Plan Review Details - Permit 17100025
Plan Review Stops For Permit 17100025
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-11-18 Cont ID  
Sent By jwitmer Date 2017-11-18 Time 09:00 Rev Time 0.00
Received By jwitmer Date 2017-11-18 Time 08:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-06 Cont ID  
Sent By jwitmer Date 2017-10-06 Time 07:29 Rev Time  
Received By jwitmer Date 2017-10-06 Time 06:19 Sent To  
Notes
2017-10-06 07:25:242014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010025
 ADD: 1696 OKEECHOBEE BLVD. SUITE: 2B/2C
 CONT: FLORIDA GENERAL CONTRACTOR
 TEL: 561-667-7529
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. OCT. 06/2017
 ACTION: DENIED
  
 1) NEITHER LIFE SAFETY PLAN NOR THE A-1 SHEET SHOW WALL
 TAGS IDENTIFYING THE WALL TYPES. SHEET A-2 SHOWS 3 WALL
 TYPES, WALL TYPE 2 IS A ONE HOUR FIRE RATED WALL.
 WITHOUT THE WALLS BEING IDENTIFIED ON EITHER THE LIFE
 SAFETY SHEET OR A-2 THE CONTRACTOR WILL NOT KNOW WHAT
 WALL TYPE TO BUILD. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2) SHEET A-1 INDICATES A EXTERIOR DOOR SCHEDULE WITH
 ASSOCIATED PRESSURES. THERE IS NO WIND DESIGN CRITERIA
 WHERE THE PRESSURES WERE DEIGNED FROM NOR IF THE
 PRESSURES ARE IN VULT OR VASD.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 2.2. RISK CATEGORY.
  
 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 3) THE COVERSHEET DOES NOT INDICATE THE USE OF THE 2014
 EXISTING BUILDING CODE AND IF THIS IS A CHANGE OF
 OCCUPANCY (CHAPTER 10). 301.1. THE REPAIR, ALTERATION,
 CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL
 EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS
 LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED
 BY THE APPLICANT.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-01-09 Cont ID  
Sent By jpearson Date 2018-01-09 Time 11:47 Rev Time 0.00
Received By jpearson Date 2018-01-09 Time 11:47 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-12-01 Cont ID  
Sent By jpearson Date 2017-12-01 Time 16:19 Rev Time 0.00
Received By jpearson Date 2017-12-01 Time 15:26 Sent To I
Notes
2017-12-01 15:45:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 MANY PREVIOUS COMMENTS NOT ADDRESSED, OR NOT ADDRESSED
 SATISFACTORILY. THE PLAN PROVIDED IS SUBSTANTIALLY
 NON-COMPLIANT WITH NEC, THEREFORE, A COMPLETE REVIEW IS
 NOT POSSIBLE. I HAVE LISTED AS MANY ITEMS AS POSSIBLE
 FOR THIS PLAN, BUT FURTHER COMMENTS ARE LIKELY.
  
 1. NOT COMPLIED FROM FIRST REVIEW: VALUE OF WORK STATED
 ON APPLICATION APPEARS LOW. PROVIDE COPY OF SIGNED
 CONTRACT WITH SCOPE OF WORK AND VALUE STATED. FBC 109.3
 (BE ADVISED THAT ANY PROCESS MACHINERY SHOULD NOT BE
 INCLUDED IN THIS VALUE OF WORK, ONLY LABOR AND
 MATERIALS REQUIRED FOR CONSTRUCTION PURPOSES.)
 2. NOT COMPLIED FROM FIRST REVIEW: NEC STATES THAT
 THERE SHALL BE ONLY ONE SERVICE PER BUILDING WITH A
 MAXIMUM OF SIX DISCONNECTS. IT APPEARS YOUR PROPOSED
 INSTALLATION EXCEEDS THIS REQUIREMENT. PROVIDE
 CORRECTION AND/OR CLARIFICATION. NEC 230.2, 230.71; FBC
 107.2.1 MORE DETAIL IS REQUIRED OF EXISTING SERVICE AND
 PANELS TO DETERMINE COMPLIANCE WITH NEC.
 3. NOT COMPLIED FROM FIRST REVIEW: PROVIDE MORE DETAIL
 IN RISER DIAGRAM INCLUDING EXISTING SERVICE WIRE,
 GUTTER, AND CONDUIT SIZES. INCLUDE DETAIL OF GROUNDING
 ELECTRODE SYSTEM AND INTERSYSTEM BONDING TERMINATION
 POINT. NEC 215.5, 250.50, 250.94 WHY IS THERE A CABLE
 TRAY SHOWN ABOVE THE METER CANS? ANY SPLICES MUST BE IN
 AN APPROVED GUTTER/WIREWAY THAT IS RATED FOR OUTDOOR
 LOCATION. FBC 107.2.1, NEC 300.15
 4. NOT CORRECTED FROM FIRST REVIEW: WIRE SIZE SHOWN IN
 RISER DIAGRAM TO THE 400 AMP PANELS IS 2/0 COPPER. THIS
 WIRE IS NOT RATED FOR 400 AMPS. PROVIDE CORRECTION. NEC
 310.15 WIRE SIZE STATED IS STILL NOT RATED FOR 400 AMPS
 AND PLAN SHOWS ONLY ONE WIRE FROM METER DISCONNECT TO
 PANEL AND ONLY TWO WIRES FROM METER TO METER
 DISCONNECT. SIZE WIRE PER NEC.
 5. NOT COMPLIED FROM FIRST REVIEW: PROVIDE THE
 ADDITIONAL LIGHTING CONTROLS STIPULATED IN THE FBC
 ENERGY CODE. IF THIS IS A CHANGE IN OCCUPANCY, ALL
 LIGHTING WILL NEED CONTROLS. FBC CE 405.2.2, 405.2.2.2
 6. NOT COMPLIED SATISFACTORILY FROM FIRST REVIEW:
 PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30 YOU CAN NOT USE
 RESIDENTIAL DEMAND FACTORS FOR COMMERCIAL APPLICATIONS.
 NEC 220
 7. NOT COMPLIED FROM FIRST REVIEW: PROVIDE AVAILABLE
 SHORT CIRCUIT CALCULATION FOR EACH PANEL INCLUDING
 INFORMATION FROM THE POWER COMPANY STATING WHAT THE
 AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE TO
 CONFIRM THE STATED AIC RATING OF THE SERVICE EQUIPMENT
 AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9, 110.10
 8. NOT COMPLIED SATISFACTORILY FROM FIRST REVIEW:
 PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 THE NOTE SUPPLIED ONLY STATES LABEL FOR ARC FLASH
 HAZARD WARNING. PROVIDE CORRECTION.
 9. NOT COMPLIED SATISFACTORILY FROM FIRST REVIEW: PANEL
 SCHEDULES SHOW 2 PANELS NAMED PANEL A AND 2 PANELS
 NAMED PANEL B. EACH PANEL NEEDS A UNIQUE
 IDENTIFICATION. NEC 408.4, 230.2(E) EXISTING PANEL
 SCHEDULES ARE NOT SHOWN. PROVIDE PANELS SCHEDULES FOR
 ALL PANELS IN UNIT WITH A UNIQUE NAME FOR EACH.
 10. COMPLIED.
 11. NOT COMPLIED FROM FIRST REVIEW: THERE IS A BLOCK
 NOTE THAT INDICATES "CONDUIT AND METAL BOXES SHALL MEET
 THE REQUIREMENTS OF NEC 2008". THIS IS NOT THE CURRENT
 CODE. DELETE OR CORRECT. FBC PREFACE.
 12. COMPLIED.
 13. COMPLIED.
 14. NEW COMMENT: THE WIRE SIZE SPECIFIED FROM POWER
 COMPANY IS SHOWS AS 6/0 WIRE, WHICH DOES NOT EXIST.
 DESIGN MUST COMPLY WITH THE NATIONAL ELECTRICAL CODE,
 2011 EDITION.
  
 PLEASE BE ADVISED THAT SOME OF THESE COMMENT HAVE NOT
 BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 A THIRD TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN
 REVIEW WILL BE REQUIRED. FLORIDA STATUTES STATE: ?WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)?
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-10-16 Cont ID  
Sent By jpearson Date 2017-10-16 Time 10:43 Rev Time 0.00
Received By jpearson Date 2017-10-16 Time 10:43 Sent To  
Notes
2017-10-16 10:43:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE OF WORK STATED ON APPLICATION APPEARS LOW.
 PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE OF WORK AND
 VALUE STATED. FBC 109.3
 2. NEC STATES THAT THERE SHALL BE ONLY ONE SERVICE PER
 BUILDING WITH A MAXIMUM OF SIX DISCONNECTS. IT APPEARS
 YOUR PROPOSED INSTALLATION EXCEEDS THIS REQUIREMENT.
 PROVIDE CORRECTION AND/OR CLARIFICATION. NEC 230.2,
 230.71; FBC 107.2.1
 3. PROVIDE MORE DETAIL IN RISER DIAGRAM INCLUDING
 EXISTING SERVICE WIRE, GUTTER, AND CONDUIT SIZES.
 INCLUDE DETAIL OF GROUNDING ELECTRODE SYSTEM AND
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5,
 250.50, 250.94
 4. WIRE SIZE SHOWN IN RISER DIAGRAM TO THE 400 AMP
 PANELS IS 2/0 COPPER. THIS WIRE IS NOT RATED FOR 400
 AMPS. PROVIDE CORRECTION. NEC 310.15
 5. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE. IF THIS IS A CHANGE IN
 OCCUPANCY, ALL LIGHTING WILL NEED CONTROLS. FBC CE
 405.2.2, 405.2.2.2
 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 7. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 8. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 9. PANEL SCHEDULES SHOW 2 PANELS NAMED PANEL A AND 2
 PANELS NAMED PANEL B. EACH PANEL NEEDS A UNIQUE
 IDENTIFICATION. NEC 408.4, 230.2(E)
 10. NEW PANELS A AND B CALL FOR 75 AMP BREAKERS, WHICH
 IS NOT A STANDARD BREAKER RATING. PLEASE CLARIFY THIS
 IS THE SIZE THAT WILL BE USED. NEC 240.6
 11. THERE IS A BLOCK NOTE THAT INDICATES "CONDUIT AND
 METAL BOXES SHALL MEET THE REQUIREMENTS OF NEC 2008".
 THIS IS NOT THE CURRENT CODE. DELETE OR CORRECT. FBC
 PREFACE.
 12. NOTE UNDER THE PANEL SCHEDULES STATES "ALL 15 AND
 20 AMP BREAKERS TO BE AFCI BREAKERS". THERE ARE NO AFCI
 REQUIREMENTS FOR COMMERCIAL APPLICATIONS. REMOVE ANY
 NOTES ON PLAN NOT USED FOR THIS PROJECT. FBC 107.2.1;
 NEC 210.12
 13. THERE IS A LOT OF CONFLICTING INFORMATION ON THE
 POWER PLAN. SOME OF THE NEW EQUIPMENT STATES THAT IT IS
 150 AMP, BUT HAS A 75 AMP, A 50 AMP, AND A 90 AMP
 CIRCUIT FEEDING THE UNIT. THE PRINTER STATES THAT IT IS
 150 AMP, BUT HAS TWO 20 AMP CIRCUITS FEEDING IT.
 CLARIFY AND/OR CORRECT ALL CONFLICTING INFORMATION. FBC
 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-11-17 Cont ID  
Sent By pleduc Date 2017-11-17 Time   Rev Time 0.00
Received By pleduc Date 2017-11-17 Time 09:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-10-05 Cont ID  
Sent By pleduc Date 2017-10-05 Time   Rev Time 0.00
Received By pleduc Date 2017-10-04 Time 11:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-01-09 Cont ID  
Sent By jpearson Date 2018-01-09 Time 11:47 Rev Time 0.00
Received By jpearson Date 2018-01-05 Time 15:11 Sent To  
Notes
2018-01-08 15:11:42RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-01 Cont ID  
Sent By jpearson Date 2017-12-01 Time 16:19 Rev Time 0.00
Received By jpearson Date 2017-11-16 Time 12:59 Sent To  
Notes
2017-11-16 12:59:12B07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-16 Cont ID  
Sent By jpearson Date 2017-10-16 Time 10:44 Rev Time 0.00
Received By jpearson Date 2017-10-02 Time 13:29 Sent To  
Notes
2017-10-03 13:29:38B08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2017-11-18 Cont ID  
Sent By jwitmer Date 2017-11-18 Time 08:48 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-10-06 Cont ID  
Sent By jwitmer Date 2017-10-06 Time 07:29 Rev Time  
Received By jwitmer Date 2017-10-06 Time 06:19 Sent To  
Notes
2017-10-06 07:26:22IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-11-29 Cont ID  
Sent By gjohnson Date 2017-11-29 Time 12:30 Rev Time 0.00
Received By gjohnson Date 2017-11-29 Time 11:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-10-12 Cont ID  
Sent By gjohnson Date 2017-10-12 Time 13:03 Rev Time 0.00
Received By gjohnson Date 2017-10-11 Time 15:16 Sent To  
Notes
2017-10-12 13:16:201ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. COMPLY WITH BUILDINGS COMMENT #3 IF THIS A CHANGE OF
 OCCUPANCY A WATER FOUNTAIN COMPLYING WITH FBC ACC 211.2
 AND 602 IS REQUIRED ALSO A SERVICE SINK REQUIRED PER
 FBC PL TABLE 403.1
  
 2. SHT. A-1 PLEASE SHOW CLEAR FLOOR SPACE FOR WATER
 CLOSET AND LAVATORY. PER FBC ACC 604.3.1 AND 606.2
  
 3. FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET. PER FBC ACC 604.6
  
 4. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915
 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP
 OF THE GRIPPING SURFACE, PER FBC ACC 609.4
  
 5. HOT OR TEMPERED WATER IS REQUIRED AT THE LAVATORY.
 PER FBC PL 607.1
  
 6. IF A NEW BACKFLOW IS BEING INSTALLED ON THE WATER
 SERVICE A SEPARATE PERMIT IS REQUIRED IF EXISTING IT
 WILL NEED TO BE RECERTIFIED PLEASE PROVIDE NOTE ON
 PLAN. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy