Plan Review Details - Permit 17090394
Plan Review Stops For Permit 17090394
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-09-29 Cont ID  
Sent By cthroop Date 2017-09-29 Time 15:51 Rev Time 0.00
Received By cthroop Date 2017-09-27 Time 10:46 Sent To P
Notes
2017-09-29 16:22:32BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. REPLACE CODE REFERENCE ON PLAN PAGE A1 FROM FLORIDA
 ACCESSIBILITY CODE 2012 ED TO FLORIDA BUILDING CODE
 ACCESSIBILITY 2014 5TH ED.
 2. REMOVE DESCRIPTION - ALTERATION LEVEL 2 - SOW
 INCLUDES CHANGE OF OCCUPANCY WHICH REQUIRES COMPLIANCE
 WITH LEVELS 1,2 & 3 ALTERATIONS.
 3. REFERENCE PLAN PAGE A1. NOTE STATES EXISTING
 DESIGNATED HANDICAP SPACE. PER SECTION 208.1 OF THE
 ACCESSIBILITY CODE IF PARKING IS PROVIDED IT MUST
 COMPLY WITH SECTION 208. THIS SPACE IS NON-COMPLIANT.
 PLEASE REFERENCE CHPT. 5 FOR PARKING SPACE REQUIREMENTS
 AND CHPT. 4 FOR ACCESSIBLIE ROUTE REQUIREMENTS.
 4. A RIGHT-OF-WAY PERMIT WILL BE REQUIRED PRIOR TO THE
 ISSUANCE OF THIS PERMIT. CONTACT THE ENGINEERING
 DEPARTMENT TO COORDINATE THIS PERMIT.
  
 208.1 GENERAL.
 WHERE PARKING SPACES ARE PROVIDED, PARKING SPACES SHALL
 BE PROVIDED IN ACCORDANCE WITH 208. SEE SECTION 502.5
 REQUIREMENTS FOR VAN PARKING IN STRUCTURES.
  
 1001.4 CERTIFICATE OF OCCUPANCY REQUIRED.
 A CERTIFICATE OF OCCUPANCY SHALL BE ISSUED WHERE A
 CHANGE OF OCCUPANCY OCCURS THAT RESULTS IN A DIFFERENT
 OCCUPANCY CLASSIFICATION AS DETERMINED BY THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1012.1.1 COMPLIANCE WITH CHAPTER 9 .
 THE REQUIREMENTS OF CHAPTER 9 SHALL BE APPLICABLE
 THROUGHOUT THE BUILDING FOR THE NEW OCCUPANCY
 CLASSIFICATION BASED ON THE SEPARATION CONDITIONS SET
 FORTH IN SECTIONS 1012.1.1.1 AND 1012.1.1.2
  
 1012.8 ACCESSIBILITY.
 EXISTING BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR
 OCCUPANCY CLASSIFICATION SHALL COMPLY WITH THE
 PROVISIONS OF THE FLORIDA BUILDING CODE, ACCESSIBILITY.
  
 ACCESSIBLE PARKING
  
 1. PROVIDE A LEGIBLE PLAN TO PROVIDE THE FOLLOWING
 INFORMATION PER 208.2
  
 NUMBER OF ACCESSIBLE SPACES
 LOCATION OF ACCESSIBLE ENTRANCES
 LOCATION OF ACCESSIBLE SPACES AND ACCESS AISLES
 SHOW ACCESSIBLE ROUTE FROM PUBLIC WAY
 ACCESSIBLE ROUTE FROM ACCESSIBLE SPACE TO ACCESSIBLE
 ENTRANCE
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-10-03 Cont ID  
Sent By jpearson Date 2017-10-03 Time 13:45 Rev Time 0.00
Received By jpearson Date 2017-10-03 Time 13:45 Sent To  
Notes
2017-10-03 13:45:06CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER SHOWS A 3 PHASE SERVICE WITH 3 PHASE WIRING
 GOING TO A SINGLE PHASE PANEL. PLEASE CLARIFY AND/OR
 CORRECT. FBC 107.2.1
 2. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. CHANGE OF USE
 REQUIRES ALL LIGHTING TO MEET THIS CODE. FBC CE
 405.2.2, 405.2.2.2
 3. IN THE PANEL SCHEDULES PROVIDED, INDICATE ANY NEW OR
 ALTERED CIRCUITS. FBC 107.2.1, NEC 408.4
 4. PLAN INDICATES CIRCUITS ON 2ND FLOOR, BUT NO PLAN
 FOR SECOND FLOOR IS PROVIDED. PROVIDE ELECTRICAL PLAN
 FOR 2ND FLOOR. FBC 107.2.1
 5. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 6. INDICATE THE LIGHTING CIRCUIT FOR EXIT AND EMERGENCY
 LIGHTS. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE
 FED FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. NEC
 700.12(F)
 7. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE
 CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH
 CODE. FBC CE 405.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-09-20 Cont ID  
Sent By wjolin Date 2017-09-20 Time 09:50 Rev Time 0.00
Received By wjolin Date 2017-09-20 Time 09:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-05 Cont ID  
Sent By cpuell Date 2017-10-05 Time 15:18 Rev Time 0.00
Received By cpuell Date 2017-09-19 Time 18:45 Sent To  
Notes
2017-09-19 18:45:58B16

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-10-04 Cont ID  
Sent By ccole Date 2017-10-04 Time 16:28 Rev Time 0.00
Received By ccole Date 2017-10-04 Time 16:28 Sent To  
Notes
2017-10-04 16:34:121ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSWERVATION,
 EXISTING BUILDING CODES
 PERMIT #17090394
 10/4/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PERMIT APPLICATION WHICH INDICATES INTERIOR
 IMPROVEMENTS AND "BATHROOM" FOR HARD EXERCISE WORKS
 TENANT DOES NOT MATCH THE PLANS WHICH INDICATES A
 CHANGE OF OCCUPANCY FROM A WAREHOUSE (S OCCUPANCY) TO
 AN A3 EXERCISE FACILITY. PLEASE CORRECT THE APPLICATION
 AND ADJUST THE JOB VALUE ACCORDINGLY.
  
 2) THE SUBMITTED ENERGYGAUGE COMPLIANCE SUBMITTAL IS
 PROVIDING DATA FOR ONLY 130 SF. OF THE NEW TENANT
 SPACE. HOWEVER THE ACTUAL SQUARE FOOTAGE OF THE NEW
 FACILITY IS 6,125 SQUARE FOOTAGE PER SHEET A1.PLEASE
 SEE SECTION C101.4.4 FBC-14 ENERGY CONSERVATION AND
 SHOW COMPLIANCE.
  
 3) CLARIFY IF THE SECOND FLOOR SPACE NOTED ON A1 IS A
 SEPARATE TENANT SPACE OR PART OF THE NEW EXERCISE
 OCCUPANCY. PLEASE NOTE THAT VERTICAL ACCESSIBILTY MAY
 BE REQUIRED PER SECTIONS 201 & 202 FBC-14
 ACCESSIBILITY, AS WELL AS MECHANICAL PLANS.
  
 4) SHEET A5: A SPACE HEATING SYSTEM IS REQUIRED FOR THE
 EXERCISE AREA OF THE FACILITY IN ACCORDANCE WITH
 SECTION 309.1. THE SYSTEM SHALL BE CAPABLE OF
 MAINTAINING A MINIMUM INDOOR TEMPERATURE OF 68 DEGRESS
 F. THE ARCHITECT OF RECORD IS CLAIMING AN EXCEPTION TO
 THE SIMILAR CODE SECTION FOUND IN THE FBC-14 BUILDING
 CODE (SECTION 1204.1) WHICH EXEMPTS SPACE HEATING
 SYSTEMS SPACES NOT INTENDED FOR HUMAN COMFORT. PLEASE
 NOTE THAT THE INTERNATIONAL CODE AND COMMENTARIES FOR
 THE BUILDING AND MECHANICAL CODE INDICATE WAREHOUSES
 AND COOLERS AS EXAMPLES OF SUCH EXEMPT SPACES, HOWEVER
 AN EXERCISE ROOM IS NOT USED AS AN EXAMPLE. THIS MATTER
 WILL BE REFERRED TO THE BUILDING OFFICAL FOR FURTHER
 REVIEW.
  
 5) A5: PROVIDE A VENTILATION CALCULATION FOR THE
 EXERCISE AREA- SEE SECTION 402 (NATURAL VENTILATION)
 AND TABLE 403.3 (MECHANICAL VENTILATION).
  
 6) A5: PROVIDE EXHAUST VENTILATION FOR THE BATHROOMS IN
 COMPLIANCE WITH TABLE 403.3 AND PROVIDE EXHAUST FAN
 EQUIPMENT SCHEDULES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-10-02 Cont ID  
Sent By gjohnson Date 2017-10-02 Time 14:26 Rev Time 0.00
Received By gjohnson Date 2017-10-02 Time 14:26 Sent To  
Notes
2017-10-02 14:37:161ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHOW ON ENLARGED PLAN GRAB BARS SHALL COMPLY WITH
 FBC ACC 608.3.2 WHERE A SEAT IS NOT PROVIDED IN
 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS, GRAB BARS
 SHALL BE PROVIDED ON THREE WALLS. GRAB BARS SHALL BE
 INSTALLED 6 INCHES (150 MM) MAXIMUM FROM ADJACENT
 WALLS.
  
 2. GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE TO FINISHED FLOOR. PER FBC ACC 609.4
  
 3. DIMENSION MISSING DETAIL #6 SHT. A3 SHALL COMPLY
 WITH FBC ACC 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4. SHOW COMPLIANCE FBC ACC 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 5. LAV SHALL COMPLY WITH FBC PL 416.5 TEMPERED WATER
 FOR PUBLIC HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2017-10-05 Cont ID  
Sent By   Date 2017-10-05 Time   Rev Time 0.00
Received By kmartin Date 2017-10-05 Time 10:27 Sent To I
Notes
2017-10-05 10:29:231.EXISTING TRASH RECEPTACLE CANNOT ENCROACH ADJACENT
 PROPERTY.
  
 FOR MORE INFORMATION, PLEASE CONTACT KEVIN MARTIN -
 URBAN DESIGN PLANNER ([email protected]).
  