Plan Review Details - Permit 17090272
| Plan Review Stops For Permit 17090272 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2018-03-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-03-21 |
Time |
17:02 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-03-21 |
Time |
16:42 |
Sent To |
|
|
| Notes |
| 2018-03-21 17:02:10 | ****PROVISOS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | MILLWORK DETAILS TO BE SUBMITTED PRIOR TO INSTALLATION, | | | TO COMPLY WITH FBC ACCESSIBILITY | | | | | | THERE IS A DISCREPANCY BETWEEN PROPERTY APPRAISER | | | BUILDING TOTAL SF AREA OF 10,161 AND THE SF AREA SHOWN | | | ON LS-1, BUILDING AREA & HEIGHT CALCULATION, 6313. | | | CORRELATE AND SUBMIT AS A REVISION, REQUIRED PRIOR TO | | | FIRST INSPECTION (SUBMIT WITH PLUMBING REVISION). | | | | | | ******************************************************* | | | ************** | | | INTERNAL USE ONLY: | | | USC-404 TYPE 437 - ALT:NON-RES,NON-HSKPG | | | SQUARE FEET - 6313 | | | | | | CONSTRUCTION TYPE: 14-III-B - 5TH ED TYPE III-B | | | UNITS: 1 | | | FLOORS: 1 | | | BEDROOMS: | | | ROOMS: | | | SQ FT LIVABLE: 6313 | | | SQ FT FOOTPRINT: 6313 | | | SQ FT ROOF: 6313 | | | | | | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF | | | KNOWN): | | | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): | | | XX.XX | | | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: | | | XX.XX | | | OCC LOAD: | | | PROP USE: RUM DISTILLERY/TASTING TOURS/MERCANTILE | | | SPRINKLER SYS? Y | | | SPRK REQ'D? Y | | | BATHRMS: | | | | | | BLDG CODE: FL 2014 | | | OCC CLASS: 5TH ED F1,M | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2018-03-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-03-17 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-03-17 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2018-03-17 16:46:59 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1-14. OK | | | | | | 15. PN25 MERCANTILE AREA, S4, ACCESSIBLE COUNTER SHOWN | | | 30" DEPTH. PROVIDE A DETAIL OR REVISE PLAN TO SHOW | | | COMPLIANCE WITH FBC A 902.3. | | | | | | PN25 TASTING TOURS AREA, PROVIDE A DETAIL TO SHOW | | | COMPLIANCE WITH FBC A 902.3. | | | | | | 2ND REVIEW, THE TWO COUNTERS LABELED PN25 HAVE BEEN | | | RENUMBERED. RESPONSE LETTER DID NOT INDICATE WHERE | | | DETAILS FOR THE COUNTERS SHOWING COMPLIANCE WITH FBC | | | A902.3 CAN BE FOUND. EITHER ADVISE, OR REQUEST A | | | PROVISO: COMPLIANCE WITH FBC A902.3 REQUIRED, REVISION | | | REQUIRED SUBJECT TO INSPECTOR'S DISCRETION. | | | | | | 3RD REVIEW, DETAILS WERE PROVIDED. 03-S1 IS NOT CLEAR | | | AS TO COMPLIANCE AS IT LACKS DIMENSIONS. 02-S1 LACKS | | | THE KNEE AND TOE CLEARANCE REQUIRED BY FBC A 306. | | | | | | 16. PN25, PROVIDE A DETAIL SHOWING COMPLIANCE WITH FBC | | | A 227 (CHECK OUT AISLE). | | | | | | 3RD REVIEW, SEE ITEM 15. DETAILS PROVIDED EITHER ARE | | | NOT CLEAR AS TO COMPLIANCE (03-S1) OR IS NOT COMPLIANCE | | | (02-S1). ALTHOUGH IT IS UNDERSTOOD THAT MILLWORK WILL | | | BE CUSTOM, THE PLANS SHOULD SET FORTH THE DESIGN | | | CRITERIA FOR CODE COMPLIANCE. | | | | | | 17-22. OK | | | | | | 23. SEE FS 553.80(2)(B). DUE TO THE NUMEROUS COMMENTS | | | FROM MULTIPLE TRADES, PRIOR TO RESUBMITTAL APPLICANT | | | (CONTRACTOR IS SUGGESTED) IS TO REVIEW COMMENTS AND | | | PLANS, CONFIRM ALL COMMENTS HAVE BEEN ADDRESSED, AND | | | SCHEDULE A PRE-RESUBMITTAL MEETING. | | | | | | 24. OK | | | | | | NEW COMMENT 3RD REVIEW: | | | | | | 25. EXPLAIN THE DISCREPANCY BETWEEN PROPERTY APPRAISER | | | BUILDING TOTAL SF AREA OF 10,161 AND THE SF AREA SHOWN | | | ON LS-1, BUILDING AREA & HEIGHT CALCULATION, 6313. IS | | | THERE A FIRE WALL, REQUIRED TO BE 3 HOURS, WHICH MEETS | | | ALL REQUIREMENTS TO BE ABLE TO CONSIDER THE TWO AREAS | | | TWO SEPARATE BUILDINGS? IF YES, REVISE THE PLAN TO | | | CLARIFY. IF NO, THE AREA CALCULATIONS ARE NOT CORRECT | | | AS THEY CONSIDER ONLY A PORTION OF THE BUILDING. SEE | | | FBC CHAPTER 5. | | | ******************************************************* | | | ************** | | | INTERNAL USE ONLY: | | | USC-404 TYPE 437 - ALT:NON-RES,NON-HSKPG | | | SQUARE FEET - 6313 | | | | | | CONSTRUCTION TYPE: 14-III-B - 5TH ED TYPE III-B | | | UNITS: 1 | | | FLOORS: 1 | | | BEDROOMS: | | | ROOMS: | | | SQ FT LIVABLE: 6313 | | | SQ FT FOOTPRINT: 6313 | | | SQ FT ROOF: 6313 | | | | | | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF | | | KNOWN): | | | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): | | | XX.XX | | | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: | | | XX.XX | | | OCC LOAD: | | | PROP USE: RUM DISTILLERY/TASTING TOURS/MERCANTILE | | | SPRINKLER SYS? Y | | | SPRK REQ'D? Y | | | BATHRMS: | | | | | | BLDG CODE: FL 2014 | | | OCC CLASS: 5TH ED F1,M | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-01-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-01-04 |
Time |
17:05 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-01-02 |
Time |
14:49 |
Sent To |
|
|
| Notes |
| 2018-01-04 17:07:36 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. SEE PREVIOUS COMMENT. PLAN COMPLIES AS A | | | "SUBSTANTIAL IMPROVEMENT". HOWEVER, RESPONSE LETTER | | | STATES THAT THIS IS NOT A SUBSTANTIAL IMPROVEMENT DUE | | | TO REDUCTION OF SCOPE AND THAT A COST BREAKDOWN WOULD | | | BE PROVIDED. THIS WAS NOT PROVIDED. | | | | | | THIS COMMENT MAY BE DISREGARDED IF APPLICANT DOES NOT | | | OBJECT TO "SUBSTANTIAL IMPROVEMENT" DETERMINATION. | | | | | | 2-7. OK | | | | | | 8. FBC EB 301.1, THIS APPEARS TO BE A CHANGE OF | | | OCCUPANCY (CH 10). A CURSORY LOOK INTO RECORDS FOR THIS | | | BUILDING APPEAR TO REFLECT THAT CURRENT OCCUPANCY IS | | | BUSINESS OR STORAGE. IF THIS IS A CHANGE OF OCCUPANCY, | | | REVISE PLAN TO NOTE THE CHANGE OF OCCUPANCY FROM | | | CURRENT OCCUPANCY TO MIXED OCCUPANCY F1, M, AND | | | POSSIBLE ANOTHER OCCUPANCY (TASTING/TOURS). | | | | | | 2ND REVIEW, RESPONSE STATES THAT THIS IS A CHANGE OF | | | OCCUPANCY FROM BUSINESS TO F1, AND PLANS HAVE BEEN | | | REVISED TO STATE SUCH, THEN RESPONSE MAKES SOME | | | STATEMENTS REGARDING COMPLIANCE. I WAS UNABLE TO | | | LOCATION THE INFORMATION WHICH STATES THAT THIS IS | | | CURRENTLY BUSINESS, PROPOSED F1 WITH ACCESSORY | | | MERCANTILE; IF THIS IS ON THE PLAN AS STATED, PLEASE | | | PROVIDE THE PAGE NUMBER AND THIS COMMENT WILL BE | | | REMOVED. | | | | | | 9-13. OK | | | | | | 14. S4, A DASHED LINE (3') AT THE ENTRY DOOR IS SHOWN. | | | CLARIFY WHAT THIS IS. REVISE PLAN TO SHOW ACCESSIBLE | | | ROUTE AT ENTRY DOOR WHICH COMPLIES WITH FBC A 303.2 | | | (SEE ALSO FBC A 202.3). | | | | | | 2ND REVIEW, I WAS UNABLE TO LOCATE THE NOTE SHOWING | | | COMPLIANCE WITH THE REQUIREMENT FOR AN ACCESSIBLE | | | ENTRY, PLEASE ADVISE. | | | | | | 15. PN25 MERCANTILE AREA, S4, ACCESSIBLE COUNTER SHOWN | | | 30" DEPTH. PROVIDE A DETAIL OR REVISE PLAN TO SHOW | | | COMPLIANCE WITH FBC A 902.3. | | | | | | PN25 TASTING TOURS AREA, PROVIDE A DETAIL TO SHOW | | | COMPLIANCE WITH FBC A 902.3. | | | | | | 2ND REVIEW, THE TWO COUNTERS LABELED PN25 HAVE BEEN | | | RENUMBERED. RESPONSE LETTER DID NOT INDICATE WHERE | | | DETAILS FOR THE COUNTERS SHOWING COMPLIANCE WITH FBC | | | A902.3 CAN BE FOUND. EITHER ADVISE, OR REQUEST A | | | PROVISO: COMPLIANCE WITH FBC A902.3 REQUIRED, REVISION | | | REQUIRED SUBJECT TO INSPECTOR'S DISCRETION. | | | | | | 16. PN25, PROVIDE A DETAIL SHOWING COMPLIANCE WITH FBC | | | A 227 (CHECK OUT AISLE). | | | | | | 2ND REVIEW, THE TWO COUNTERS LABELED PN25 HAVE BEEN | | | RENUMBERED. RESPONSE LETTER DID NOT INDICATE WHERE | | | DETAILS FOR THE COUNTERS SHOWING COMPLIANCE WITH FBC | | | A902.3 CAN BE FOUND. EITHER ADVISE, OR REQUEST A | | | PROVISO: COMPLIANCE WITH FBC A902.3 REQUIRED, REVISION | | | REQUIRED SUBJECT TO INSPECTOR'S DISCRETION. | | | | | | 17. NO FIRE SPRINKLER INFORMATION PROVIDED. EITHER | | | PROVIDE A PLAN OR INCORPORATE ALL REQUIREMENTS OF FBC B | | | 404.6 EXCEPTION INTO THE PLAN. | | | | | | 2ND REVIEW, RESPONSE STATES: THE FIRE SPRINKLER DESIGN | | | AND DRAWINGS ARE PROVIDED VIA SEPARATE PERMIT BY A | | | SPECIALTY ENGINEER ..." | | | | | | SEE FIRE COMMENTS AND FBC 107.3.5.1.1(5). ALTHOUGH THE | | | MEZZANINE EXCEPTION IS NOT LONGER APPLICABLE, FIRE | | | SUPPRESSION INFORMATION TO BE INCORPORATED INTO THE | | | PLAN PRIOR TO PERMIT ISSUANCE. SEE FIRE COMMENTS; IT IS | | | ACKNOWLEDGED THAT THE FIRE SHOP DRAWINGS AND PERMIT MAY | | | BE SUBMITTED AFTER PERMIT ISSUANCE. IF FIRE'S COMMENT | | | IS NOT CLEAR AS TO WHAT IS REQUIRED WITH THIS BUILDING | | | PERMIT SUBMITTAL, PLEASE CONTACT THE FIRE REVIEWER FOR | | | CLARIFICATION. | | | | | | 18. OK | | | | | | 19. LS2, TRAVEL DISTANCE IS SHOWN AS 94' TO THE BASE OF | | | THE STAIR. SEE FBC B 1016.3, EXIT ACCESS TRAVEL | | | DISTANCE IS TO BE MEASURED FROM THE MOST REMOTE POINT | | | WITHIN A STORY ALONG THE NATURAL AND UNOBSTRUCTED PATH | | | OF HORIZONTAL AND VERTICAL EGRESS TRAVEL TO THE | | | ENTRANCE TO AN EXIT. IT APPEARS THAT THE MEASUREMENT IS | | | TO THE BASE OF THE STAIR, AT WHICH POINT OCCUPANT IS | | | REQUIRED TO GO THROUGH THE FIRST FLOOR TO REACH AN | | | EXIT, PLEASE REVISE OR CLARIFY. SEE ALSO FBC B 404.9 | | | (<200' TRAVEL DISTANCE). | | | | | | 20. FBC 107, PALLET RACKS, REVISE PLAN TO INCLUDE | | | HEIGHT LIMITATION. | | | | | | RESPONSE LETTER STATES THAT THIS IS PREDICATED UPON THE | | | TYPE(S) OF FIRE SPRINKLERS SPECIFIED AND IS TYPICALLY | | | PROVIDED BY THE FIRE SPRINKLER SPECIALTY ENGINEER. | | | REVIEW OF THIS ITEM WILL BE DONE WHEN FIRE SPRINKLER | | | INFORMATION REQUIRED BY FIRE IS PROVIDED. | | | | | | 21-22. OK | | | | | | NEW COMMENTS: | | | | | | 23. SEE FS 553.80(2)(B). DUE TO THE NUMEROUS COMMENTS | | | FROM MULTIPLE TRADES, PRIOR TO RESUBMITTAL APPLICANT | | | (CONTRACTOR IS SUGGESTED) IS TO REVIEW COMMENTS AND | | | PLANS, CONFIRM ALL COMMENTS HAVE BEEN ADDRESSED, AND | | | SCHEDULE A PRE-RESUBMITTAL MEETING. | | | | | | 24. ADVISORY ONLY - PRODUCT APPROVALS WERE SUBMITTED. | | | PLEASE BE ADVISED THAT THIS IS OPTIONAL AT THIS TIME. | | | THIS MAY, UPON REQUEST, BE A DEFERRED SUBMITTAL AND MAY | | | BE SUBMITTED, NO FEE, TO BE REVIEWED PRIOR TO | | | INSTALLATION. IT IS ACCEPTABLE TO PROVIDE PRODUCT | | | APPROVALS AT THIS TIME, BUT A REVISION FEE WILL BE | | | CHARGED IF THE PRODUCT IS CHANGED AFTER ISSUANCE. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-10-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-10-05 |
Time |
17:12 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-10-03 |
Time |
17:20 |
Sent To |
|
|
| Notes |
| 2017-10-05 17:12:55 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. THIS PROJECT APPEARS TO BE A "SUBSTANTIAL | | | IMPROVEMENT" AS THE VALUE OF THE IMPROVEMENT EXCEEDS | | | 50% OF THE STRUCTURE VALUE PER PALM BEACH COUNTY | | | PROPERTY APPRAISER ($310,000 PERMIT VALUE / $578,777 | | | PAPA STRUCTURE VALUE). AS THE BFE IS 13' NGVD29, | | | LOCATED IN FLOOD ZONE A9, PER FIRM PANEL 120229 0020B, | | | WITH A 1' FREEBOARD PER CITY OF WEST PALM BEACH | | | MUNICIPAL CODE 94-546(B)(2). | | | | | | FBC EB 403.2, THE STRUCTURE AND EQUIPMENT ARE TO COMPLY | | | WITH THE MINIMUM DFE OF 14' NGVD29. IT APPEARS THAT THE | | | STRUCTURE LIKELY COMPLIES (ALTHOUGH ACTUAL FFE IS NOT | | | CLEAR, SEE OTHER COMMENT REGARDING LOWEST AND NEXT | | | FLOOR); COMPLIANCE FOR MECHANICAL EQUIPMENT NOT CLEAR. | | | | | | 2. S1 DEPICTS TWO SEPARATE BUILDINGS CONNECTED WITH A | | | COMMON WALL, BOTH LABELED AS "EXISTING ONE STORY | | | BUILDING". THEY APPEAR TO BE ONE BUILDING, STRUCTURALLY | | | CONNECTED. IF THEY ARE TWO BUILDINGS, REVISE PLAN TO | | | STATE HOW THIS HAS BEEN DETERMINED. IF THEY ARE ONE | | | BUILDING, REVISE THE LABELS. | | | | | | 3. PROVIDE A COPY OF THE SURVEY FOR THIS PROPERTY, FBC | | | 107, FBC EB 403.2. | | | | | | 4. FBC EB 403.2, FBC B 1603.1.7, SHEET S4 SHOWS | | | ELEVATION AS 0'0", AND REFERS TO NAVD88 ELEVATIONS ON | | | SURVEY. NO SURVEY WAS PROVIDED. | | | | | | PLEASE REVISE S4 TO INCORPORATE THE EXISTING AND | | | PROPOSED FFE. CLARIFY FFE FOR THE CONNECTED BUILDING | | | CURRENTLY LABELED AS "EXISTING ONE STORY BUILDING". | | | | | | IT IS RECOMMENDED THAT, SINCE THE APPLICATION WAS | | | SUBMITTED PRIOR TO OCTOBER 5, 2017, THAT THE VERTICAL | | | DATUM ON THE BUILDING PLANS UTILIZE NGVD29. IF NAVD88 | | | IS UTILIZED ON THE BUILDING PLANS, INCLUDE A CONVERSION | | | (AND NOTE METHOD OF CONVERSION) SO COMPLIANCE WITH THE | | | REQUIREMENTS OF FBC EB 403.2 IS CLEAR. | | | | | | ALL ELEVATION CERTIFICATES CERTIFIED OCTOBER 5, 2017 | | | AND LATER ARE TO UTILIZE NAV88 AND INCLUDE A CONVERSION | | | TO NGVD29. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS. | | | | | | 5. FBC EB 403.2, REVISE THE PLAN TO CLARIFY THAT FFE | | | AND ALL EQUIPMENT SERVICING THE BUILDING ARE PROPOSED | | | TO BE ELEVATED OR INSTALLED AT > 14'NGVD29. REVISE THE | | | PLAN TO INCLUDE ALL EQUIPMENT SERVICING THE BUILDING. | | | | | | 6. FBC EB 403.2, COMMENTS REGARDING THE ELEVATION | | | CERTIFICATE PROVIDED: | | | | | | A. PROVIDE A "CONSTRUCTION DRAWINGS" ELEVATION | | | CERTIFICATE TO SHOW/CLARIFY PROPOSED CONSTRUCTION. | | | | | | B. ELEVATION CERTIFICATE ITEM C2(E), MECHANICAL | | | EQUIPMENT ELEVATION IS BLANK; PLEASE REVISE WITH NOTES | | | IF NEEDED. WATER HEATER? ROOFTOP MECHANICAL EQUIPMENT? | | | PLEASE CONTACT ME IF YOU WISH TO DISCUSS. | | | | | | C. THE ELEVATION CERTIFICATE, ITEM C2A TOP OF BOTTOM | | | FLOOR, 14.54, AND ITEM B, TOP OF NEXT FLOOR, AS 14.09. | | | PLEASE CORRECT. FFE IS NOT CLEAR. NOTE THAT BOTH COMPLY | | | WITH BFE + 1' FREEBOARD. | | | | | | D. A1, OWNER ON EC IS "HEALTHCARE REAL ESTATE CAPITAL"; | | | THIS IS IN CONFLICT WITH PROPERTY APPRAISER RECORDS. | | | REVISE OR CLARIFY. | | | | | | E. A9 INDICATES AN 1813 SF GARAGE, C2(D) ELEVATION IS | | | "NA" AND SHEET S1 DOES NOT SHOW A GARAGE, PLEASE | | | CORRELATE. | | | | | | F. C2 BENCHMARK, SEE INSTRUCTIONS: INCLUDE PERMANENT | | | IDENTIFIER (PID). ON THE EC, BENCHMARK UTILIZED IS | | | "LOCAL"; IT IS NOT CLEAR IF THAT MEANS A LOCAL | | | BENCHMARK, OR IF THE NAME OF THE BENCHMARK IS "LOCAL". | | | | | | G. SECTION E (E1-E5), PLEASE REVISE TO INCLUDE "NA" FOR | | | FIELDS WHICH ARE CURRENTLY. | | | | | | 7. THIS PERMIT WILL BE ISSUED WITH PROVISO; PRIOR TO | | | CONCRETE POUR, A "BUILDING UNDER CONSTRUCTION" | | | ELEVATION CERTIFICATE OR FORM BOARD SURVEY WITH | | | ELEVATIONS WILL BE REQUIRED. PRIOR TO FINAL INSPECTION, | | | A "FINISHED CONSTRUCTION" ORIGINAL SIGNED AND SEALED | | | ELEVATION CERTIFICATE, WITH COLOR PHOTOGRAPHS OF ALL | | | SIDES OF THE STRUCTURE AND EXTERIOR MECHANICAL | | | EQUIPMENT (WITH TIE DOWNS VISIBLE IN PHOTOS) WILL BE | | | REQUIRED. SUBMIT THE "FINISHED CONSTRUCTION" ELEVATION | | | CERTIFICATE AT THE BUILDING DIVISION AS A SUBMITTAL (NO | | | FEE) FOR REVIEW WHEN AVAILABLE. | | | | | | 8. FBC EB 301.1, THIS APPEARS TO BE A CHANGE OF | | | OCCUPANCY (CH 10). A CURSORY LOOK INTO RECORDS FOR THIS | | | BUILDING APPEAR TO REFLECT THAT CURRENT OCCUPANCY IS | | | BUSINESS OR STORAGE. IF THIS IS A CHANGE OF OCCUPANCY, | | | REVISE PLAN TO NOTE THE CHANGE OF OCCUPANCY FROM | | | CURRENT OCCUPANCY TO MIXED OCCUPANCY F1, M, AND | | | POSSIBLE ANOTHER OCCUPANCY (TASTING/TOURS). | | | | | | VIA A RECORDS RESEARCH REQUEST, PLEASE DETERMINE THE | | | CURRENT OCCUPANCY AS PERMITTED; CONTACT | | | [email protected]. | | | | | | 9. THE PROCESSING PORTION HAS TEXT WHICH STATES: | | | "TASTING/TOURS". SEE FBC B 302: "A ROOM OR SPACE THAT | | | IS INTENDED TO BE OCCUPIED AT DIFFERENT TIMES FOR | | | DIFFERENT PURPOSES SHALL COMPLY WITH ALL OF THE | | | REQUIREMENTS THAT ARE APPLICABLE TO EACH OF THE | | | PURPOSES FOR WHICH THE ROOM OR SPACE WILL BE OCCUPIED." | | | | | | NOT ENOUGH INFORMATION TO DETERMINE CODE COMPLIANCE. IF | | | THIS AREA WILL BE USED FOR TOURS/TASTING, IT APPEARS | | | THAT THE AREA WOULD ALSO BE SUBJECT TO ACCESSIBILITY. | | | AN F1 OCCUPANT LOAD OF 51 IS DECLARED; IS THE | | | TOURS/TASTING OCCUPANT LOAD IN ADDITION TO THIS | | | OCCUPANT LOAD OR INCLUSIVE? WHAT IS THE OCCUPANT LOAD | | | ANTICIPATED FOR THE TOURS/TASTING VS. F1 OCCUPANT LOAD? | | | | | | 10. IF THIS IS A CHANGE OF OCCUPANCY, SEE FBC EB TABLES | | | 1012.4 THROUGH 1012.6. IN ANY CASE WHERE CHANGE OF | | | OCCUPANCY IS MADE TO A HIGHER HAZARD, REVISE PLAN TO | | | SHOW COMPLIANCE. | | | | | | 11. SEE IMPACT FEE REVIEW. PLAN IS TO BE CLEAR AS TO | | | PREVIOUS USE/OCCUPANCY (PERMITTED AND INSPECTED) SO | | | THEY CAN PERFORM AN ACCURATE REVIEW. | | | | | | IT APPEARS THAT ADDITIONAL SQUARE FOOT AREA IS BEING | | | ADDED (CREATING A 2ND FLOOR). REVISE THE PLAN TO | | | CLARIFY EXISTING SF AREA, PROPOSED NEW. | | | | | | 12. THE DOOR TO "MOLASSES TANKS" ROOM LACKS THE | | | MANEUVERING CLEARANCE REQUIRED BY FBC A TABLE 404.2.4.1 | | | (A), 18" PULL SIDE. THIS APPEARS TO BE A WORK AREA; SEE | | | FBC A 206.2.8 REGARDING EMPLOYEE WORK AREAS. IF AN | | | EXEPTION IS APPLICABLE, REVISE PLAN TO INCLUDE | | | EXCEPTION. | | | | | | 13. FBC A TABLE 404.2.4.1(A), REVISE PLAN TO SHOW 18" | | | MANEUVERING CLEARANCE REQUIRED FOR DOOR DR 3. | | | | | | 14. S4, A DASHED LINE (3') AT THE ENTRY DOOR IS SHOWN. | | | CLARIFY WHAT THIS IS. REVISE PLAN TO SHOW ACCESSIBLE | | | ROUTE AT ENTRY DOOR WHICH COMPLIES WITH FBC A 303.2 | | | (SEE ALSO FBC A 202.3). | | | | | | 15. PN25 MERCANTILE AREA, S4, ACCESSIBLE COUNTER SHOWN | | | 30" DEPTH. PROVIDE A DETAIL OR REVISE PLAN TO SHOW | | | COMPLIANCE WITH FBC A 902.3. | | | | | | PN25 TASTING TOURS AREA, PROVIDE A DETAIL TO SHOW | | | COMPLIANCE WITH FBC A 902.3. | | | | | | 16. PN25, PROVIDE A DETAIL SHOWING COMPLIANCE WITH FBC | | | A 227 (CHECK OUT AISLE). | | | | | | 17. NO FIRE SPRINKLER INFORMATION PROVIDED. EITHER | | | PROVIDE A PLAN OR INCORPORATE ALL REQUIREMENTS OF FBC B | | | 404.6 EXCEPTION INTO THE PLAN. | | | | | | 18. REVISE PLAN TO INDICATE FLOOR DESIGN LIVE LOAD, OR | | | ADVISE WHERE THIS INFORMATION CAN BE LOCATED. REVISE | | | PLAN TO INCLUDE THE REQUIREMENTS OF FBC B 106.1, 106.2: | | | | | | 106.1 LIVE LOADS POSTED. WHERE THE LIVE LOADS FOR WHICH | | | EACH FLOOR OR PORTION THEREOF OF A COMMERCIAL OR | | | INDUSTRIAL BUILDING IS OR HAS BEEN DESIGNED TO EXCEED | | | 50 PSF (2.40 KN/M2), SUCH DESIGN LIVE LOADS SHALL BE | | | CONSPICUOUSLY POSTED BY THE OWNER IN THAT PART OF EACH | | | STORY IN WHICH THEY APPLY, USING DURABLE SIGNS. IT | | | SHALL BE UNLAWFUL TO REMOVE OR DEFACE SUCH NOTICES | | | | | | 106.2 ISSUANCE OF CERTIFICATE OF OCCUPANCY. A | | | CERTIFICATE OF OCCUPANCY REQUIRED BY SECTION 111 SHALL | | | NOT BE ISSUED UNTIL THE FLOOR LOAD SIGNS, REQUIRED BY | | | SECTION 106.1, HAVE BEEN INSTALLED. | | | | | | 19. LS2, TRAVEL DISTANCE IS SHOWN AS 94' TO THE BASE OF | | | THE STAIR. SEE FBC B 1016.3, EXIT ACCESS TRAVEL | | | DISTANCE IS TO BE MEASURED FROM THE MOST REMOTE POINT | | | WITHIN A STORY ALONG THE NATURAL AND UNOBSTRUCTED PATH | | | OF HORIZONTAL AND VERTICAL EGRESS TRAVEL TO THE | | | ENTRANCE TO AN EXIT. IT APPEARS THAT THE MEASUREMENT IS | | | TO THE BASE OF THE STAIR, AT WHICH POINT OCCUPANT IS | | | REQUIRED TO GO THROUGH THE FIRST FLOOR TO REACH AN | | | EXIT, PLEASE REVISE OR CLARIFY. SEE ALSO FBC B 404.9 | | | (<200' TRAVEL DISTANCE). | | | | | | 20. FBC 107, PALLET RACKS, REVISE PLAN TO INCLUDE | | | HEIGHT LIMITATION. | | | | | | 21. FBC A 213.1, 206.2.3, DEFINITION OF "ADDITION" | | | 106.5, 202.2, PRIOR TO RESUBMITTING, SEND VIA EMAIL THE | | | RATIONALE FOR NOT PROVIDING ACCESSIBLE BATHING | | | FACILITIES ON THE FIRST FLOOR. ALSO PROVIDE RATIONALE | | | FOR LACK OF ACCESSIBLE BATHING FACILITY ON THE 2ND | | | FLOOR. | | | | | | SEE ALSO HTTPS://WWW.ACCESS-BOARD.GOV/GUIDELINES-AND-ST | | | ANDARDS/BUILDINGS-AND-SITES/ABOUT-THE-ADA-STANDARDS/GUI | | | DE-TO-THE-ADA-STANDARDS/CHAPTER-4-ACCESSIBLE-ROUTES | | | | | | 22. REVISE PLAN TO EXPLAIN PURPOSE OF INTERIOR WINDOWS | | | ON 2ND FLOOR, FBC 107. IS THIS FOR VISITORS, EMPLOYEES, | | | AND WHY? PLEASE SEND VIA EMAIL PRIOR TO RESUBMITTAL SO | | | IT CAN BE DETERMINED IF ADDITIONAL INFORMATION IS | | | REQUIRED. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS | | | ANY OF THE ISSUES/INQUIRIES RAISED IN THIS PLAN REVIEW. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-03-20 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-03-20 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-03-20 |
Time |
11:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2017-12-27 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-12-27 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-12-27 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2017-12-27 10:08:51 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS ADDRESSED SATISFACTORILY HAVE BEEN | | | NOTED AS CORRECTED. COMMENTS REMAINING HAVE ADDITIONAL | | | COMMENTS IN PARENTHESES. | | | | | | 1. PANEL M IS SHOWN AS A 600 AMP PANEL, BUT THE LOAD ON | | | A PHASE IS 640.21 AMPS AND THE LOAD ON C PHASE IS 646 | | | AMPS, WHICH EXCEEDS THE CAPACITY OF THE PANEL. PROVIDE | | | CORRECTION. NEC 408.30 (A PHASE LOAD IS SHOWN AS 78.2 | | | KVA, WHICH DIVIDED BY 120 EQUALS 651.67 AMPS. C PHASE | | | LOAD IS SHOWN AS 77.4 KVA, WHICH DIVIDED BY 120 EQUALS | | | 645 AMPS. THIS WILL EXCEED THE CAPACITY OF THE WIRE, | | | THE PANEL, AND THE MAIN BREAKER. PROVIDE CORRECTION AS | | | PREVIOUSLY REQUESTED.) NEC 310.15(B)(16) | | | 2. CORRECTED. | | | 3. PANEL C LOAD CALCULATION IS LABELED AS "PANEL A LOAD | | | CALCS". ADDITIONALLY, THE MATH IS WRONG FOR THE TOTALS | | | ON A PHASE. BY MY ADDITION OF THE LOADS STATED, THE | | | TOTAL LOAD ON THIS PHASE WOULD BE 136 AMPS, WHICH | | | EXCEEDS THE RATING OF THE WIRE AND THE VALUE OF THE | | | CIRCUIT BREAKER FEEDING THE PANEL. PROVIDE CORRECTION. | | | NEC 220, 310.15(B)(16), 408.30, 215.2; FBC 107.2.1 | | | (THIS WAS PARTIALLY CORRECTED. LOAD CALCS ARE NOW | | | LABELED CORRECTLY. HOWEVER, A PHASE LOAD IS SHOWN AS | | | 15.6 KVA, WHICH DIVIDED BY 120 VOLTS EQUALS 130 AMPS. | | | THIS WILL EXCEED THE CAPACITY OF THE PANEL AND BREAKER | | | FEEDING THE PANEL. PROVIDE CORRECTION AS PREVIOUSLY | | | REQUESTED.) | | | 4. CORRECTED. | | | 5. CORRECTED. | | | 6. CORRECTED. | | | | | | NEW COMMENT: PLEASE BE ADVISED THAT THIS COMMENT HAS | | | NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD | | | REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN | | | A THIRD TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN | | | REVIEW IS REQUIRED. FLORIDA STATUTES STATE: ?WITH | | | RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? | | | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN | | | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING | | | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS | | | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO | | | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY | | | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, | | | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)? | | | | | | END OF COMMENTS | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-10-16 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-10-16 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-10-16 |
Time |
16:32 |
Sent To |
|
|
| Notes |
| 2017-10-16 16:32:22 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PANEL M IS SHOWN AS A 600 AMP PANEL, BUT THE LOAD ON | | | A PHASE IS 640.21 AMPS AND THE LOAD ON C PHASE IS 646 | | | AMPS, WHICH EXCEEDS THE CAPACITY OF THE PANEL. PROVIDE | | | CORRECTION. NEC 408.30 | | | 2. LOAD CALCULATION FOR PANELS M, B, AND C NEED | | | CORRECTION. THE RECEPTACLE LOAD STATES THAT THE FIRST | | | 10K VA IS FIGURED AT 100%, BUT THE ACTUAL AMOUNT | | | FIGURED AT 100% IS ONLY 5K VA. PROVIDE CORRECTION. NEC | | | 220; FBC 107.2.1 | | | 3. PANEL C LOAD CALCULATION IS LABELED AS "PANEL A LOAD | | | CALCS". ADDITIONALLY, THE MATH IS WRONG FOR THE TOTALS | | | ON A PHASE. BY MY ADDITION OF THE LOADS STATED, THE | | | TOTAL LOAD ON THIS PHASE WOULD BE 136 AMPS, WHICH | | | EXCEEDS THE RATING OF THE WIRE AND THE VALUE OF THE | | | CIRCUIT BREAKER FEEDING THE PANEL. PROVIDE CORRECTION. | | | NEC 220, 310.15(B)(16), 408.30, 215.2; FBC 107.2.1 | | | 4. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED | | | SEPARATE PERMITS AND DATA SPECIFICATION SHEET | | | SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS, | | | FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, | | | WALK-IN COOLERS, HOODS, ETC. FBC 105.1, 107.2.1 | | | 5. LIGHTING PLAN SHOWS ALL CIRCUITS FOR LIGHTING BEING | | | FED FROM PANEL A, WHICH CONFLICTS WITH THE PANEL | | | SCHEDULE FOR PANEL A. PROVIDE CORRECTION. NEC 408.4; | | | FBC 107.2.1 | | | 6. PANEL M HAS THE CAPACITY TO EXCEED THE MAXIMUM | | | NUMBER OF DISCONNECTS PERMITTED FOR A SERVICE, WHICH IS | | | 6. PROVIDE EITHER MAIN BREAKER FOR PANEL OR DISCONNECT | | | AHEAD OF PANEL. NEC 230.71 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2018-03-01 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-03-01 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-03-01 |
Time |
08:08 |
Sent To |
|
|
| Notes |
| 2018-03-01 10:18:51 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) SEPARATE SHOP DRAWINGS SHALL BE SUBMITTED FOR THE | | | FIRE SPRINKLER SYSTEM UNDER A SEPARATE PERMIT #. | | | | | | THE APPROVAL OF THE SPRINKLER DOCUMENTS IS ONLY FOR THE | | | MASTER PERMIT 61G CONCEPTUAL DRAWINGS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2017-12-12 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2017-12-12 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2017-12-12 |
Time |
14:23 |
Sent To |
|
|
| Notes |
| 2017-12-12 14:29:17 | 1615 CLARE AVENUE | | | PERMIT #17090272 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | REPEAT COMMENT - ENGINEERED FIRE SPRINKLER CONSTRUCTION | | | DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT. | | | AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE | | | SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS | | | (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS) | | | FOR A SUB-PERMIT. PER FLORIDA ADMINISTRATIVE CODE | | | SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING | | | DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE | | | WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS | | | APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD | | | OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM | | | TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP | | | DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED | | | INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS. | | | | | | REPEAT COMMENT - PROVIDE TACTILE SIGNAGE AT ALL | | | REQUIRED EXIT DOORS WITH EXIT SIGNS. | | | | | | REPEAT COMMENT - PROVIDE AN EXTERIOR KEY SAFE TO ALLOW | | | EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE | | | BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE | | | ORDERED FROM WWW.KNOXBOX.COM. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2017-09-20 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2017-09-20 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2017-09-20 |
Time |
13:21 |
Sent To |
|
|
| Notes |
| 2017-09-20 13:26:01 | 1615 CLARE AVENUE | | | PERMIT #17090272 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE | | | REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE | | | BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN | | | THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED | | | CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. PER FLORIDA | | | ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE | | | PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF | | | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, | | | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER | | | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) | | | AND ANY PERFORMANCE BASED INFORMATION SUCH AS | | | PRE-ENGINEERED SYSTEMS. | | | | | | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH | | | EXIT SIGNS. | | | | | | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY | | | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING | | | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM | | | WWW.KNOXBOX.COM. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2018-03-21 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-03-21 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-03-21 |
Time |
11:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2018-01-08 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-01-08 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-01-08 |
Time |
10:06 |
Sent To |
|
|
| Notes |
| 2018-01-08 10:07:24 | 2ND REVIEW: FBC 2014 5TH EDITION | | | | | | GAS COMMENTS: | | | | | | 1. SHT. M-1 KEYNOTE #13 CALLS OUT A 4" CONCENTRIC VENT | | | PROVIDE DETAIL SHOW TYPE OF PIPE LENGTH AND | | | CONFIGURATION. PER WPB AMEND TO FBC 107.2.1 | | | | | | 2. SHT. M2 BOILER VENT DETAIL SHOWS 3 DIFFERENT | | | CONFIGURATION PLEASE PROVIDE A SITE SPECIFIC DRAWING | | | WITH PIPE TYPE, SIZING AND LENGTH. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 3. SHT. P-2 SHOW 2 DIFFERENT VENT CONFIGURATIONS PLEASE | | | PROVIDE A SITE SPECIFIC DRAWING WITH PIPE TYPE, SIZING | | | AND LENGTH. PER WPB AMEND TO FBC 107.2.1 | | | | | | 4. SHT. G-1 HEATER DETAIL SHOWS A DUAL PIPE INLET | | | OUTLET VENT CONFIGURATION SHT. P-2 SHOWS I SINGLE | | | CONCENTRIC VENT PLEASE CLARIFY. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 5. THE TANKLESS HEATER MANUFACTURE SPECIFICATION | | | INSTALLATION MANUAL IS NOT COMPLETE PLEASE PROVIDE | | | COMPLETE MANUAL. PER WPB AMEND TO FBC 107.2.1 | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2017-10-12 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-10-12 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-10-12 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2017-10-12 11:52:16 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | GAS COMMENTS: | | | | | | 1. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS FOR THE | | | BOILER AND ASSOCIATED EQUIPMENT, TANKLESS HEATERS AND | | | FLUE PIPING. PER WPB AMEND TO FBC 107.2.1 | | | | | | 2. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER | | | FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2. | | | | | | 3. THE PLUMBING PLAN SHOWS 2 TANKLESS WATER HEATERS THE | | | GAS RISER ONLY SHOWS 1 TANKLESS WATER HEATER PLEASE | | | CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 4. SHT. G-1 GAS RISER THE BRANCH PIPING FEEDING THE | | | TANKLESS WATER HEATERS IS UNDERSIZED FOR 2 HEATERS AS | | | SHOWN ON PLUMBING PLAN IT SHALL BE 2". PER FBC FG TABLE | | | 402.4(1) | | | | | | 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | | | 6. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014 | | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | | PSI. | | | | | | 7. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | | TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE | | | SEC. 502 THRU 505. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-03-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-03-21 |
Time |
17:04 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-02-22 |
Time |
13:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-01-08 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-01-08 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-12-01 |
Time |
09:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-10-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-09-15 |
Time |
15:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
P |
Date |
2018-03-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-03-17 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-03-17 |
Time |
16:24 |
Sent To |
|
|
| Notes |
| 2018-03-17 16:25:42 | MU2017-32602, MU2017-32605 | | | $124.33 RECEIPT PROVIDED | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2018-01-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-01-04 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-01-04 |
Time |
14:52 |
Sent To |
|
|
| Notes |
| 2018-01-04 14:54:40 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | MU2017-32602, MU2017-32605 6,312 SQUARE FEET | | | THE PLANS HAVE BEEN STAMPED BUT THE RECEIPT SHOWING | | | THAT FEES DUE WERE PAID WAS NOT PROVIDED. THIS MAY BE | | | SENT VIA EMAIL. | | | | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2017-10-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-10-05 |
Time |
12:45 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-10-05 |
Time |
12:45 |
Sent To |
|
|
| Notes |
| 2017-10-05 12:46:55 | AFTER ALL PLAN REVIEWS HAVE PASSED AND PLANS STAMPED | | | FOR ISSUANCE: | | | | | | IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED | | | THE PLAN ARE TO BE STAMPED AND THE RECEIPT SHOWING THAT | | | FEES DUE WERE PAID (IF APPLICABLE) IS TO BE PROVIDED | | | 561-233-5025 FOR MORE INFORMATION | | | | | | PLAN IS TO BE CLEAR AS TO PREVIOUS USE/OCCUPANCY | | | (PERMITTED AND INSPECTED) SO THEY CAN PERFORM AN | | | ACCURATE REVIEW. | | | | | | IT APPEARS THAT ADDITIONAL SQUARE FOOT AREA IS BEING | | | ADDED (CREATING A 2ND FLOOR). REVISE THE PLAN TO | | | CLARIFY EXISTING SF AREA, PROPOSED NEW. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2018-03-14 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-03-14 |
Time |
16:06 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-03-14 |
Time |
16:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2017-12-22 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-12-22 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-12-21 |
Time |
17:26 |
Sent To |
|
|
| Notes |
| 2017-12-22 11:24:51 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17090272 | | | 12/22/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE LS-1 PLAN IS MISSING FROM ONE OF THE RESUBMITTED | | | PLAN SETS. | | | | | | 2) SHEETS LS-1, M-1, & M-2: THE VENTILATION | | | CALCULATIONS BASED ON WAREHOUSE AND SALE AREA DO NOT | | | CLEARLY REPRESENT THE ACTUAL USES OF THE TENANT SPACE. | | | THE LS-1 IS INDICATING F-1 WHICH IS A FACTORY | | | OCCUPANCY, AND THE PLANS ARE INDICATING A BAR AND | | | TABLES FOR OCCUPANTS TO GATHER FOR SAMPLING OF THE RUM. | | | PLEASE REFER TO SECTION 403.3 AND TABLE 403.3 TO FIND | | | THE MOST SIMILAR OCCUPANCIES. UNDER WORK ROOMS THE | | | FACTORY OR DISTILLERY AREA WOULD BE MOST SIMILAR TO | | | MEAT PROCESSING- 51 PERSONS AT 15 CFM PER OCCUPANT= 765 | | | CFMS. THE BAR AREA MUST BE SEPARATELY CALCULATED FROM | | | THE SALES AREA (CALCULATED AT 15 PERSONS PER SQ. FT.) | | | BECAUSE BARS ARE CALCULATED AT 100 PERSONS PER SQ. FT. | | | PLEASE REVISE THE CALCULATIONS. | | | | | | 3) SHEET P3: SECOND REQUEST FOR THE MECHANICAL PLAN FOR | | | THE DISTILLERY. THE RESUBMITTED PLAN DOES NOT INCLUDE | | | THE STEAM PIPING FROM THE BOILER TO THE DISTILLERY | | | TANKS. | | | | | | 4) IN RESPONSE TO COMMENT #S 6A & 6C, THE ENGINEER OF | | | RECORD IS STATING THAT NO DATA SHEETS ARE AVAILABLE FOR | | | THE DISTILLERY TANKS AND THAT THE TANKS AND THE | | | PROCESSING EQUIPMENT ARE USED AND BEING RELOCATED TO | | | THE NEW FACILITY. PLEASE SEE SECTION 101.9.1 WPB | | | AMENDMENTS TO THE FBC. USED MATERIALS AND EQUIPMENT. | | | | | | "THE USE OF USED MATERIALS WHICH MEET THE REQUIREMENTS | | | OF THIS CODE FOR NEW MATERIALS IS PERMITTED. USED | | | EQUIPMENT AND DEVICES SHALL NOT BE REUSED UNLESS | | | APPROVED BY THE BUILDING OFFICIAL." | | | | | | THE DISTILLERY TANKS AND EQUIPMENT ARE NOT APPROVED AT | | | THIS TIME WITHOUT FURTHER EVIDENCE OF COMPLIANCE WITH | | | THE GOVERNING TESTING AGENCY FOR DISTILLERY TANKS AND | | | EQUIPMENT. DISTILLERY TANKS AND EQUIPMENT ARE NOT | | | SPECIFICALLY ADDRESSED IN THE MECHANICAL CODE, HOWEVER | | | IN ACCORDANCE WITH SECTION 1003.1 FBC-14 MECHANICAL: | | | | | | "ALL PRESSURE VESSELS SHALL BE IN ACCORDANCE WITH THE | | | ASME BOILER AND PRESSURE VESSEL CODE, SHALL BEAR THE | | | LABEL OF AN APPROVED AGENCY AND SHALL BE INSTALLED IN | | | ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS." | | | | | | PRESSURE VESSEL DEFINITION - SCOPE | | | | | | THESE SCOPES ARE BASED ASME CODE SEC VIII DIV 1 | | | THE VESSEL WITH MAXIMUM ALLOWABLE WORKING | | | PRESSURE(MAWP) HIGHER THAN 15 PSI | | | INSIDE DIAMETER TO BE HIGHER THAN 152 MM | | | NO PIPING OR PIPING COMPONENT | | | NO ROTATING OR RECIPROCATING EQUIPMENT | | | NOT WATER VESSEL UP TO 300PSI OR 210?F | | | NOT WITHIN THE SCOPE OF OTHER SECTIONS | | | ALSO FOR GAS FIRED DOUBLE SHELL HEAT EXCHANGERS < 50 | | | PSI | | | NOT STEAM BOILERS WITH DIRECT FIRING | | | NOT FOR HUMAN OCCUPANCY (PVHO) | | | | | | ADVISORY: PLEASE CONSULT WITH THE ALCOHOL AND TOBACCO | | | TAX AND TRADE BUREAU (TTB) FOR DISTILLERY TESTING AND | | | INSPECTION GUIDELINES. | | | | | | 5) THE SUBMITTED ENERGYGAUGE COMPLIANCE REPORT IS | | | INDICATING AHU-1 TO HAVE A DESIGN EFFICIENCY RATING OF | | | 12 EER, HOWEEVER THE EQUIPMEBNT SCHEDULE ON SHEET M-2 | | | INDICATES 11.2 EER. | | | | | | 6) THE REQUESTED ENGINEERING FOR INSTALLATION OF THE | | | CHILLER AS SHOWN ON SHEET S-15 IS INCOMPLETE. MISSING | | | FROM THE DETAIL IS THE WIND LOAD DESIGN CRITERIA PER | | | SECTION 1609 FBC-14 BUILDING, AND ALSO SPECIFICATIONS | | | AND DETAILS FROM THE CHILLER MANUFACTURER. PLEASE NOTE | | | THAT COMPLETE ENGINEERING MAY BE A DEFERRED SUBMITTAL | | | IF NECESSARY. | | | | | | 1) DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS. | | | FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS | | | ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE | | | NOT SUBMITTED AT THE TIME OF THE | | | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE | | | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL | | | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF | | | THE BUILDING OFFICIAL. THE REGISTERED DESIGN | | | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE | | | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR | | | REVIEW BY THE BUILDING OFFICIAL. | | | | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | 2) DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT | | | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE | | | DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-10-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-10-16 |
Time |
17:35 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-10-16 |
Time |
17:30 |
Sent To |
|
|
| Notes |
| 2017-10-16 17:56:39 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING, | | | ENERGY CONSERVATION CODES. | | | PERMIT #17090272 | | | 10/16/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) REFER TO SECTIONS C101.4.4 AND C101.4.5 FBC-14 | | | ENERGY CONSERVATION: THE PROPOSED PROJECT IS DETERMINED | | | TO BE A CHANGE OF OCCUPANCY AND ALSO A CHANGE IN SPACE | | | CONDITIONING WHICH REQUIRES FULL COMPLIANCE WITH THE | | | CURRENT ENERGY CODE. THE SUBMITTED FORM C402-2014 IS A | | | COMPLIANCE FORM USED FOR ALTERATIONS AND CANNOT BE USED | | | IN THIS CASE- SECTION C101.5.1.1. PLEASE | | | | | | SEE SECTION C401.2 AND SUBMIT AN ENERGY COMPLIANCE FORM | | | UTILIZING ONE OF THE METHODS DESCRIBED THERE. | | | | | | 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. CLARIFY IF VENTILATION | | | FOR THE BOILER ROOM AND THE MOLASSES TANK ROOM IS TO BE | | | PROVIDED, AND IN ACCORDANCE WITH WHICH CODE STANDARD | | | | | | OR BY MANUFACTURER'S SPECIFICATIONS. | | | | | | 3) CORRECT KEYNOTE 1 ON SHEET M-1 WHICH IS INDICATING | | | BATHROOM EXHAUST AT THE O/A INTAKE FOR THE RELOCATED 10 | | | TON AC SYSTEM. NOTE 1 IS ALSO INCORRECTLY SHOWN AT THE | | | COMBUSTION AIR OPENING FOR THE BOILER ROOM- PLEASE | | | CORRECT. REFER TO SECTION 401.4(2): THE LOCATION OF THE | | | O/A INTAKE APPEARS TO BE WITHIN 10' OF THE STREET- | | | PLEASE RELOCATE THE INLET. | | | | | | 4) AC SYSTEMS: A) NON-COMBUSTIBLE DOORS ARE REQUIRED | | | FOR THE SECOND FLOOR MECHANICAL ROOM AND THE STORAGE 2 | | | ROOM WHERE THE AIR HANDLERS ARE LOCATED- SEE SECTION | | | C403.2.7.2 FBC-14 ENERGY CONSERVATION AND SECTION 602 | | | FBC-14 MECHANICAL. B) PROVIDE CONDENSATE DISPOSAL | | | PLANS- SECTION 307. C) PROVIDE STRUCTURAL ENGINEERING | | | FOR INSTALLATION OF THE CONDENSER PADS AND | | | | | | ANCHORING DETAILS FOR MOUNTING THE CONDENSERS TO THE | | | PADS- SECTION 301.15. D) FLOOD HAZARD- SEE SECTION | | | 301.16: THE CONDENSERS SHALL BE INSTALLED AT OR ABOVE | | | THE ELEVATION REQUIRED BY SECTION 1612 FBC-14 BUILDING. | | | REFER ALSO TO BUILDING REVIEW COMMENTS REQUIRING A | | | SURVEY AND ELEVATION CERTIFICATES. | | | | | | 5) BOILER: A) PROVIDE COMBUSTION AIR CALCULATIONS AND | | | INDICATE HOW COMBUSTION AIR IS BEING PROVIDED PER | | | SECTION 304 FBC-14 FUEL GAS. B) PROVIDE A VENTING PLAN | | | INDICATING THE TYPE AND SIZE OF FLUE PIPE, LENGTH OF | | | THE VENT RUN, TERMINATION HEIGHT ABOVE THE ROOF, AND | | | CLEARANCE DISTANCES TO GRAVITY AND MECHANICAL AIR | | | INTAKES- SECTION 503 FBC-14 FUEL GAS. C) SUBMIT | | | MANUFACTURER'S | | | | | | SPECIFICATIONS FOR THE BOILER AND ALL ASSOCIATED | | | EQUIPMENT- SECTION 631. | | | | | | 6) PROVIDE A MECHANICAL PLAN FOR THE DISTILLERY | | | PROCESS: A) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR | | | THE CHILLER, AND ALL DISTILLERY TANKS AND EQUIPMENT | | | LISTED IN THE KEYNOTES ON S4- PN-32, 33, 34, 35, 36, | | | 37, 38, 39, 40, & 41. B) PROVIDE A CHILLED WATER PIPING | | | LAYOUT PLAN. C) PROVIDE TANK VENTING DETAILS. D) | | | PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF THE | | | CHILLER, AND VERIFY | | | | | | COMPLIANCE WITH FLOOD ELEVATION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
4 |
Status |
N |
Date |
2018-02-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-02-26 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-02-26 |
Time |
12:41 |
Sent To |
|
|
| Notes |
| 2018-02-26 12:42:20 | APPRAISAL PROVIDED, 3 YEAR CUMULATIVE IMPROVEMENTS | | | (INCLUDING PROPOSED IMPROVEMENTS) ARE 30% OF VALUE OF | | | STRUCTURE | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
3 |
Status |
F |
Date |
2018-02-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-02-14 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-02-14 |
Time |
16:00 |
Sent To |
|
|
| Notes |
| 2018-02-14 16:06:22 | ADDITIONAL INFORMATION IS REQUIRIED | | | SEE APPLICATION 18020610; THE 5 YEAR CUMULATIVE VALUE | | | WILL BE OVER 50% OF THE PROPERTY APPRAISER VALUATION. | | | | | | **SUBSTANTIAL IMPROVEMENT** | | | APPLICANT REDUCED SCOPE OF WORK (REMOVED MEZZANINE AND | | | STAIRS TO THE MEZZANINE). | | | PAPA 2017 VALUE OF STRUCTURE = $578,777 | | | VALUE OF WORK = $250,000 | | | CUMULATIVE 5 YEAR FOR PROPERTY; INCLUDING #18020610 | | | CURRENTLY IN APPLICATION IS $415,000 | | | | | | MAP 12099C0579F EFFECTIVE 10/05/2017, BFE 12.1 + 2' | | | FREEBOARD = 14.1' NAVD88 | | | PER ELEVATION CERTIFICATE DATED 8/23/17, FFE IS 14.09' | | | AND 14.54' NGVD29. | | | PER VERTCON (NOAA), 14.54 NGVD29 = 13.021 NAVD88 | | | IT APPEARS THAT THE STRUCTURE IS ABOVE BFE BUT DOES NOT | | | COMPLY WITH THE 2' FREEBOARD REQUIREMENT | | | | | | PLEASE CALL ME TO DISCUSS OPTIONS | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
P |
Date |
2018-01-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-01-04 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-01-04 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2018-01-04 14:20:18 | THIS PROJECT IS A "SUBSTANTIAL IMPROVEMENT" AS THE | | | VALUE OF THE IMPROVEMENT EXCEEDS 50% OF THE STRUCTURE | | | VALUE PER PALM BEACH COUNTY PROPERTY APPRAISER | | | ($310,000 PERMIT VALUE / $578,777 PAPA STRUCTURE | | | VALUE). AS THE BFE IS 13' NGVD29, LOCATED IN FLOOD ZONE | | | A9, PER FIRM PANEL 120229 0020B, WITH A 1' FREEBOARD | | | PER CITY OF WEST PALM BEACH MUNICIPAL CODE 94-546(B)(2) | | | DFE = 14' NGVD29 | | | | | | PROVISO; PRIOR TO CONCRETE POUR, A "BUILDING UNDER | | | CONSTRUCTION" ELEVATION CERTIFICATE OR FORM BOARD | | | SURVEY WITH ELEVATIONS WILL BE REQUIRED. PRIOR TO FINAL | | | INSPECTION, A "FINISHED CONSTRUCTION" ORIGINAL SIGNED | | | AND SEALED ELEVATION CERTIFICATE, WITH COLOR | | | PHOTOGRAPHS OF ALL SIDES OF THE STRUCTURE AND EXTERIOR | | | MECHANICAL EQUIPMENT (WITH TIE DOWNS VISIBLE IN PHOTOS) | | | WILL BE REQUIRED. SUBMIT THE "FINISHED CONSTRUCTION" | | | ELEVATION CERTIFICATE AT THE BUILDING DIVISION AS A | | | SUBMITTAL (NO FEE) FOR REVIEW WHEN AVAILABLE. | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2017-10-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-10-04 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-10-04 |
Time |
16:36 |
Sent To |
|
|
| Notes |
| 2017-10-04 16:36:39 | SEE BUILDING REVIEW | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2018-03-21 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-03-21 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-03-21 |
Time |
08:18 |
Sent To |
|
|
| Notes |
| 2018-03-26 11:17:30 | PROVISO COMPLIED SANITARY ISOMETRIC HAS BEEN APPROVED | | | 3/26/18/GPJ | | 2018-03-21 15:12:55 | | | | PLUMBING PROVISO: | | | | | | SHALL BE COMPLIED WITH BEFORE 1ST ROUGH INSPECTION. | | | | | | 1. PROVIDE AN APPROVED SANITARY ISOMETRIC DRAWING SHALL | | | BE APPROVED BY PLUMBING PLANS EXAMINER PRIOR TO | | | SCHEDULING INSPECTIONS. | | | PER FRANK SPENCER FROM DKK CONSULTING | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2018-01-08 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-01-08 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-01-08 |
Time |
08:22 |
Sent To |
|
|
| Notes |
| 2018-01-08 09:27:24 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED | | | | | | PARTIALLY COMPLIED 3. SHT. P-3 SANITARY ISOMETRIC | | | DRAWING THE FLOOR DRAINS ARE NOT VENTED THEY SHALL | | | COMPLY WITH FBC PL 901.2.1 THE VENTS THAT WERE ADDED | | | APPEAR TO BE HORIZONTAL DRY VENTS WHICH ARE NON CODE | | | COMPLIANT, ALL DRY VENTS SHALL CONNECT TO THE | | | HORIZONTAL DRAIN ABOVE THE CENTERLINE OF THE PIPE AND | | | RUN VERTICAL TO A POINT ABOVE THE FLOOD LEVEL RIM OF | | | THE FIXTURES. FOR CLARIFICATION VENTS SHOULD CONNECT TO | | | THE HORIZONTAL DRAIN AT A LOCATION WERE THEY CAN RUN UP | | | INTO A VERTICAL WALL THEY CAN NOT CONNECT IN THE MIDDLE | | | OF THE FLOOR. PER FBC PL 905.3 AND 905.4 | | | | | | PARTIALLY COMPLIED 4. SHT. P-3 SANITARY ISOMETRIC | | | DRAWING THE EYE WASH IS NOT VENTED IT SHALL COMPLY WITH | | | FBC PL 901.2.1 THE VENTS THAT WERE ADDED APPEAR TO BE | | | HORIZONTAL DRY VENTS WHICH ARE NON CODE COMPLIANT, ALL | | | DRY VENTS SHALL CONNECT TO THE HORIZONTAL DRAIN ABOVE | | | THE CENTERLINE OF THE PIPE AND RUN VERTICAL TO A POINT | | | ABOVE THE FLOOD LEVEL RIM OF THE FIXTURES. FOR | | | CLARIFICATION VENTS SHOULD CONNECT TO THE HORIZONTAL | | | DRAIN AT A LOCATION WERE THEY CAN RUN UP INTO A | | | VERTICAL WALL THEY CAN NOT CONNECT IN THE MIDDLE OF THE | | | FLOOR. PER FBC PL 905.3 AND 905.4 | | | | | | PARTIALLY COMPLIED 9. PLEASE SHOW COMPLIANCE WITH FBC | | | PL 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING | | | FACILITIES. | | | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND | | | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES | | | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED | | | WATER SHALL BE DELIVERED THROUGH AN APPROVED | | | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE | | | 1070 OR CSA B125.3. TEMPERED WATER IS ONLY REQUIRED AT | | | HAND WASHING LAVATORY,S IN THE BATHROOMS THE | | | TEMPERATURE LIMITING DEVICE SHALL ONLY CONNECT THESE | | | LAVATORY,S THE OTHER SINKS USED FOR CLEANING UTENSILS, | | | EQUIPMENT AND THE FACULTY THEY SHALL BE SUPPLIED WITH | | | HOT WATER WITH A TEMPERATURE ABOVE 110 DEQ. PER FBC PL | | | 607.1 | | | | | | 10. PLEASE SHOW COMPLIANCE WITH FBC PL 606.1 LOCATION | | | OF FULL-OPEN VALVES. | | | FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING | | | LOCATIONS: 5. ON THE TOP OF EVERY WATER DOWN-FEED PIPE | | | IN OCCUPANCIES OTHER THAN ONE- AND TWO-FAMILY | | | RESIDENTIAL OCCUPANCIES. | | | | | | 11. PLEASE SHOW COMPLIANCE WITH FBC PL 607.2 HOT OR | | | TEMPERED WATER SUPPLY TO FIXTURES. | | | THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING, | | | FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT | | | REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET | | | (15 240 MM). RECIRCULATING SYSTEM PIPING AND | | | HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF | | | HOT OR TEMPERED WATER. | | | [E] 607.5 PIPE INSULATION. | | | HOT WATER PIPING IN AUTOMATIC TEMPERATURE MAINTENANCE | | | SYSTEMS SHALL BE INSULATED WITH 1 INCH (25 MM) OF | | | INSULATION HAVING A CONDUCTIVITY NOT EXCEEDING 0.27 BTU | | | PER INCH/H ? FT2 ? ?F (1.53 W PER 25 MM/M2 ? K). THE | | | FIRST 8 FEET (2438 MM) OF HOT WATER PIPING FROM A HOT | | | WATER SOURCE THAT DOES NOT HAVE HEAT TRAPS SHALL BE | | | INSULATED WITH 0.5 INCH (12.7 MM) OF MATERIAL HAVING A | | | CONDUCTIVITY NOT EXCEEDING 0.27 BTU PER INCH/H ? FT2 ? | | | ?F (1.53 W PER 25 MM/ M2 ? K). FOR CLARIFICATION ANY | | | FIXTURE OVER 50' FROM THE WATER HEATER ARE REQUIRED TO | | | BE ON A HOT WATER RECIRCULATING SYSTEM. PER FBC PL | | | 607.2 | | | | | | 12. PLEASE SHOW COMPLIANCE WITH FBC PL 604.9 WATER | | | HAMMER. | | | THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM | | | SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER | | | HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED | | | WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER | | | ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE | | | MANUFACTURER?S INSTRUCTIONS. WATER-HAMMER ARRESTORS | | | SHALL CONFORM TO ASSE 1010. PLEASE SHOW WATER-HAMMER | | | ARRESTORS ON WATER RISER. | | | | | | 13. ANY EQUIPMENT CONNECTED TO THE POTABLE WATER SYSTEM | | | SHALL HAVE A BACK FLOW ON IT PLEASE SHOW ON WATER | | | RISER. FBC PL 608.3 . | | | | | | 14. PLEASE PROVIDE A RISER DIAGRAM FOR PROCESS PIPING | | | AND STEAM PIPING. PER WPB AMEND TO FBC 107.3.5.1.3(13) | | | FLAT DRAWINGS DO NOT COMPLY WITH THIS REQUIREMENT | | | PLEASE PROVIDE PIPE SIZING AND THE TYPE OF PIPE ON THE | | | RISER. | | | | | | NEW COMMENTS: | | | | | | 1. PLEASE SEPARATE THE SANITARY AND THE WATER ISOMETRIC | | | DRAWING WITH THEM TOGETHER IT IS EXTREMELY DIFFICULT TO | | | DETERMINE IF THEY ARE CODE COMPLIANT AND WILL NOT SCAN | | | PROPERLY FOR OUR RECORD KEEPING. PER WPB AMEND TO FBC | | | 107.2.1.4 | | | | | | 2. PLEASE SHOW PIPE SIZING, VALVES, AND ANY OTHER | | | DEVICES ON THE WATER ISOMETRIC. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 3. TRAP PRIMERS ARE REQUIRED ON ALL FLOOR DRAINS TRENCH | | | DRAIN AND FLOOR SINKS PLEASE SHOW IN THE ISO DRAWING. | | | PER FBC PL 1002.4 | | | | | | SHALL COMPLY WITH MECHANICAL COMMENTS: | | | 3) SHEET P3: SECOND REQUEST FOR THE MECHANICAL PLAN FOR | | | THE DISTILLERY. THE RESUBMITTED PLAN DOES NOT INCLUDE | | | THE STEAM PIPING FROM THE BOILER TO THE DISTILLERY | | | TANKS. | | | | | | 4) IN RESPONSE TO COMMENT #S 6A & 6C, THE ENGINEER OF | | | RECORD IS STATING THAT NO DATA SHEETS ARE AVAILABLE FOR | | | THE DISTILLERY TANKS AND THAT THE TANKS AND THE | | | PROCESSING EQUIPMENT ARE USED AND BEING RELOCATED TO | | | THE NEW FACILITY. PLEASE SEE SECTION 101.9.1 WPB | | | AMENDMENTS TO THE FBC. USED MATERIALS AND EQUIPMENT. | | | | | | "THE USE OF USED MATERIALS WHICH MEET THE REQUIREMENTS | | | OF THIS CODE FOR NEW MATERIALS IS PERMITTED. USED | | | EQUIPMENT AND DEVICES SHALL NOT BE REUSED UNLESS | | | APPROVED BY THE BUILDING OFFICIAL." | | | | | | THE DISTILLERY TANKS AND EQUIPMENT ARE NOT APPROVED AT | | | THIS TIME WITHOUT FURTHER EVIDENCE OF COMPLIANCE WITH | | | THE GOVERNING TESTING AGENCY FOR DISTILLERY TANKS AND | | | EQUIPMENT. DISTILLERY TANKS AND EQUIPMENT ARE NOT | | | SPECIFICALLY ADDRESSED IN THE MECHANICAL CODE, HOWEVER | | | IN ACCORDANCE WITH SECTION 1003.1 FBC-14 MECHANICAL: | | | | | | "ALL PRESSURE VESSELS SHALL BE IN ACCORDANCE WITH THE | | | ASME BOILER AND PRESSURE VESSEL CODE, SHALL BEAR THE | | | LABEL OF AN APPROVED AGENCY AND SHALL BE INSTALLED IN | | | ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS." | | | | | | PRESSURE VESSEL DEFINITION - SCOPE | | | | | | THESE SCOPES ARE BASED ASME CODE SEC VIII DIV 1 | | | THE VESSEL WITH MAXIMUM ALLOWABLE WORKING | | | PRESSURE(MAWP) HIGHER THAN 15 PSI | | | INSIDE DIAMETER TO BE HIGHER THAN 152 MM | | | NO PIPING OR PIPING COMPONENT | | | NO ROTATING OR RECIPROCATING EQUIPMENT | | | NOT WATER VESSEL UP TO 300PSI OR 210?F | | | NOT WITHIN THE SCOPE OF OTHER SECTIONS | | | ALSO FOR GAS FIRED DOUBLE SHELL HEAT EXCHANGERS < 50 | | | PSI | | | NOT STEAM BOILERS WITH DIRECT FIRING | | | NOT FOR HUMAN OCCUPANCY (PVHO) | | | | | | ADVISORY: PLEASE CONSULT WITH THE ALCOHOL AND TOBACCO | | | TAX AND TRADE BUREAU (TTB) FOR DISTILLERY TESTING AND | | | INSPECTION GUIDELINES. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-10-12 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-10-12 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-10-11 |
Time |
15:29 |
Sent To |
|
|
| Notes |
| 2017-10-12 11:30:47 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. SHT. S-15 FLUSH CONTROLS SHALL COMPLY WITH FBC ACC | | | 604.6 FLUSH CONTROLS. | | | FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE | | | WATER CLOSET. | | | | | | 2. SHT.S-2 DN -23 AND THE PLUMBING SHEETS PLEASE | | | CLARIFY WILL THE EXISTING STORM WATER SYSTEM REMAIN THE | | | SAME PROVIDE NOTE ON PLAN. PER WPB AMEND TO FBC 107.2.1 | | | | | | 3. SHT. P-3 SANITARY ISOMETRIC DRAWING THE FLOOR DRAINS | | | ARE NOT VENTED THEY SHALL COMPLY WITH FBC PL 901.2.1 | | | | | | 4. SHT. P-3 SANITARY ISOMETRIC DRAWING THE EYE WASH IS | | | NOT VENTED IT SHALL COMPLY WITH FBC PL 901.2.1 | | | | | | 5. SHT. P-3 SANITARY ISOMETRIC DRAWING THE VENTS FOR | | | THE LAVATORY AND WATER CLOSET IN THE HANDICAP STALL OF | | | WOMENS BATHROOM SHALL EXTEND THROUGH 2ND FLOOR AND | | | REVENT ABOVE THE FLOOD LEVEL RIM OF THE FIXTURES ON THE | | | 2ND FLOOR. PER FBC PL 905.5 | | | | | | 6. SHT. P-3 SANITARY ISOMETRIC DRAWING THE SOIL STACK | | | FROM 2ND FLOOR SHALL CONNECT TO THE BUILDING BRANCH | | | DRAIN DOWN STREAM OF THE WATER CLOSET. PER FBC PL 912.1 | | | | | | 7.SHT. P-3 SANITARY ISOMETRIC DRAWING A CLEANOUT SHALL | | | BE PROVIDED AT THE BASE OF EACH WASTE OR SOIL STACK. | | | PER FBC PL 708.3.4 | | | | | | 8. PLEASE PROVIDE A DOMESTIC WATER ISOMETRIC DRAWING. | | | PER WPB AMEND TO FBC 107.3.5.1.3(13) | | | | | | 9. PLEASE SHOW COMPLIANCE WITH FBC PL 416.5 TEMPERED | | | WATER FOR PUBLIC HAND-WASHING FACILITIES. | | | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND | | | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES | | | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED | | | WATER SHALL BE DELIVERED THROUGH AN APPROVED | | | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE | | | 1070 OR CSA B125.3. | | | | | | 10. PLEASE SHOW COMPLIANCE WITH FBC PL 606.1 LOCATION | | | OF FULL-OPEN VALVES. | | | FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING | | | LOCATIONS: 5. ON THE TOP OF EVERY WATER DOWN-FEED PIPE | | | IN OCCUPANCIES OTHER THAN ONE- AND TWO-FAMILY | | | RESIDENTIAL OCCUPANCIES. | | | | | | 11. PLEASE SHOW COMPLIANCE WITH FBC PL 607.2 HOT OR | | | TEMPERED WATER SUPPLY TO FIXTURES. | | | THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING, | | | FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT | | | REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET | | | (15 240 MM). RECIRCULATING SYSTEM PIPING AND | | | HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF | | | HOT OR TEMPERED WATER. | | | [E] 607.5 PIPE INSULATION. | | | HOT WATER PIPING IN AUTOMATIC TEMPERATURE MAINTENANCE | | | SYSTEMS SHALL BE INSULATED WITH 1 INCH (25 MM) OF | | | INSULATION HAVING A CONDUCTIVITY NOT EXCEEDING 0.27 BTU | | | PER INCH/H ? FT2 ? ?F (1.53 W PER 25 MM/M2 ? K). THE | | | FIRST 8 FEET (2438 MM) OF HOT WATER PIPING FROM A HOT | | | WATER SOURCE THAT DOES NOT HAVE HEAT TRAPS SHALL BE | | | INSULATED WITH 0.5 INCH (12.7 MM) OF MATERIAL HAVING A | | | CONDUCTIVITY NOT EXCEEDING 0.27 BTU PER INCH/H ? FT2 ? | | | ?F (1.53 W PER 25 MM/ M2 ? K). | | | | | | 12. PLEASE SHOW COMPLIANCE WITH FBC PL 604.9 WATER | | | HAMMER. | | | THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM | | | SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER | | | HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED | | | WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER | | | ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE | | | MANUFACTURER?S INSTRUCTIONS. WATER-HAMMER ARRESTORS | | | SHALL CONFORM TO ASSE 1010. | | | | | | 13. PLEASE SHOW COMPLIANCE WITH FBC PL 608.3 DEVICES, | | | APPURTENANCES, APPLIANCES AND APPARATUS. | | | DEVICES, APPURTENANCES, APPLIANCES AND APPARATUS | | | INTENDED TO SERVE SOME SPECIAL FUNCTION, SUCH AS | | | STERILIZATION, DISTILLATION, PROCESSING, COOLING, OR | | | STORAGE OF ICE OR FOODS, AND THAT CONNECT TO THE WATER | | | SUPPLY SYSTEM, SHALL BE PROVIDED WITH PROTECTION | | | AGAINST BACKFLOW AND CONTAMINATION OF THE WATER SUPPLY | | | SYSTEM. WATER PUMPS, FILTERS, SOFTENERS, TANKS AND | | | OTHER APPLIANCES AND DEVICES THAT HANDLE OR TREAT | | | POTABLE WATER SHALL BE PROTECTED AGAINST CONTAMINATION. | | | | | | 14. PLEASE PROVIDE A RISER DIAGRAM FOR PROCESS PIPING | | | AND STEAM PIPING. PER WPB AMEND TO FBC 107.3.5.1.3(13) | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2018-03-02 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2018-03-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2018-03-01 |
Time |
17:27 |
Sent To |
|
|
| Notes |
| 2018-03-02 11:25:10 | ZONING PROVISO: | | | | | | 1.) SEPARATE PERMITS AND REVIEWS REQUIRED FOR: DUMPSTER | | | ENCLOSURE IF TRASH IS GOING TO BE STORED OUTSIDE RATHER | | | THAN INSIDE THE BUILDING. | | | | | | | | | NOTES: | | | | | | * ZONE: I | | | | | | * USE CATEGORY: "WHOLESALING HAVING SIGNIFICANT | | | EXTERNAL IMPACT (DISTILLED ALCOHOLIC BEVERAGES, | | | WHOLESALE TRADE, ETC.)" | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2017-12-21 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2017-12-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2017-12-21 |
Time |
|
Sent To |
|
|
| Notes |
| 2017-12-21 16:40:13 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) FLOOR PLAN AND SITE PLAN MUST DEMONSTRATE THAT THE | | | DISTILLERY COMPONENT IS GREATER THAN 65 PERCENT OF THE | | | OVERALL SQUARE FOOTAGE OF THE FACILITY IN ORDER TO | | | LOCATE AT THE SUBJECT LOCATION. PLEASE PROVIDE | | | CALCULATIONS. [REPEAT COMMENT FROM 9/26/2017] | | | | | | 2.) CALCULATIONS, INCLUDING BUT NOT LIMITED TO THE | | | EXISTING AND PROPOSED: LOT COVERAGE, IMPERVIOUS | | | SURFACE, FLOOR AREA RATIO, ETC., MUST BE PROVIDED IN | | | THE SITE PLAN TO DEMONSTRATE COMPLIANCE WITH THE | | | DEVELOPMENT REQUIREMENTS OF THE INDUSTRIAL (I) ZONING | | | DISTRICT. | | | | | | 3.) PLEASE ENSURE ALL PLANS WITHIN THE PERMIT SET HAVE | | | BEEN MODIFIED TO MATCH. SOME SHEETS (I.E. SHEET G-1) | | | STILL SHOWS THAT CATWALK THAT WAS REMOVED IN THE LATEST | | | REVISION. | | | | | | | | | NOTES: | | | | | | * ZONE: I | | | | | | * USE CATEGORY: "WHOLESALING HAVING SIGNIFICANT | | | EXTERNAL IMPACT (DISTILLED ALCOHOLIC BEVERAGES, | | | WHOLESALE TRADE, ETC.)" | | | | | | * PER CHAPTER 6, "MICRO-DISTILLERIES" EXEMPTED FROM THE | | | DISTANCE REQUIREMENTS, PROVIDED > 65 PERCENT OF THE SF | | | OF THE FACILITY SHALL BE DEDICATED TO THE BREWERY | | | FUNCTION. | | | | | | * VALUE OF CONSTRUCTION MODIFIED TO $250,000, WHICH | | | DOES NOT EXCEED 50% OF THE STRUCTURE?S VALUE. | | | | | | * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2017-09-26 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2017-09-26 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2017-09-26 |
Time |
|
Sent To |
|
|
| Notes |
| 2017-09-26 15:15:42 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) AN UPDATED SURVEY OF THE PROPERTY IS REQUIRED. | | | | | | 2.) PLANS INDICATE ADDITIONAL SQUARE FOOTAGE WILL BE | | | ADDED TO THE EXISTING BUILDING. HOW MUCH SQUARE FOOTAGE | | | IS BEING ADDED? PLEASE NOTE THAT ADDITIONS GREATER THAN | | | 1,000 SQ. FT. (INCLUDING MEZZANINE/CATWALK AREA) WILL | | | REQUIRE AN INFORMAL SITE PLAN REVIEW THROUGH THE | | | PLANNING DIVISION PRIOR TO BUILDING PERMIT. | | | | | | 3.) PROVIDE A SITE PLAN OF THE PROPERTY. BUILDING | | | SETBACK DIMENSIONS TO THE NEW BUILDING ADDITION AND NEW | | | STRUCTURES ON THE PROPERTY WILL BE REQUIRED ON THE SITE | | | PLAN. | | | | | | 4.) THE VALUE OF THE CONSTRUCTION ($310,000.00) EXCEEDS | | | 50% OF THE STRUCTURE'S VALUE ($578,777.00) ACCORDING TO | | | THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, | | | PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE | | | SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE | | | REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE | | | SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A | | | LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE | | | INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES | | | NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING | | | APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND | | | IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL | | | TO BRING THE SITE INTO CONFORMITY. | | | | | | 5.) FLOOR PLAN MUST DEMONSTRATE THAT THE DISTILLERY | | | COMPONENT IS GREATER THAN 65 PERCENT OF THE OVERALL | | | SQUARE FOOTAGE OF THE FACILITY IN ORDER TO LOCATE AT | | | THE SUBJECT LOCATION. PLEASE PROVIDE CALCULATIONS. | | | | | | 6.) SHOW ALL DIMENSIONS IN THE PROPOSED ELEVATIONS. | | | | | | | | | NOTES: | | | | | | * ZONE: I | | | | | | * USE CATEGORY: "WHOLESALING HAVING SIGNIFICANT | | | EXTERNAL IMPACT (DISTILLED ALCOHOLIC BEVERAGES, | | | WHOLESALE TRADE, ETC.)" | | | | | | * PER CHAPTER 6, "MICRO-DISTILLERIES" EXEMPTED FROM THE | | | DISTANCE REQUIREMENTS, PROVIDED > 65 PERCENT OF THE SF | | | OF THE FACILITY SHALL BE DEDICATED TO THE BREWERY | | | FUNCTION. | | | | | | * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | |
|
|
|