| 2017-10-10 08:48:28 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. BREAK AREA SINK IS TO COMPLY WITH FBC A 606.3, | | | PROVIDE A DETAIL. | | | | | | 2. TWO COMPLETE SETS OF PLANS REQUIRED, FBC 107. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-10-25 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-10-25 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-10-25 |
Time |
13:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-10-05 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-10-05 |
Time |
16:18 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-10-05 |
Time |
16:18 |
Sent To |
|
|
| Notes |
| 2017-10-05 16:18:39 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4 | | | 2. PROVIDE RISER DIAGRAM. NEC 215.5; FBC 107.2.1 | | | 3. PROVIDE LOAD CALCULATION FOR PANEL, INCLUDING ALL | | | LOADS TO CONFIRM PANEL SIZE IS ADEQUATE FOR ADDITIONAL | | | LOAD. NEC 220 | | | 4. SHOW ALL CIRCUITS REQUIRED ON PLAN. I DO NOT SEE ANY | | | CIRCUITS INDICATED FOR TANKLESS WATER HEATER OR | | | DISPOSAL. FBC 107.2.1 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-10-23 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-10-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-10-23 |
Time |
11:12 |
Sent To |
|
|
| Notes |
| 2017-10-23 12:03:02 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND | | | SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY | | | CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | | | | | | | 2) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | | CONSTRUCTION PERIOD. | | | | | | | | | | | | 3) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE | | | SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP | | | DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2017-10-05 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-10-05 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-10-04 |
Time |
11:45 |
Sent To |
|
|
| Notes |
| 2017-10-04 16:30:20 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND | | | SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY | | | CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | | | | | | | 2) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | | CONSTRUCTION PERIOD. | | | | | | | | | | | | 3) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE | | | SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP | | | DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-10-25 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-10-25 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-10-18 |
Time |
14:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-10-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-10-11 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-10-02 |
Time |
11:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2017-10-23 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-10-23 |
Time |
17:54 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-10-23 |
Time |
17:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2017-10-11 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-10-11 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-10-11 |
Time |
10:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2017-10-21 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-10-21 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-10-21 |
Time |
10:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-10-06 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-10-06 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-10-05 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2017-10-06 09:42:58 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PLEASE PROVIDE FIRE STOPPING DETAILS. PER WPB AMEND | | | TO FBC 107.2.1 | | | | | | 2. THE BREAK ROOM SINK SHALL COMPLY WITH FBC ACC 606.3 | | | HEIGHT. | | | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT | | | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|