Plan Review Details - Permit 17090751
Plan Review Stops For Permit 17090751
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2018-01-04 Cont ID  
Sent By skennedy Date 2018-01-04 Time 12:32 Rev Time 0.00
Received By skennedy Date 2018-01-04 Time 12:32 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2017-10-31 Cont ID  
Sent By rmcdouga Date 2017-10-31 Time 10:04 Rev Time 0.00
Received By rmcdouga Date 2017-10-31 Time 10:04 Sent To  
Notes
2017-11-06 08:21:2511/6/17 LOT A, 249 EDMOR RD
 PCN: 74-43-44-03-28-000-0010
 PCN & ADDRESS ARE PENDING WITH PAPA AND CANNOT BE
 ASSIGNED AT THIS TIME
  
  
2017-10-31 10:07:35THE PERMIT CAN NOT BE ISSUED UNTIL AN ADDRESS HAS BEEN
 ASSIGNED TO THE PROPERTY. IN ORDER TO OBTAIN AN
 ADDRESS, PLEASE CONTACT MICHEAL ORIO BY PHONE AT
 561-494-1080 OR BY EMAIL AT [email protected].

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-01-31 Cont ID  
Sent By rmcdouga Date 2018-01-31 Time 08:40 Rev Time 0.00
Received By rmcdouga Date 2018-01-31 Time 07:46 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-12-21 Cont ID  
Sent By rmcdouga Date 2017-12-21 Time 14:00 Rev Time 0.00
Received By rmcdouga Date 2017-12-19 Time 18:40 Sent To  
Notes
2017-12-21 13:59:57PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE A SITE PLAN THAT THAT SHOWS COMPLIANCE WITH
 FBC-R401.3 DRAINAGE. SURFACE DRAINAGE SHALL BE DIVERTED
 TO A STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF
 COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS SHALL BE
 GRADED TO DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 INCHES (152
 MM) WITHIN THE FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES AND, AS APPLICABLE,
 FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN FLOOD
 ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN
 ACCURATE BOUNDARY LINE SURVEY.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-01 Cont ID  
Sent By rmcdouga Date 2017-11-01 Time 14:31 Rev Time 0.00
Received By rmcdouga Date 2017-10-31 Time 10:04 Sent To  
Notes
2017-11-01 11:05:33PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON SHEET A-301 UNDER ENGINEERING CRITERIA THE
 EXPOSURE CATEGORY IS LISTED AS "D". ON SHEETS S-2 AND
 S-3 THE EXPOSURE CATEGORY IS SPECIFIED AS "C" IN THE
 CAST-CRETE UPLIFT CALCULATIONS AND THE ROOF FRAMING
 NOTES. PLEASE CHANGE AS NECESSARY SO THAT ONLY ONE
 EXPOSURE CATEGORY IS SPECIFIED. BASED ON
 FBC-R301.2.1.4, THIS STRUCTURE IS LOCATED IN EXPOSURE
 "C". THE COMPONENT AND CLADDING PRESSURES LISTED ON
 SHEET A-301 SHOULD BE REDUCED FOR EXPOSURE "C".
  
 2) SHOW COMPLIANCE WITH FBC-R807.1 ATTIC ACCESS.
 BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF CONSTRUCTION
 SHALL HAVE AN ATTIC ACCESS OPENING TO ATTIC AREAS THAT
 EXCEED 30 SQUARE FEET (2.8 M2) AND HAVE A VERTICAL
 HEIGHT OF 30 INCHES (762 MM) OR GREATER. THE VERTICAL
 HEIGHT SHALL BE MEASURED FROM THE TOP OF THE CEILING
 FRAMING MEMBERS TO THE UNDERSIDE OF THE ROOF FRAMING
 MEMBERS. THE ROUGH-FRAMED OPENING SHALL NOT BE LESS
 THAN 22 INCHES BY 30 INCHES (559 MM BY 762 MM) AND
 SHALL BE LOCATED IN A HALLWAY OR OTHER READILY
 ACCESSIBLE LOCATION.
  
 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR THE AH 160 ROOF TILE
 ADHESIVE AND THE SLIDING GLASS DOOR.
  
 4) THE PRODUCT APPROVAL FOR THE SANTAFE CLAY ROOF TILE,
 NOA NO.12-0210.01, EXPIRED ON 2/01/2016. SUBMIT TWO
 CURRENT PRODUCT APPROVALS THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD. FBC 107.3.4
  
 5)THE DESIGN PRESSURES (+36.0 PSF, -42.0 PSF) ON THE
 PRODUCT APPROVAL FOR THE 16' WIDE CLOPAY SECTIONAL
 GARAGE DOOR FL16107 DO NOT MEET THE REQUIRED GARAGE
 DOOR PRESSURES (+42.25 PSF, -59.22 PSF) THAT ARE
 SPECIFIED ON SHEET A-301. FBC-R 301.2.1
  
 6) THE PRODUCT APPROVALS SUBMITTED FOR THE ETO WOOD
 OUTSWING DOORS DO NOT HAVE A COVERSHEET WITH A FL
 NUMBER OR AN NOA NO. TO IDENTIFY IT. THE EDITIONS OF
 THE FBC LISTED ON THE DRAWINGS ARE THE 2007 AND 2010
 EDITIONS. THE PRODUCT APPROVALS ARE REQUIRED TO
 REFERENCE THE 2014 EDITION OF THE FBC. THE DESIGN
 PRESSURES (+60 PSF, -60PSF) ON THE DOCUMENTS THAT WERE
 SUBMITTED DO NOT MEET THE REQUIRED DOOR PRESSURES
 (+48.15 PSF, -59.22 PSF) THAT ARE SPECIFIED ON SHEET
 A-301. FBC-R 301.2.1
  
 7) INDICATE THE SPECIFIC DOORS THAT EACH OF THE DOOR
 PRODUCT APPROVALS ARE INTENDED FOR. YOU CAN USE THE
 DOOR NUMBERING FROM THE PLANS. FBC 107.2.1
  
 8) SPECIFY THE SIZE OF THE DOOR SIDE LIGHTS ON THE
 PLANS. ON THE PRODUCT APPROVAL FOR THE DOOR WITH SIDE
 LIGHTS, MARK THE APPROPRIATE SIZE DOOR, SIDE LIGHTS AND
 DESIGN PRESSURES FROM THE ONES THAT ARE LISTED IN THE
 TABLES. FBC-R301.2.1 & FBC 107.2.1
  
 9) MARK THE APPROPRIATE SIZE AND DESIGN PRESSURES ON
 THE PRODUCT APPROVAL ( NOA NO.16-0629.22 ) FOR THE
 FIXED CASEMENT WINDOW. IDENTIFY WHICH WINDOW THIS
 PRODUCT APPROVAL APPLIES TO. FBC 107.2.1
  
 10) SUBMIT SIGNED AND SEALED RAS117 CALCULATIONS FOR
 ENHANCED FASTENING AS REQUIRED BY LIMITATION NUMBER 7
 FOR THE TARCO MODIFIED BITUMEN ROOFING MATERIAL (NOA
 NO. 12-0703.06).
  
 11) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-12-11 Cont ID  
Sent By jpearson Date 2017-12-11 Time 15:34 Rev Time 0.00
Received By jpearson Date 2017-12-11 Time 15:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-10-26 Cont ID  
Sent By jpearson Date 2017-10-26 Time 13:56 Rev Time 0.00
Received By jpearson Date 2017-10-26 Time 13:55 Sent To  
Notes
2017-10-26 13:55:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SERVICE CONDUCTORS FROM METER CAN TO MCB PANELS IS
 SHOWN AS # 1 WIRE TO A 150 AMP MAIN BREAKER. WIRE SIZES
 FROM NEC 310.15(B)(7), OR FBC RE TABLE E3603.1, CAN
 ONLY BE USED WHEN THE SERVICE CONDUCTOR SUPPLIES 100%
 OF THE LOAD. SINCE THIS IS NOT THE CASE, PROVIDE
 CORRECTED WIRE SIZE FROM METER CAN TO PANELS. NEC
 310.15(B)(7) AND (B)(15); FBC RE TABLE E3601.3
 2. SERVICE CONDUCTORS FROM THE METER CAN TO THE MCB
 PANELS SHOULD NOT INCLUDE AN EQUIPMENT GROUNDING
 CONDUCTOR. PROVIDE CORRECTION. NEC 250.122; FBC RE 3607
 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3
 4. CLARIFICATION REQUIRED FOR THE GROUNDING ELECTRODE
 CONDUCTOR (GEC) SIZE. IF THE GEC IS ATTACHED TO THE CWP
 AS SHOWN, THEN IT IS TOO SMALL, ASSUMING THE SIZE OF
 SERVICE CONDUCTOR FROM FPL IS RATED FOR 300 AMPS. IF
 THERE IS NOT 10 FEET OF BURIED METAL CWP, THEN THE
 CURRENT SIZE IS ADEQUATE TO THE FOOTER STEEL AND GROUND
 RODS. IN THIS CASE, REMOVE THE CWP REFERENCE ON THE
 RISER DIAGRAM GROUNDING. NEC 250.52; FBC RE 3608.1
 5. SHOW LOCATION OF SERVICE AND ELECTRICAL PANELS ON
 PLAN. HOW FAR FROM THE METER CAN IS THE LOCATION OF THE
 PANELS? SERVICE ENTRANCE CONDUCTORS WITHOUT AN
 OVERCURRENT PROTECTION SHALL NOT BE PERMITTED TO BE RUN
 INSIDE THE BUILDING MORE THAN 8 FEET. EACH OF THE MAIN
 CIRCUIT BREAKERS ARE REQUIRED TO BE IN SAME LOCATION
 (GROUPED). FBC 107.2.1; NEC 230.72
 6. FOR POOL PANEL, DEMAND FACTORS CANNOT BE USED. THE
 DEMAND FACTORS ARE ONLY FOR FEEDERS RATED 100 AMPS OR
 GREATER. SIZE WIRING AND OVERCURRENT PROTECTION FOR THE
 LOAD OF THE PANEL. PROVIDE CORRECTION. NEC 220.82; FBC
 RE 3702.1
 7. BREAKER FOR POOL PUMP IS REQUIRED TO BE GFCI
 PROTECTED. NEC 680.21(C); FBC RE 4203.1.3
 8. PANEL A, CIRCUIT 1,3 SHOWS A # 6 ROMEX WIRE ON A 60
 AMP BREAKER. #6 ROMEX WIRE IS NOT RATED FOR 60 AMPS.
 PROVIDE CORRECTION. NEC 334.80; FBC RE3705.4.4
 9. WATER HEATER IS SHOWN ON ELECTRICAL PLAN, BUT THERE
 IS NO LOAD INCLUDED FOR LOAD CALCULATION OR CIRCUIT
 SHOWN FOR WATER HEATER. THERE IS ALSO NO PLUMBING PLAN
 PROVIDED TO VERIFY THE TYPE OF WATER HEATER. PROVIDE
 CORRECTION. NEC 220; FBC 107.2.1
 10. NOTE 21 OF ELECTRICAL NOTES STATES THAT RECEPTACLES
 SHALL BE TAMPER RESISTANT PER NEC 2008, 406.11. THIS IS
 NOT THE CURRENT CODE OR CORRECT CODE SECTION. PROVIDE
 CORRECTION. NEC 406.12; FBC RE4002.14
 11. PROVIDE GFCI PROTECTION FOR ALL OUTLETS IN GARAGE,
 INCLUDING GARAGE DOOR OPENER.. NEC 210.8; FBC RE3902.2
 12. MASTER AND GUEST BATH SHOW A CHANDELIER OVER THE
 TUB. NO PARTS OF CORD-CONNECTED LUMINAIRES, CHAIN-,
 CABLE-, OR CORD-SUSPENDED LUMINAIRES, LIGHTING TRACK,
 PENDANTS, OR CEILING-SUSPENDED (PADDLE) FANS SHALL BE
 LOCATED WITHIN A ZONE MEASURED 3 FEET HORIZONTALLY AND
 8 FEET VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR
 SHOWER STALL THRESHOLD. PROVIDE CORRECTION. NEC
 410.10(D); FBC RE 4003.11
 13. ALL WALK IN CLOSETS SHOW STANDARD RECESS LIGHTS
 WITH LED. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS". PROVIDE
 CORRECTION. NEC 410.16; FBC RE4003.12
 14. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR LOW VOLTAGE SYSTEMS AND POOL. FBC 105.1,
 107.2.1
 15. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC CE R404.1
 16. SECOND FLOOR PLAN, AT TOP OF STAIRS AND IN HALLWAY,
 A REGULAR SMOKE ALARM IS SHOWN. PROVIDE CARBON MONOXIDE
 ALARMS WITHIN 10 FEET OF EACH ROOM USED FOR SLEEPING
 PURPOSES. FBC R315.1
 17. SMOKE ALARMS IN SEVERAL LOCATION ARE SHOWN WITHIN 3
 FEET OF A CEILING FAN. PER THE FIRE CODE, SMOKE ALARMS
 SHALL BE AT LEAST 3 FEET FROM CEILING FANS OR
 MECHANICAL GRILLS. PROVIDE CORRECTION. NFPA 72;
 29.8.3.4, AND 6, AND 7
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-02-07 Cont ID  
Sent By cthroop Date 2018-02-07 Time 13:58 Rev Time 0.00
Received By cthroop Date 2018-02-06 Time 13:26 Sent To I
Notes
2018-02-07 13:26:45GIVEN TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-01-31 Cont ID  
Sent By rmcdouga Date 2018-01-31 Time 08:40 Rev Time 0.00
Received By rmcdouga Date 2018-01-16 Time 15:51 Sent To  
Notes
2018-01-18 15:51:57RESUB ROUTED TO AWOOTEN VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-12 Cont ID  
Sent By cpuell Date 2018-01-12 Time 14:03 Rev Time 0.00
Received By cpuell Date 2017-11-28 Time 15:27 Sent To  
Notes
2017-11-29 15:27:53R35

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-01 Cont ID  
Sent By rmcdouga Date 2017-11-01 Time 16:53 Rev Time 0.00
Received By rmcdouga Date 2017-09-28 Time 10:29 Sent To  
Notes
2017-09-29 10:29:45R17

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-02-07 Cont ID  
Sent By cthroop Date 2018-02-07 Time 13:58 Rev Time 0.00
Received By cthroop Date 2018-02-07 Time 13:57 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-10-31 Cont ID  
Sent By rmcdouga Date 2017-10-31 Time 10:08 Rev Time 0.00
Received By rmcdouga Date 2017-10-31 Time 10:08 Sent To  
Notes
2017-10-31 10:08:08BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-01-31 Cont ID  
Sent By rmcdouga Date 2018-01-31 Time 07:46 Rev Time 0.00
Received By rmcdouga Date 2018-01-31 Time 07:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-12-21 Cont ID  
Sent By rmcdouga Date 2017-12-21 Time 07:16 Rev Time 0.00
Received By rmcdouga Date 2017-12-19 Time 18:40 Sent To  
Notes
2017-12-21 07:16:53PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE TRANSFER DUCT FOR THE FIRST FLOOR MASTER SUITE
 IS UNDER SIZED. ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED IN SIZING THE TRANSFER DUCTS PER
 FBC-R - M 1602.4. (SEE TRANSFER DUCT AT MASTER SUITE ON
 PLAN SHEET M-101.)
  
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-01 Cont ID  
Sent By rmcdouga Date 2017-11-01 Time 16:53 Rev Time 0.00
Received By rmcdouga Date 2017-11-01 Time 15:04 Sent To  
Notes
2017-11-01 16:53:29PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS FOR
 THE HEATING AND COOLING EQUIPMENT AS REQUIRED BY FBC-R
 - M1401.3 SIZING. HEATING AND COOLING EQUIPMENT SHALL
 BE SIZED BASED ON BUILDING LOADS CALCULATED IN
 ACCORDANCE WITH ACCA MANUAL J OR OTHER APPROVED HEATING
 AND COOLING CALCULATION METHODOLOGIES.
  
 2) THE TRANSFER DUCT FOR THE FIRST FLOOR MASTER SUITE
 IS UNDER SIZED. ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED IN SIZING THE TRANSFER DUCTS PER
 FBC-R - M 1602.4.
  
 3) SUBMIT TWO SETS OF THE SPECIFICATIONS FOR THE
 OUTDOOR GAS COOKTOP AND THE EXHAUST HOOD THAT ARE
 LOCATED ON THE COVERED PORCH. FBC 107.2.1
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-12-22 Cont ID  
Sent By rmcdouga Date 2017-12-22 Time 15:14 Rev Time 0.00
Received By tklarge Date 2017-12-28 Time 05:50 Sent To  
Notes
2017-12-22 15:15:17APPROVED BY TIM HUNT ON 10/11/17. RM

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-10-13 Cont ID  
Sent By lcrespo Date 2017-10-13 Time 12:05 Rev Time 0.00
Received By lcrespo Date 2017-10-13 Time 12:05 Sent To  
Notes
2017-10-13 12:05:0310/13/17 APPROVED LAC

Review Stop Z ZONING
Rev No 3 Status P Date 2018-01-22 Cont ID  
Sent By AW Date 2018-01-22 Time 16:16 Rev Time 0.00
Received By awooten Date 2018-01-22 Time 15:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-01-11 Cont ID  
Sent By AW Date 2018-01-12 Time 11:22 Rev Time 0.00
Received By awooten Date 2018-01-09 Time 11:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2017-10-25 Cont ID  
Sent By   Date 2017-10-25 Time   Rev Time  
Received By   Date 2017-10-25 Time   Sent To  
Notes
2017-10-25 14:29:58*****ZONING REVIEW FAILED********
 SETBACK ENCROACHMENTS:
 STRUCTURAL INTRUSIONS. STRUCTURAL OVERHANGS, INCLUDING
 BUT NOT LIMITED TO BALCONIES, CORNICES, GUTTERS, EAVES,
 AND ROOF OVERHANG PROJECTIONS SHALL NOT EXTEND FARTHER
 THAN THREE FEET INTO ANY SETBACK.
  
 LANDSCAPING:
 GENERAL LANDSCAPING STANDARDS FOR SINGLE-FAMILY
 DWELLING UNITS SHALL BE AS FOLLOWS:
 A. SINGLE-FAMILY DWELLING UNITS. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING OR FRUIT
 TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR
 EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.
 B. PLEASE SUBMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PLAN WITH TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 MECHANICAL EQUIPMENT:
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN FOUR
 FEET INTO A SETBACK. WINDOW AIR-CONDITIONING UNITS MAY
 NOT PROJECT MORE THAN 18 INCHES INTO A REQUIRED SIDE
 SETBACK.
  
 DRIVEWAY REQUIRES A SEPARATE PERMIT.
  
 PLEASE LET ME KNOW IF YOU HAVE ANY QUESTIONS.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]