Plan Review Details - Permit 17090577
Plan Review Stops For Permit 17090577
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-10-27 Cont ID  
Sent By jleahy Date 2017-10-27 Time 11:48 Rev Time 0.00
Received By jleahy Date 2017-10-27 Time 11:48 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-09-28 Cont ID  
Sent By jleahy Date 2017-09-28 Time 18:21 Rev Time 0.00
Received By jleahy Date 2017-09-28 Time 18:18 Sent To  
Notes
2017-09-28 18:21:13FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 PROVIDE INTERIOR LIGHTING CALCULATION SHOWING
 COMPLIANCE WITH THE FBC ENERGY CODE. FBC CE 405.5
  
 PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED IN
 THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE
 OCCUPANCY SENSORS REQUIRED. FBC CE 405.2.2, 405.2.2.2

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-27 Cont ID  
Sent By jleahy Date 2017-10-27 Time 11:48 Rev Time 0.00
Received By jleahy Date 2017-10-24 Time 12:45 Sent To  
Notes
2017-10-25 12:45:18REVISION RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-28 Cont ID  
Sent By jleahy Date 2017-09-28 Time 18:21 Rev Time 0.00
Received By jleahy Date 2017-09-25 Time 14:19 Sent To  
Notes
2017-09-26 14:19:28REVISION ROUTED TO JLEAHY