Plan Review Details - Permit 17090754
Plan Review Stops For Permit 17090754
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-10-16 Cont ID  
Sent By cthroop Date 2017-10-16 Time 17:09 Rev Time 0.00
Received By cthroop Date 2017-10-16 Time 17:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2017-10-04 Cont ID  
Sent By jpearson Date 2017-10-04 Time 14:38 Rev Time 0.00
Received By jpearson Date 2017-10-04 Time 14:38 Sent To  
Notes
2017-10-04 14:38:33NO ELECTRICAL REVISION SUPPLIED - NOT REQUIRED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-10-20 Cont ID  
Sent By pleduc Date 2017-10-20 Time   Rev Time 0.00
Received By pleduc Date 2017-10-20 Time 13:19 Sent To P
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-10-02 Cont ID  
Sent By pleduc Date 2017-10-02 Time   Rev Time 0.00
Received By pleduc Date 2017-10-02 Time 13:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-25 Cont ID  
Sent By gjohnson Date 2017-10-25 Time 10:28 Rev Time 0.00
Received By gjohnson Date 2017-10-19 Time 10:35 Sent To  
Notes
2017-10-20 10:35:33RESUB OF REVISION ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-16 Cont ID  
Sent By cthroop Date 2017-10-16 Time 17:09 Rev Time 0.00
Received By cthroop Date 2017-09-28 Time 11:31 Sent To  
Notes
2017-09-29 11:31:13B01

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-10-25 Cont ID  
Sent By gjohnson Date 2017-10-25 Time 10:28 Rev Time 0.00
Received By gjohnson Date 2017-10-25 Time 10:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-10-05 Cont ID  
Sent By gjohnson Date 2017-10-05 Time 10:40 Rev Time 0.00
Received By gjohnson Date 2017-10-05 Time 09:44 Sent To  
Notes
2017-10-05 11:40:261ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE ACCESSIBLE BATH ROOM SHALL COMPLY WITH FLORIDA
 BUILDING CODE ACCESSIBILITY 5TH EDITION 2014
 PLEASE SHOW COMPLIANCE WITH
 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2.
 WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR
 RIGHT-HAND APPROACH.
 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS FOR
 CHILDREN?S USE COMPLYING WITH 604.9, GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION 18 INCHES (455 MM)
 MINIMUM AND 27 INCHES (685 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE
 HEIGHT OF THE LOWER GRAB BAR ON THE BACK WALL OF A
 BATHTUB SHALL COMPLY WITH 607.4.1.1 OR 607.4.2.1.
 THE DIAPER CHANGING STATION SHALL COMPLY WITH 902.1
  
 2. ALL FLOOR DRAINS REQUIRE A TRAP PRIMER. PER FBC PL
 1002.4
  
 3. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 4. PLEASE PROVIDE WATER ISOMETRIC DRAWING. PER WPB
 AMEND TO FBC 107.3.5.1.3(3)(13)
  
 5. THE COOLER FLOOR DRAIN SHALL BE INDIVIDUALLY VENTED.
 PER FBC PL 901.2.1/910.1
  
 6. THE WC SHALL CONNECT TO THE WET VENT DOWN STREAM OF
 THE LAVATORY STACK AND BE INDIVIDUALLY CONNECT TO WET
 VENT. PER FBC PL 912.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  