICATIONS
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-10-05 Cont ID  
Sent By wjolin Date 2017-10-05 Time 09:18 Rev Time 0.00
Received By wjolin Date 2017-10-05 Time 09:12 Sent To ENG
Notes
2017-10-05 09:23:148230 OKEECHOBEE BOULEVARD
 PERMIT #17100064
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 CONTRACTOR SHALL BE A CONTRACTOR I OR V TO DO
 UNDERGROUDN FIRE LINE WORK.
  
 CONTRACTOR TO PROVIDE EQUIPMENT CUT SHEETS INDICATING
 JOINT RESTRAINT TORQUE REQUIREMENTS TO THE FIELD
 INSPECTOR (IF APPLICABLE).
  
 WORK SHALL COMPLY WITH NFPA 24.
  
 JOINT RESTRAINT: PER NFPA 13 & 24, SECTION 10.8.1.1,
 ALL TEES, PLUGS, CAPS, BENDS, REDUCERS, VALVES, AND
 HYDRANT BRANCHES SHALL BE RESTRAINED AGAINST MOVEMENT
 BY USING THRUST BLOCKS OR RESTRAINED JOINT SYSTEMS.
  
 CORROSION RESISTANCE: PER NFPA 13 & 24, SECTION
 10.8.3.5, AFTER INSTALLATION, RODS, NUTS, BOLTS,
 WASHERS, CLAMPS, AND OTHER RESTRAINING DEVICES SHALL BE
 CLEANED AND THOROUGHLY COATED WITH A BITUMINOUS OR
 OTHER ACCEPTABLE CORROSION-RETARDING MATERIAL.
  
 ACCEPTANCE REQUIREMENTS: PER NFPA 13 & 24, SECTION
 10.10.2.1.3, UNDERGROUND PIPING, FROM THE WATER SUPPLY
 TO THE SYSTEM RISER, AND LEAD-IN CONNECTIONS TO THE
 SYSTEM RISER SHALL BE COMPLETELY FLUSHED BEFORE
 CONNECTION IS MADE TO DOWNSTREAM FIRE PROTECTION SYSTEM
 PIPING. THE MINIMUM RATE OF FLOW SHALL BE NOT LESS THAN
 THE FLOW NECESSARY TO PROVIDE A VELOCITY OF 10 FEET PER
 SECOND.
  
 FLUSHING PAPERS: PER NFPA 13 & 24, SECTION 10.10.1, THE
 INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR THE
 COMPLETING AND SIGNING THE CONTRACTOR?S MATERIAL AND
 TEST CERTIFICATE(S) SHOWN IN FIGURE 10.10.1.
  
 HYDROSTATIC TESTING: PER NFPA 13 & 24, SECTION
 10.10.2.2.1 ALL PIPING AND ATTACHED APPURTENANCES
 SUBJECTED TO SYSTEM WORKING PRESSURE SHALL BE
 HYDROSTATICALLY TESTED AT 200 PSI OR 50 PSI IN EXCESS
 OF THE SYSTEM WORKING PRESSURE, WHICHEVER IS GREATER,
 AND SHALL MAINTAIN THAT PRESSURE +/-5 PSI FOR 2 HOURS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-10-18 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-03 Time 15:49 Sent To  
Notes
2017-10-04 15:50:06ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-10-18 Cont ID  
Sent By ccole Date 2017-10-18 Time 10:10 Rev Time 0.00
Received By ccole Date 2017-10-17 Time 17:53 Sent To  
Notes
***NONE***