Plan Review Details - Permit 17090219
| Plan Review Stops For Permit 17090219 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2017-10-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-10-16 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-10-16 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2017-10-16 13:45:30 | PROVISO | | | ARCHITECT TO PROVIDE A LETTER WHICH STATES THAT | | | NON-RELIGIOUS ENTITIES WILL NOT RENT FACILITY | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2017-10-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-10-13 |
Time |
17:11 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-10-13 |
Time |
17:11 |
Sent To |
|
|
| Notes |
| 2017-10-13 17:17:11 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | FROM PREVIOUS LIST: | | | | | | 1. OK | | | | | | 2. IF EXEMPT (FROM ACCESSIBILITY), PROVIDE INFORMATION | | | REGARDING EXEMPTION. IT IS SUGGESTED THAT YOU SEND THE | | | PROPOSED LANGUAGE TO ME VIA EMAIL PRIOR TO RESUBMITTAL. | | | THE JUSTIFICATION FOR EXEMPTION MAY BE MADE EITHER BY | | | DESIGN PROFESSIONAL ON THE PLAN OR IN THE FORM OF A | | | LETTER FROM THE CHURCH ON LETTERHEAD. CONTACT ME IF YOU | | | WISH TO DISCUSS. | | | | | | PLAN WAS NOT REVISED TO INCLUDE INFORMATION. PLEASE | | | PROVIDE A SIGNED AND SEALED LETTER STATING THAT THE | | | FACILITY IS NOT RENTED TO NON-RELIGIOUS ENTITIES. | | | | | | 3. PURPOSE OF THE "WORK ALCOVE" IS NOT CLEAR (SHEET | | | A1.0 "NEW WORK NOTES"). "WORK AREAS" ARE GENERALLY | | | EXEMPT, BUT THE NATURE OF THE "WORK AREAS" IS NOT | | | CLEAR, REVISE PLAN TO CLARIFY. | | | | | | THIS WAS ADDRESSED IN A RESPONSE LETTER, BUT PLAN WAS | | | NOT REVISED. RESPONSE LETTERS ARE NOT RETAINED AS A | | | PART OF THE PERMIT RECORD. THIS MAY ALSO BE DESCRIBED | | | IN THE LETTER ADDRESSING ITEM #2. | | | | | | 4. OK | | | | | | 5. PLAN REFERS TO "REMOVED WINDOWS"; SHOULDN'T THIS BE | | | "PROPOSED" WORK? FBC 107. | | | | | | NOT REVISED; SHALL I REDLINE THIS TO READ "REMOVE" | | | WINDOWS RATHER THAN "REMOVED"? OR HAS THIS WORK BEEN | | | DONE UNDER ANOTHER PERMIT? | | | | | | 6. FBC 107, FBC B CHAPTER 3, REVISE PLAN TO INCLUDE | | | OCCUPANCY CLASSIFICATION. | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2017-09-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-09-27 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-09-27 |
Time |
07:20 |
Sent To |
|
|
| Notes |
| 2017-09-27 07:55:46 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. SHEET A0.1, FBC EB 504, THIS IS A LEVEL TWO | | | ALTERATION (NOT LEVEL ONE), REVISE PLAN. | | | | | | 2. IT IS NOT CLEAR IF FBC ACCESSIBILITY APPLIES, SEE | | | FBC A 106. A CHURCH WHICH IS NOT A PLACE OF PUBLIC | | | ACCOMMODATION IS EXEMPT. HOWEVER, IF THE PREMISES ARE | | | RENTED OUT FOR FUNCTIONS (WEDDINGS, CONFERENCES, ETC.), | | | IT IS POSSIBLE THAT THE FACILITY IS CONSIDERED A PLACE | | | OF PUBLIC ACCOMMODATION AND SUBJECT TO THE REQUIREMENTS | | | OF FBC ACCESSIBILITY. | | | | | | IF EXEMPT, PROVIDE INFORMATION REGARDING EXEMPTION. IT | | | IS SUGGESTED THAT YOU SEND THE PROPOSED LANGUAGE TO ME | | | VIA EMAIL PRIOR TO RESUBMITTAL. THE JUSTIFICATION FOR | | | EXEMPTION MAY BE MADE EITHER BY DESIGN PROFESSIONAL ON | | | THE PLAN OR IN THE FORM OF A LETTER FROM THE CHURCH ON | | | LETTERHEAD. CONTACT ME IF YOU WISH TO DISCUSS. | | | | | | 3. PURPOSE OF THE "WORK ALCOVE" IS NOT CLEAR (SHEET | | | A1.0 "NEW WORK NOTES"). "WORK AREAS" ARE GENERALLY | | | EXEMPT, BUT THE NATURE OF THE "WORK AREAS" IS NOT | | | CLEAR, REVISE PLAN TO CLARIFY. | | | | | | 4. VALUE APPEARS LOW, FBC 109. IF SUBJECT TO | | | ACCESSIBILITY, ACCESSIBLE ROUTE TO THE ALTERED AREA | | | (PULPIT) MAY BE REQUIRED, FBC A 202.3. A COST BREAKDOWN | | | MAY BE REQUIRED IN THE EVENT OF DISPROPORTIONATE COST. | | | NOT ENOUGH INFORMATION ON THE PLAN TO DETERMINE CODE | | | COMPLIANCE. | | | | | | 5. PLAN REFERS TO "REMOVED WINDOWS"; SHOULDN'T THIS BE | | | "PROPOSED" WORK? FBC 107. | | | | | | 6. FBC 107, FBC B CHAPTER 3, REVISE PLAN TO INCLUDE | | | OCCUPANCY CLASSIFICATION. | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-10-17 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-10-17 |
Time |
07:39 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-10-17 |
Time |
07:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2017-09-27 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-09-27 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-09-27 |
Time |
08:48 |
Sent To |
|
|
| Notes |
| 2017-09-27 08:48:42 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND | | | SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE | | | ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H); | | | 471.025; FBC 107.2.1, 107.3.5 | | | 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | | WITH CODE. NEC 210.8, 210.12, 215.2, 215.5, 408.4 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-10-13 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-10-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-10-13 |
Time |
09:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2017-09-15 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-09-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-09-15 |
Time |
12:03 |
Sent To |
|
|
| Notes |
| 2017-09-15 13:05:02 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET A 0.1 - THERE IS NO INDICATION OF REVIEW OR | | | DESIGN WITH ANY FIRE CODE. | | | | | | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE | | | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING | | | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER | | | APPLICABLE CODES OR STANDARDS. | | | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS | | | OF NFPA 13, 2010 EDITION. | | | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | | NFPA 72, 2010 EDITION. | | | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | | NFPA 241, 2009 EDITION. | | | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS | | | OF NFPA 10, 2010 EDITION. | | | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. | | | | | | PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE A | | | INDICATING NOTE. | | | | | | | | | | | | 2) SHEET A 0.1 - THERE IS NO REFERNCE TO THE EXISTING | | | OCCUPANCY TYPE AND IF THERE IS AN EXISTING FIRE | | | SPRINKLER OR FIRE ALARM SYSTEM. | | | | | | PLEASE INDICATE THE OCCUPANCY TYPE AND ANY EXISTING | | | FIRE SPRINKLER AND/OR FIRE ALARM SYSTEM. | | | | | | | | | | | | 3) SHEET A 1.0 - THE PROPOSED PROJECT REMOVES WALLS AND | | | INSTALLS NEW WALLS THAT MAY AFFECT THE THE EXISTING | | | FIRE SPRINKLER COVERAGE AND FIRE ALARM SYSTEM DEVICES | | | AND FUNCTION. | | | | | | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | | CONSTRUCTION PERIOD. | | | | | | ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE | | | ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP | | | DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | PLEASE PROVIDE THE APPLICABLE NOTE. | | | | | | | | | | | | 4) SHEET A 1.1 - NOTE 23 INDICATES ELECTRICAL WORK, | | | WIRING AND EQUIPEMNT; HOWEVER, THERE IS NO ELECTRICAL | | | DRAWING SHEET. | | | | | | PLEASE PROVIDE AN ELECTRICAL DRAWING SHEET SHOWING THE | | | ELECTRIC SERVICE PANEL INFORMATION AND ALL APPLICABLE | | | WIRING ROUTES AND EQUIPMENT LOCATIONS. | | | | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-10-17 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-10-17 |
Time |
07:39 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-10-11 |
Time |
14:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-09-27 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-09-27 |
Time |
12:14 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-09-13 |
Time |
15:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2017-10-16 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-10-16 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-10-16 |
Time |
11:33 |
Sent To |
|
|
| Notes |
| 2017-10-16 11:34:09 | NO PLUMBING UNDER THIS PERMIT. | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-09-27 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-09-27 |
Time |
12:07 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-09-27 |
Time |
12:07 |
Sent To |
|
|
| Notes |
| 2017-09-27 12:14:25 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. WHAT ARE THE NEW WATER AND SANITARY LINES SERVING | | | SHOW FIXTURES ON FLOOR PLAN. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 2. PROVIDE A WATER AND SANITARY ISOMETRIC DRAWING | | | SHOWING NEW WORK. WPB AMEND TO FBC 107.3.5.1.3(13) | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
|