Plan Review Details - Permit 17100041
Plan Review Stops For Permit 17100041
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-10-25 Cont ID  
Sent By cthroop Date 2017-10-25 Time 11:25 Rev Time 0.00
Received By cthroop Date 2017-10-25 Time 11:14 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-10 Cont ID  
Sent By shill Date 2017-10-10 Time 08:47 Rev Time 0.00
Received By shill Date 2017-10-10 Time 08:47 Sent To  
Notes
2017-10-10 08:48:28****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. BREAK AREA SINK IS TO COMPLY WITH FBC A 606.3,
 PROVIDE A DETAIL.
  
 2. TWO COMPLETE SETS OF PLANS REQUIRED, FBC 107.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-10-25 Cont ID  
Sent By jpearson Date 2017-10-25 Time 13:53 Rev Time 0.00
Received By jpearson Date 2017-10-25 Time 13:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-10-05 Cont ID  
Sent By jpearson Date 2017-10-05 Time 16:18 Rev Time 0.00
Received By jpearson Date 2017-10-05 Time 16:18 Sent To  
Notes
2017-10-05 16:18:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4
 2. PROVIDE RISER DIAGRAM. NEC 215.5; FBC 107.2.1
 3. PROVIDE LOAD CALCULATION FOR PANEL, INCLUDING ALL
 LOADS TO CONFIRM PANEL SIZE IS ADEQUATE FOR ADDITIONAL
 LOAD. NEC 220
 4. SHOW ALL CIRCUITS REQUIRED ON PLAN. I DO NOT SEE ANY
 CIRCUITS INDICATED FOR TANKLESS WATER HEATER OR
 DISPOSAL. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-10-23 Cont ID  
Sent By pleduc Date 2017-10-23 Time   Rev Time 0.00
Received By pleduc Date 2017-10-23 Time 11:12 Sent To  
Notes
2017-10-23 12:03:02THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
  
 2) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
  
  
 3) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-10-05 Cont ID  
Sent By pleduc Date 2017-10-05 Time   Rev Time 0.00
Received By pleduc Date 2017-10-04 Time 11:45 Sent To  
Notes
2017-10-04 16:30:20THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
  
 2) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
  
  
 3) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-25 Cont ID  
Sent By jpearson Date 2017-10-25 Time 14:03 Rev Time 0.00
Received By jpearson Date 2017-10-18 Time 14:37 Sent To  
Notes
2017-10-19 14:38:01B01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-11 Cont ID  
Sent By shill Date 2017-10-11 Time 10:22 Rev Time 0.00
Received By shill Date 2017-10-02 Time 11:24 Sent To  
Notes
2017-10-03 11:24:35B03

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-10-23 Cont ID  
Sent By ccole Date 2017-10-23 Time 17:54 Rev Time 0.00
Received By ccole Date 2017-10-23 Time 17:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-10-11 Cont ID  
Sent By ccole Date 2017-10-11 Time 10:14 Rev Time 0.00
Received By ccole Date 2017-10-11 Time 10:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-10-21 Cont ID  
Sent By gjohnson Date 2017-10-21 Time 10:21 Rev Time 0.00
Received By gjohnson Date 2017-10-21 Time 10:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-10-06 Cont ID  
Sent By gjohnson Date 2017-10-06 Time 09:16 Rev Time 0.00
Received By gjohnson Date 2017-10-05 Time 16:27 Sent To  
Notes
2017-10-06 09:42:581ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE FIRE STOPPING DETAILS. PER WPB AMEND
 TO FBC 107.2.1
  
 2. THE BREAK ROOM SINK SHALL COMPLY WITH FBC ACC 606.3
 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  