Plan Review Details - Permit 17090763
Plan Review Stops For Permit 17090763
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-10-31 Cont ID  
Sent By jleahy Date 2017-10-31 Time 10:41 Rev Time 0.00
Received By jleahy Date 2017-10-31 Time 10:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-10-02 Cont ID  
Sent By jleahy Date 2017-10-02 Time 10:02 Rev Time 0.00
Received By jleahy Date 2017-10-02 Time 10:02 Sent To  
Notes
2017-10-02 10:05:25FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER SHOWS NO WIRE SIZES 215.5
  
 NO INTERSYSTEM BONDING STRIP SHOWN 250.94
  
 RISER SHOWS CONDUIT GOING INTO THE HOUSE WHAT IS IT
 FEEDING, AND WHAT SIZE OF THE WIRES?

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-02 Cont ID  
Sent By jleahy Date 2017-10-02 Time 10:06 Rev Time 0.00
Received By jleahy Date 2017-09-28 Time 09:40 Sent To  
Notes
2017-09-29 09:40:17ELEC <5K