Plan Review Details - Permit 17100042
| Plan Review Stops For Permit 17100042 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2017-11-21 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2017-11-21 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2017-11-21 |
Time |
09:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-10-24 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2017-10-24 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2017-10-24 |
Time |
08:24 |
Sent To |
|
|
| Notes |
| 2017-10-24 08:48:20 | ****PLAN REVIEW COMMENTS**** | | | | | | ART LANGE - BUILDING INSPECTOR | | | 561-805-6667 [email protected] | | | FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA | | | RESIDENTIAL CODE 2015 5TH EDITION | | | | | | 1. PROVIDE 2 COPIES OF PRODUCT APPROVALS FOR NEW DOORS | | | AND WINDOWS. FLORIDA STATE OR LOCAL PRODUCT APPROVAL | | | REQUIRED, FAC9N-3, FBC 5TH EDITION RESIDENTIAL 301. | | | | | | 2. REVIEW PRODUCT APPROVAL PRIOR TO SUBMITTING AND | | | INCLUDE THE FOLLOWING. FBC-107.2.1 INFORMATION ON | | | CONSTRUCTION DOCUMENTS. ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | | DESIGN. | | | | | | | | | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. | | | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED | | | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS | | | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE | | | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE | | | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR | | | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN | | | THE PERMIT PACKAGE. | | | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS | | | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2017-11-29 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-11-29 |
Time |
08:05 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-11-29 |
Time |
08:05 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2017-11-16 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-11-16 |
Time |
08:00 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-11-16 |
Time |
07:11 |
Sent To |
|
|
| Notes |
| 2017-11-16 08:00:02 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL 2ND REVIEW STATUS: DENIED, SEE COMMENTS | | | BELOW. | | | | | | ALL OF THE FOLLOWING COMMENTS WERE PREVIOUS COMMENTS | | | THAT WERE NOT ADDRESSED. RESPONSE LETTER STATED THE | | | ITEMS WERE CORRECTED ON SHEET A-4, BUT THERE WERE NOT | | | ANY CORRECTIONS. PLEASE BE ADVISED THAT THIS COMMENT | | | HAS NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE | | | THIRD REVIEW, IF IT IS NECESSARY TO REJECT THE | | | SUBMITTED PLAN A THIRD TIME FOR THE SAME REASONS, AN | | | ADDITIONAL PLAN REVIEW IS REQUIRED. FLORIDA STATUTES | | | STATE: ?WITH RESPECT TO EVALUATION OF DESIGN | | | PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT FINDS | | | IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE | | | FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT | | | DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE | | | TIMES FOR FAILURE TO CORRECT A CODE VIOLATION | | | SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION, | | | INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION, | | | STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING, | | | VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS | | | SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF | | | THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO | | | CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH | | | TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED | | | FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT | | | OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS | | | REVIEW. FS 553.80(2)(B)? | | | | | | 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF | | | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, | | | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR | | | PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM | | | BONDING TERMINATION POINT. NEC 215.5, 230, 250.50, | | | 250.94, 408.30 FBC RE3706.1, RE3608.1, RE3609.3; FBC | | | 107.2.1 | | | 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | | WITH CODE. INCLUDE THE 20 AMP BRANCH CIRCUIT REQUIRED | | | FOR BATHROOM RECEPTACLE OUTLETS. NEC 210.8, 210.11, | | | 210.12, 215.5, 408.4; FBC RE3 706.2, RE 3902, RE 3703 | | | 3. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE | | | SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC | | | 410.10(D); FBC RE4003.11 | | | 4. LIGHT IN CLOSET IS SHOWN AS A RECESS LIGHT. PER | | | CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS | | | AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE | | | PERMITTED IN CLOTHES CLOSETS". PROVIDE CORRECTION. NEC | | | 410.16; FBC RE4003.12 | | | 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A | | | NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 | | | 6. PROVIDE COMPLIANCE FOR ANY NEW OR ALTERED CIRCUIT: | | | "ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH | | | CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT FAMILY | | | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, | | | DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, | | | HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI | | | PROTECTION". NEC 210.12; FBC RE3902.12 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-10-27 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-10-27 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-10-27 |
Time |
09:31 |
Sent To |
|
|
| Notes |
| 2017-10-27 09:31:17 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF | | | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, | | | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR | | | PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM | | | BONDING TERMINATION POINT. NEC 215.5, 230, 250.50, | | | 250.94, 408.30 FBC RE3706.1, RE3608.1, RE3609.3; FBC | | | 107.2.1 | | | 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | | WITH CODE. INCLUDE THE 20 AMP BRANCH CIRCUIT REQUIRED | | | FOR BATHROOM RECEPTACLE OUTLETS. NEC 210.8, 210.11, | | | 210.12, 215.5, 408.4; FBC RE3 706.2, RE 3902, RE 3703 | | | 3. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE | | | SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC | | | 410.10(D); FBC RE4003.11 | | | 4. LIGHT IN CLOSET IS SHOWN AS A RECESS LIGHT. PER | | | CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS | | | AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE | | | PERMITTED IN CLOTHES CLOSETS". PROVIDE CORRECTION. NEC | | | 410.16; FBC RE4003.12 | | | 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A | | | NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 | | | 6. PROVIDE COMPLIANCE FOR ANY NEW OR ALTERED CIRCUIT: | | | "ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH | | | CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT FAMILY | | | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, | | | DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, | | | HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI | | | PROTECTION". NEC 210.12; FBC RE3902.12 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2017-11-21 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-11-21 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-11-21 |
Time |
10:55 |
Sent To |
|
|
| Notes |
| 2017-11-21 10:56:02 | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | | THIS TIME. A GAS PERMIT IS REQUIRED FOR A CONTRACTOR TO | | | PERFORM THE RELATED WORK. PROVIDE COMPLETE PLANS THAT | | | REFLECT THE ENTIRE SCOPE OF GAS WORK TO BE DONE. WPB | | | AMEND. TO FBC SEC.107.2.1. | | | | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE | | | FBC-R, SEC. G2404.3. | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL | | | GAS SEC. 301.3. | | | | | | A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2017-10-20 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-10-20 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-10-20 |
Time |
15:27 |
Sent To |
|
|
| Notes |
| 2017-10-20 15:29:16 | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER | | | FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS | | | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB | | | AMENDMENTS TO FBC SEC. 107.2.1. | | | | | | 3. TYPE OF GAS, (LP OR NATURAL). | | | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON | | | THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37). | | | | | | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING | | | AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ? | | | USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE | | | SEC. 402.4.1. | | | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014 | | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | | PSI. | | | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | | TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE | | | SEC. 502 THRU 505. | | | | | | 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | | | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-11-29 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-11-29 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-11-27 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2017-11-28 16:01:59 | RESUB ROUTED TO JPEARSON |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-11-21 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-11-21 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-11-01 |
Time |
14:20 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-11-01 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-11-01 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-10-02 |
Time |
11:46 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2017-11-29 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-11-29 |
Time |
13:32 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-11-29 |
Time |
13:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2017-11-21 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-11-21 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-11-21 |
Time |
10:22 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-10-20 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-10-20 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-10-20 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2017-10-20 15:27:20 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PLEASE PROVIDE DETAILED SCOPE OF PLUMBING WORK. PER | | | WPB AMEND TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2017-11-15 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2017-11-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2017-11-15 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2017-10-10 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2017-10-10 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2017-10-10 |
Time |
|
Sent To |
|
|
| Notes |
| 2017-10-10 11:05:31 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) A SURVEY OF THE PROPERTY IS REQUIRED. PLEASE | | | PROVIDE. | | | | | | 2.) THE CORRECT ZONING OF THE PROPERTY IS "SF14" (NOT | | | "SF14-C3"). PLEASE ADDRESS ON SHEET A.01. | | | | | | | | | NOTES: | | | | | | * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ZONE: SF14 | | | | | | * PROPOSED WORK DOES NOT EXCEED 50% VALUE OF THE | | | STRUCTURE. | | | |
|
|
|