Plan Review Details - Permit 17090510
Plan Review Stops For Permit 17090510
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-10-20 Cont ID  
Sent By cthroop Date 2017-10-20 Time 07:31 Rev Time 0.00
Received By cthroop Date 2017-10-20 Time 07:31 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-10-18 Cont ID  
Sent By cthroop Date 2017-10-18 Time 14:26 Rev Time 0.00
Received By cthroop Date 2017-10-18 Time 14:25 Sent To  
Notes
2017-10-18 14:27:55BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED
  
 1. PROVIDE FLOOR PLAN. IDENTIFY LOCATION OF WORK.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-10 Cont ID  
Sent By cthroop Date 2017-10-10 Time 14:22 Rev Time 0.00
Received By cthroop Date 2017-10-10 Time 14:21 Sent To  
Notes
2017-10-10 14:24:02BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND
 THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON
 RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE.
  
 1. PROVIDE FLOOR PLAN. IDENTIFY LOCATION OF WORK.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-18 Cont ID  
Sent By cthroop Date 2017-10-18 Time 14:25 Rev Time 0.00
Received By cthroop Date 2017-10-16 Time 13:11 Sent To  
Notes
2017-10-17 13:11:28RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-10 Cont ID  
Sent By cthroop Date 2017-10-10 Time 14:21 Rev Time 0.00
Received By cthroop Date 2017-09-22 Time 10:35 Sent To  
Notes
2017-09-25 10:36:00PLUMB <5K

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-10-23 Cont ID  
Sent By thunt Date 2017-10-23 Time 13:14 Rev Time 0.00
Received By thunt Date 2017-10-23 Time 13:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-10-17 Cont ID  
Sent By thunt Date 2017-10-17 Time 15:43 Rev Time 0.00
Received By thunt Date 2017-10-17 Time 15:43 Sent To  
Notes
2017-10-17 15:45:31 
  
 10/17/17 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT FOR THE 2ND
 REQUEST
  
 DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND
 THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON
 RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE.
  
 1. PROVIDE FLOOR PLAN. IDENTIFY LOCATION OF WORK. NOC
 DESCRIPTION OF WORK AS POWER ROOM RENOVATION
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-09-29 Cont ID  
Sent By thunt Date 2017-09-29 Time 14:17 Rev Time 0.00
Received By thunt Date 2017-09-29 Time 14:17 Sent To  
Notes
2017-09-29 14:21:409/29/17 1ST REVIEW PLUMBING
  
 1) DESCRIPTION OF WORK ON N.O.C STATES POWER ROOM
 RENOVATION. PROVIDE FLOOR PLAN DRAWING AND EXPLAIN WHAT
 IS TO BE DONE IN DETAIL. PROVIDE 2 COPIES FBC 107.2.1
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  