Plan Review Details - Permit 17090382
Plan Review Stops For Permit 17090382
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-07-10 Cont ID  
Sent By rgathrig Date 2018-07-10 Time 11:36 Rev Time 0.00
Received By rgathrig Date   Time   Sent To  
Notes
2018-07-10 11:36:38PROVISO FOR SOUND TRANSMISSION TEST VERIFICATION WAS
 SUBMITTED/APPROVED UNDER 17110020 (REG)

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-11-13 Cont ID  
Sent By jwitmer Date 2017-11-13 Time 16:24 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2017-11-13 16:24:422010 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17090382
 W. P. B. PERMIT: 15111020
 ADD: 1100 S. FLAGLER DR. SUITE: UNIT 12C
 CONT: SUFFOLK
 TEL: 561-827-3678
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 SUBJECT TO FAIR HOUSING!
  
 2ND REVIEW
 DATE: MON. NOV. 13/ 2017
 ACTION: BUILDING PROVISO
  
 1) SUFFOLK CONSTRUCTION TO CONDUCT SITE TESTING FOR
 COMPLIANCE WITH THE 2010 FBC-B SECTIONS:
 FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FBC-B 2010 1207.2 AIR-BORNE SOUND.
 FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 THE SOUND TESTS WILL BE CONDUCTED ON A 10 INCH CONCRETE
 SLAB UNDER THE MAIN PERMIT (15111020) AND SUBMITTED AS
 SOON AS RESULTS ARE PRINTED AND REVIEWED BY THE
 DESIGNER OF RECORD.
  
 NOTE: SITE TESTING FOR FLOOR INSULATION WILL REQUIRE
 THE APPLICANT TO REQUEST (IN WRITING) UNDER THE 2010 W.
 P. B. ADMINISTRATIVE CODE SECTION 104.11 ALTERNATE
 MATERIALS, DESIGN AND METHODS OF CONSTRUCTION FOR THE
 SOUND UNDERLAYMENT. THE LETTER SHOULD BE MADE OUT TO
 THE BUILDING OFFICIAL ROBERT BROWN.
  
 SHEET 242.31-A6-66-12C. FINISHES. UNIT 12C.
 FLOOR FINISHES. BLDG TYPE: TYPE I/ TYPE II FLOOR
 INSULATION (FBC-B 2010)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING OR
 PROVIDE TESTING FOR THE THICKNESS FOR THE SLAB AND IF
 THERE IS A DROP CEILING WITH OR WITHOUT INSULATION OR
 PROVIDE ONSITE TESTING TO THE LISTED BELOW ASTM
 STANDARDS:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-07 Cont ID  
Sent By jwitmer Date 2017-10-07 Time 11:45 Rev Time 0.00
Received By jwitmer Date 2017-10-07 Time 11:17 Sent To  
Notes
2017-10-07 11:33:502014 FBC- BUILDING PLAN REVIEW
 2014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17090382
 W. P. B. PERMIT: 15111020
 ADD: 1100 S. FLAGLER DR. SUITE: UNIT 12C
 CONT: SUFFOLK
 TEL: 561-827-3678
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 SUBJECT TO FAIR HOUSING!
  
 1ST REVIEW
 DATE: SAT. OCT. 07/ 2017
 ACTION: DENIED
  
 1) SHEET 126.31-A2-90-12C. UNIT 12C:
  
 1A) THE MASTER BATHROOM ENTRY DOORS (U04B) ARE BOTH
 POCKET DOORS AND WILL NEED TO SHOW COMPLIANCE WITH:
 1A)(1) POCKET DOORS SHOWN IN THE OPEN POSITION MEASURE
 2.50 FT. FAIR HOUSING REQUIRES A CLEAR WIDTH OF 32
 INCHES. 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205.(C)(2)(2).
  
 1A)(2) PLEASE PROVIDE WHAT TYPE OF HANDLES WILL BE
 INSTALLED ON THE POCKET DOORS CANNOT BE FULLY RECESSED
 HARDWARE HAS TO BE ACCESSIBLE FOR PEOPLE THAT HAVE
 LIMITED HAND MOBILITY.
 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205.(C)(2)(2).FIGURE 1( C ).
  
 2) SHEET 242.31-A6-66-12C. FINISHES. UNIT 12C.
 FLOOR FINISHES. BLDG TYPE: TYPE I/ TYPE II FLOOR
 INSULATION (FBC-B 2010)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING OR
 PROVIDE TESTING FOR THE THICKNESS FOR THE SLAB AND IF
 THERE IS A DROP CEILING WITH OR WITHOUT INSULATION OR
 PROVIDE ONSITE TESTING TO THE LISTED BELOW ASTM
 STANDARDS:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-10-27 Cont ID  
Sent By jleahy Date 2017-10-27 Time 15:58 Rev Time 0.00
Received By jleahy Date 2017-10-27 Time 12:51 Sent To  
Notes
2017-10-20 15:58:28FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PLANS ARE NOT CLOUDED FOR THE REVISION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-10-06 Cont ID  
Sent By pleduc Date 2017-10-06 Time   Rev Time 0.00
Received By pleduc Date 2017-10-05 Time 16:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-13 Cont ID  
Sent By jwitmer Date 2017-11-13 Time 16:25 Rev Time 0.00
Received By jwitmer Date 2017-11-07 Time 12:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-20 Cont ID  
Sent By jleahy Date 2017-10-20 Time 15:58 Rev Time 0.00
Received By lmarchan Date 2017-10-04 Time 11:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-10-19 Cont ID  
Sent By ccole Date 2017-10-19 Time 17:42 Rev Time 0.00
Received By ccole Date 2017-10-19 Time 17:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-10-13 Cont ID  
Sent By gjohnson Date 2017-10-13 Time 15:19 Rev Time 0.00
Received By gjohnson Date 2017-10-13 Time 13:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2017-11-13 Cont ID  
Sent By jwitmer Date 2017-11-13 Time 16:26 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2017-11-13 16:25:37DIGITAL SIGNATURE FOR ARCHITECTURAL SHEETS OK. JW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2017-10-27 Cont ID  
Sent By jleahy Date 2017-10-27 Time 12:51 Rev Time 0.00
Received By jleahy Date 2017-10-27 Time 12:51 Sent To  
Notes
2017-10-13 15:20:4510/13/17 DIG SIG ON PLUMB OK/GPJ


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved