| 2017-10-23 12:33:06 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW |
| | COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD) FOR IMPACT FEE ASSESSMENT. |
| | BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| | THE UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 2- PLANS SUBMITTED HAVE A COPY OF THE SEAL AND |
| | SIGNATURE. ALL PLANS NEED TO HAVE THE ORIGINAL |
| | SIGNATURE OF THE ARCHITECT AS REQUIRED BY CHAPTER 481 |
| | WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. |
| | |
| | 3- IT LOOKS LIKE THE CASEMENT WINDOWS SPECIFIED FOR THE |
| | GUEST BEDROOM AND BEDROOM #2 DON'T COMPLY WITH THE |
| | EGRESS REQUIREMENTS OF SEC. R310 FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). ACCORDING TO THE PGT WINDOWS WEBSITE, |
| | THE SIZE OF WINDOWS SPECIFIED DON'T COMPLY WITH THE |
| | REQUIRED WIDTH CLEAR OPENING AND TOTAL CLEAR OPENING. |
| | REVISE AS REQUIRED TO COMPLY OR PROVIDE MANUFACTURER'S |
| | CUT SHEETS SHOWING COMPLIANCE WITH ALL THE CLEAR |
| | OPENINGS. NOTE: KEEP IN MIND THAT EGRESS NEED TO BE |
| | ACCOMPLISHED BY THE NORMAL OPERATION OF THE WINDOW |
| | WITHOUT ANY ADDITIONAL STEP OR KNOWLEDGE TO OBTAIN THE |
| | REQUIRED OPENING. |
| | |
| | 4- SPECIFY SELF CLOSING DEVICE FOR THE GARAGE DOOR |
| | LEADING TO THE INTERIOR OF THE HOUSE AS REQUIRED BY |
| | SEC. R302.5.1 FBC-RESIDENTIAL. |
| | |
| | 5- ENGINEERING CRITERIA ON THE NEW CONSTRUCTION NOTES |
| | ON SHEET A-301 SPECIFIES R2. THIS IS A SINGLE FAMILY |
| | RESIDENCE, THEREFORE THE CORRECT OCCUPANCY |
| | CLASSIFICATION IS R3. REVISE AS REQUIRED. SEC. 310.5 |
| | FBC-BUILDING, 5TH EDITION (2014). |
| | |
| | 6- SPECIFY CARBON MONOXIDE ALARMS ON THE SECOND FLOOR |
| | ON THE LOCATION REQUIRED BY SEC. R315.1 |
| | FBC-RESIDENTIAL. NOTE: ELECTRICAL PLAN FOR THE FIRST |
| | FLOOR SHOWS SMOKE AND ALARMS AND CARBON MONOXIDE ALARMS |
| | COMBO, BUT SECOND FLOOR PLAN ONLY SHOWS SMOKE ALARMS. |
| | |
| | 7- SIZE OF FOOTINGS SHOWN ON SHEET S-1 DON'T MATCH |
| | SIZES SHOWN ON THE WALL SECTIONS ON SHEET A-402. REVISE |
| | AS REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 8- SPACING OF THE ANCHORS SHOWN ON THE LEDGER TABLE ON |
| | SHEET S-2 AND S-3 DOESN'T MATCH SPACING SHOWN ON THE |
| | TWO STORY WALL SECTION SHOWN ON SHEET A-402. REVISE AS |
| | REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 9- SPECIFY ATTIC ACCESS LOCATION AND SIZE SHOWING |
| | COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL. |
| | |
| | 10- BUILDING EXPOSURE SPECIFIED ON ROOF FRAMING NOTES |
| | ON SHEETS S-2 AND S-3 DOESN'T MATCH THE EXPOSURE |
| | SPECIFIED ON THE NEW CONSTRUCTION NOTES ON SHEET A-301. |
| | REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 11- CLARIFY WHY THE DESIGN PRESSURES SHOWN ON SHEETS |
| | S-2 AND S-3 ARE BASED ON 20 S.F TRIBUTARY AREA. PROVIDE |
| | THE DESIGN PRESSURES BASED ON THE ACTUAL EFFECTIVE AREA |
| | OR USE THE LOAD ASSOCIATED WITH THE LOWER EFFECTIVE |
| | AREA. SEE NOTE "B" OF TABLE R301.2(2) FC-RESIDENTIAL. |
| | NOTE: COORDINATE DESIGN PRESSURES WITH THOSE SHOWN ON |
| | SHEET A-301. |
| | CLARIFY WHY THE DESIGN PRESSURES FOR THE DOORS ARE |
| | HIGHER THAN THE DESIGN PRESSURES FOR THE WINDOWS. |
| | TYPICALLY, THE SMALLER THE OPENING THE HIGHER THE |
| | DESIGN PRESSURES. |
| | |
| | 12- PROVIDE DETAILS AND SPECIFICATIONS FOR THE |
| | CONNECTION AT TOP AND BOTTOM OF STEEL COLUMN LOCATED BY |
| | THE GARAGE AREA AND GOING ALL THE WAY UP TO THE ROOF |
| | FRAMING. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 13- SPECIFY DOUBLE LAYER OF WATER RESISTIVE BARRIER FOR |
| | WOOD FRAMED WALL WITH STUCCO AS REQUIRED BY SEC. |
| | R703.6.3 FBC-RESIDENTIAL. |
| | |
| | 14- REVISE STUCCO THICKNESS SPECIFIED ON ALL WALL |
| | SECTIONS. NEED 7/8" MIN. THICKNESS NOT 5/8" AS REQUIRED |
| | BY TABLE R702.1(1) FBC-RESIDENTIAL. |
| | |
| | 15- ENERGY CALCULATIONS SUBMITTED: |
| | A) AREAS SHOWN ON ITEM #8 DON'T MATCH ARCHITECTURAL |
| | PLANS SHEET A-101. REVISE AS REQUIRED. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). NOTE: CHECK FIRST FLOOR AREA AND SECOND FLOOR |
| | AREA. |
| | |
| | B) FLOOR INFORMATION ON ITEM #8 IS MISSING THE |
| | INSULATION R-VALUE BETWEEN THE GARAGE AND THE A/C AREA |
| | ABOVE. REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | C) THE AREA SHOWN ON THE "SPACES" INFORMATION ON PAGE 2 |
| | OF 5 DOESN'T MATCH PLANS. COORDINATE WITH ITEM #15(A) |
| | ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | D) ROOF MATERIAL SHOWN ON PAGE 2 OF 5 DOESN'T MATCH |
| | PLANS. REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | E) THE VENT RATIO SHOWN ON PAGE 2 OF 5 IS 1/300. |
| | ARCHITECTURAL PLANS DON'T SPECIFY THIS VENT RATIO. |
| | PERSON PREPARING THE ENERGY CALCULATIONS TO PROVIDE |
| | COMPLETE DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE |
| | WITH THE 1/300 RATIO AS REQUIRED BY THE EXCEPTION OF |
| | SEC. R806.2 FBC-RESIDENTIAL. OR, SPECIFY THE TYPICAL |
| | 1/150 VENT RATIO. |
| | |
| | F) CEILING AREAS SHOWN ON PAGE 3 OF 5 DON'T MATCH |
| | PLANS. REVISE AS REQUIRED. WHERE ARE THESE AREAS TAKEN |
| | FROM?. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | G) DOORS INFORMATION SHOWN ON PAGE 3 OF 5 DOESN'T MATCH |
| | PLANS AND PRODUCT APPROVALS SUBMITTED. REVISE AS |
| | REQUIRED. THE SIZE DOESN'T MATCH PLANS AND THIS IS A |
| | DOOR WITH GLASS. DOORS WITH GLASS NEED TO BE CONSIDERED |
| | IN THE GLAZING (WINDOWS) AREA AS REQUIRED BY SEC. |
| | R405.5.3.3 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | H) WINDOWS INFORMATION SHOWN ON PAGE 3 OF 5 DOESN'T |
| | MATCH PLANS. REVISE AS REQUIRED. NOTE: REVISE THE |
| | ORIENTATION, AREA AND OVERHANG DEPTH AND SEPARATION TO |
| | MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | I) GARAGE FLOOR AREA SHOWN ON PAGE 4 OF 5 DOESN'T MATCH |
| | AREA SHOWN ON PLANS. REVISE AS REQUIRED. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | J) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | NOTE: |
| | LABEL FOR DOORS AND WINDOWS SHOWING THE U-FACTOR AND |
| | SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL |
| | BE REQUIRED WHEN THE ENERGY CALCULATIONS DON'T USE THE |
| | DEFAULT FACTOR FOR GLAZING. |
| | |
| | 16- A) SOIL TEST REPORT SUBMITTED NEEDS THE ENGINEER'S |
| | ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 |
| | FLORIDA STATUTE WHEN SUBMITTING DOCUMENTS FOR PUBLIC |
| | RECORDS. |
| | |
| | B) SOIL TEST REPORT SUBMITTED IS MISSING A PLOT PLAN |
| | SHOWING THE LOCATION OF THE SOIL INVESTIGATION AS |
| | REQUIRED BY SEC. 1803.6 FBC-BUILDING, 5TH EDITION |
| | (2014). |
| | |
| | 17- PROVIDE COMPLETE WALL SECTIONS AND SPECIFICATIONS |
| | FOR THE CONSTRUCTION OF THE CONCRETE BALCONIES AS SHOWN |
| | ON PLANS. SEC. R301.1 FBC-RESIDENTIAL. NOTE: ALSO |
| | SPECIFY FLOOR FINISH. THIS IS REQUIRED TO VERIFY |
| | COMPLIANCE OF THE UNDERLAYMENT PRODUCT APPROVAL. |
| | |
| | 18- PROVIDE COMPLETE SECTION/DETAIL AND SPECIFICATIONS |
| | FOR THE INSTALLATION OF THE DECORATIVE SHUTTERS SHOWN |
| | ON THE FRONT ELEVATION ON THE SECOND FLOOR COVERED |
| | BALCONY. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 19- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | A) ENTRY DOOR WITH SIDELITE AS SHOWN ON PLANS. NOTE: |
| | NEED PRODUCT APPROVAL FOR DOOR THAT MEETS OR EXCEEDS |
| | THE DESIGN PRESSURES CALCULATED BY THE ARCHITECT ON |
| | SHEET A-301. AND NEED TO PROVIDE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE THAT CORRESPONDS TO DRAWING #: |
| | ET0002 SUBMITTED. SUBMIT TWO COPIES. ONLY ONE WAS |
| | SUBMITTED. |
| | |
| | B) MODIFIED BITUMEN FOR BALCONIES UNDERLAYMENT. NOA |
| | 12-0703.06 SUBMITTED IS FOR WOOD DECKS. NEED PRODUCT |
| | APPROVAL FOR CONCRETE DECK THAT IS DESIGNED TO RECEIVE |
| | FINISH FLOOR AS SPECIFIED BY THE ARCHITECT OF RECORD. |
| | NOTE: CLEARLY MARK SPECIFIC ASSEMBLY TO BE INSTALLED |
| | AND PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF |
| | THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES |
| | FOR ALL DECK ZONES. |
| | |
| | C) PEEL AND STICK UNDERLAYMENT AS SPECIFIED ON |
| | PLANS/DETAILS. ROOFING UNDERLAYMENT NOA 16-1116.09 |
| | SUBMITTED: CLEARLY MARK WHICH APPROVED UNDERLAYMENT |
| | ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE |
| | WITH THE PROPOSED INSTALLATION. |
| | |
| | D) METAL ROOF AS SPECIFIED ON PLANS. |
| | |
| | E) ALUMINUM MULLIONS NOA 16-0218.03 SUBMITTED: CLEARLY |
| | IDENTIFY SIZE OF MULLIONS AND WHERE IS GOING TO BE |
| | INSTALLED. |
| | |
| | F) THERE ARE DIFFERENT NOA'S SUBMITTED FOR THE FRENCH |
| | DOORS. NOA 16-0629.16 AND NOA 16-0629.17. CLEARLY MARK |
| | WHERE EACH DOOR IS GOING TO BE INSTALLED TO VERIFY |
| | COMPLIANCE WITH THE DESIGN PRESSURES. |
| | |
| | G) OVERHEAD GARAGE DOOR. NEED PRODUCT APPROVAL FOR DOOR |
| | THAT MEETS THE DESIGN PRESSURES CALCULATED BY THE |
| | ARCHITECT ON SHEET A-301. AND, PROVIDE COPY OF FLORIDA |
| | PRODUCT APPROVAL COVER PAGE THAT CORRESPONDS TO |
| | DRAWINGS SUBMITTED. |
| | |
| | H) GARAGE SIDE DOOR. NEED PRODUCT APPROVAL FOR DOOR |
| | THAT MEETS THE DESIGN PRESSURES CALCULATED BY THE |
| | ARCHITECT ON SHEET A-301. AND, PROVIDE COPY OF FLORIDA |
| | PRODUCT APPROVAL COVER PAGE THAT CORRESPONDS TO |
| | DRAWINGS SUBMITTED. |
| | |
| | I) BAHAMA SHUTTERS AS SPECIFIED ON PLANS. AND, PROVIDE |
| | COMPLETE INSTALLATION SCHEDULE. SEE CITY SAMPLE. |
| | |
| | J) COLONIAL SHUTTERS AS SPECIFIED ON PLANS. AND, |
| | PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY |
| | SAMPLE. |
| | |
| | K) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | L) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED |
| | CONNECTOR. |
| | |
| | 20- ARCHITECT OF RECORD TO REVIEW AND APPROVE ALL |
| | PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| | AMENDMENTS. NOTE: PLEASE PLACE THE REVIEW STAMP ON THE |
| | FRONT OF THE PRODUCT APPROVAL NOT ON THE BACK. THIS IS |
| | REQUIRED FOR PROPER RECORD RETENTION PURPOSES. WHEN THE |
| | STAMPS ARE PLACED ON THE BACK OF THE PRODUCT APPROVAL, |
| | THEY DON'T GET SCANNED. SEC. 107.2.1.4 CITY AMENDMENTS. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| | FOR REFERENCE. |
| | |