Plan Review Details - Permit 17090359
Plan Review Stops For Permit 17090359
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-09-20 Cont ID  
Sent By tklarge Date 2017-09-22 Time 07:50 Rev Time 0.00
Received By shill Date 2017-09-20 Time 16:22 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-06 Cont ID  
Sent By cpuell Date 2017-10-06 Time 14:59 Rev Time 0.00
Received By cpuell Date 2017-10-05 Time 09:39 Sent To  
Notes
2017-10-06 09:39:54RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-22 Cont ID  
Sent By tklarge Date 2017-09-22 Time 07:50 Rev Time 0.00
Received By tklarge Date 2017-09-18 Time 16:10 Sent To B
Notes
2017-09-20 16:22:54TO TL DESK

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-10-06 Cont ID  
Sent By tklarge Date 2017-10-06 Time 14:22 Rev Time 0.00
Received By thunt Date 2017-10-06 Time 14:22 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-09-22 Cont ID  
Sent By tklarge Date 2017-09-22 Time 07:49 Rev Time 0.00
Received By tklarge Date 2017-09-22 Time 06:58 Sent To  
Notes
2017-09-22 07:05:101) SUBMIT A LISTED FIRESTOPPING DETAIL FOR THE FLOOR
 PENETRATION OF THE RELOCATED RAIN WATER LEADER. SHOW
 THE FIRE RATING OF THE EXISTING FLOOR ON THE PLAN. WPB
 AMEND. TO FBC SEC. 107.2.1.
 2) THE RECOMMENDATIONS FROM WOJCIESZAK & ASSOCIATES
 REFERS TO PLUGGING THE EXISTING ROOF DRAIN FOR THE
 EXISTING RAIN WATER LEADER BUT THERE IS NO MENTION OF
 RECONNECTING THIS ROOF DRAIN. THIS ROOF DRAIN CANNOT BE
 ABANDONED. CLARIFY WHAT WILL BE DONE WITH THIS ROOF
 DRAIN IN THE REPORT.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy