Plan Review Details - Permit 17090219
Plan Review Stops For Permit 17090219
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-10-16 Cont ID  
Sent By shill Date 2017-10-16 Time 13:44 Rev Time 0.00
Received By shill Date 2017-10-16 Time 13:44 Sent To  
Notes
2017-10-16 13:45:30PROVISO
 ARCHITECT TO PROVIDE A LETTER WHICH STATES THAT
 NON-RELIGIOUS ENTITIES WILL NOT RENT FACILITY
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-10-13 Cont ID  
Sent By shill Date 2017-10-13 Time 17:11 Rev Time 0.00
Received By shill Date 2017-10-13 Time 17:11 Sent To  
Notes
2017-10-13 17:17:11****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FROM PREVIOUS LIST:
  
 1. OK
  
 2. IF EXEMPT (FROM ACCESSIBILITY), PROVIDE INFORMATION
 REGARDING EXEMPTION. IT IS SUGGESTED THAT YOU SEND THE
 PROPOSED LANGUAGE TO ME VIA EMAIL PRIOR TO RESUBMITTAL.
 THE JUSTIFICATION FOR EXEMPTION MAY BE MADE EITHER BY
 DESIGN PROFESSIONAL ON THE PLAN OR IN THE FORM OF A
 LETTER FROM THE CHURCH ON LETTERHEAD. CONTACT ME IF YOU
 WISH TO DISCUSS.
  
 PLAN WAS NOT REVISED TO INCLUDE INFORMATION. PLEASE
 PROVIDE A SIGNED AND SEALED LETTER STATING THAT THE
 FACILITY IS NOT RENTED TO NON-RELIGIOUS ENTITIES.
  
 3. PURPOSE OF THE "WORK ALCOVE" IS NOT CLEAR (SHEET
 A1.0 "NEW WORK NOTES"). "WORK AREAS" ARE GENERALLY
 EXEMPT, BUT THE NATURE OF THE "WORK AREAS" IS NOT
 CLEAR, REVISE PLAN TO CLARIFY.
  
 THIS WAS ADDRESSED IN A RESPONSE LETTER, BUT PLAN WAS
 NOT REVISED. RESPONSE LETTERS ARE NOT RETAINED AS A
 PART OF THE PERMIT RECORD. THIS MAY ALSO BE DESCRIBED
 IN THE LETTER ADDRESSING ITEM #2.
  
 4. OK
  
 5. PLAN REFERS TO "REMOVED WINDOWS"; SHOULDN'T THIS BE
 "PROPOSED" WORK? FBC 107.
  
 NOT REVISED; SHALL I REDLINE THIS TO READ "REMOVE"
 WINDOWS RATHER THAN "REMOVED"? OR HAS THIS WORK BEEN
 DONE UNDER ANOTHER PERMIT?
  
 6. FBC 107, FBC B CHAPTER 3, REVISE PLAN TO INCLUDE
 OCCUPANCY CLASSIFICATION.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-09-27 Cont ID  
Sent By shill Date 2017-09-27 Time 07:55 Rev Time 0.00
Received By shill Date 2017-09-27 Time 07:20 Sent To  
Notes
2017-09-27 07:55:46****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. SHEET A0.1, FBC EB 504, THIS IS A LEVEL TWO
 ALTERATION (NOT LEVEL ONE), REVISE PLAN.
  
 2. IT IS NOT CLEAR IF FBC ACCESSIBILITY APPLIES, SEE
 FBC A 106. A CHURCH WHICH IS NOT A PLACE OF PUBLIC
 ACCOMMODATION IS EXEMPT. HOWEVER, IF THE PREMISES ARE
 RENTED OUT FOR FUNCTIONS (WEDDINGS, CONFERENCES, ETC.),
 IT IS POSSIBLE THAT THE FACILITY IS CONSIDERED A PLACE
 OF PUBLIC ACCOMMODATION AND SUBJECT TO THE REQUIREMENTS
 OF FBC ACCESSIBILITY.
  
 IF EXEMPT, PROVIDE INFORMATION REGARDING EXEMPTION. IT
 IS SUGGESTED THAT YOU SEND THE PROPOSED LANGUAGE TO ME
 VIA EMAIL PRIOR TO RESUBMITTAL. THE JUSTIFICATION FOR
 EXEMPTION MAY BE MADE EITHER BY DESIGN PROFESSIONAL ON
 THE PLAN OR IN THE FORM OF A LETTER FROM THE CHURCH ON
 LETTERHEAD. CONTACT ME IF YOU WISH TO DISCUSS.
  
 3. PURPOSE OF THE "WORK ALCOVE" IS NOT CLEAR (SHEET
 A1.0 "NEW WORK NOTES"). "WORK AREAS" ARE GENERALLY
 EXEMPT, BUT THE NATURE OF THE "WORK AREAS" IS NOT
 CLEAR, REVISE PLAN TO CLARIFY.
  
 4. VALUE APPEARS LOW, FBC 109. IF SUBJECT TO
 ACCESSIBILITY, ACCESSIBLE ROUTE TO THE ALTERED AREA
 (PULPIT) MAY BE REQUIRED, FBC A 202.3. A COST BREAKDOWN
 MAY BE REQUIRED IN THE EVENT OF DISPROPORTIONATE COST.
 NOT ENOUGH INFORMATION ON THE PLAN TO DETERMINE CODE
 COMPLIANCE.
  
 5. PLAN REFERS TO "REMOVED WINDOWS"; SHOULDN'T THIS BE
 "PROPOSED" WORK? FBC 107.
  
 6. FBC 107, FBC B CHAPTER 3, REVISE PLAN TO INCLUDE
 OCCUPANCY CLASSIFICATION.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-10-17 Cont ID  
Sent By jpearson Date 2017-10-17 Time 07:39 Rev Time 0.00
Received By jpearson Date 2017-10-17 Time 07:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-09-27 Cont ID  
Sent By jpearson Date 2017-09-27 Time 08:48 Rev Time 0.00
Received By jpearson Date 2017-09-27 Time 08:48 Sent To  
Notes
2017-09-27 08:48:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; FBC 107.2.1, 107.3.5
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.2, 215.5, 408.4
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-10-13 Cont ID  
Sent By pleduc Date 2017-10-13 Time   Rev Time 0.00
Received By pleduc Date 2017-10-13 Time 09:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-09-15 Cont ID  
Sent By pleduc Date 2017-09-15 Time   Rev Time 0.00
Received By pleduc Date 2017-09-15 Time 12:03 Sent To  
Notes
2017-09-15 13:05:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 0.1 - THERE IS NO INDICATION OF REVIEW OR
 DESIGN WITH ANY FIRE CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE A
 INDICATING NOTE.
  
  
  
 2) SHEET A 0.1 - THERE IS NO REFERNCE TO THE EXISTING
 OCCUPANCY TYPE AND IF THERE IS AN EXISTING FIRE
 SPRINKLER OR FIRE ALARM SYSTEM.
  
 PLEASE INDICATE THE OCCUPANCY TYPE AND ANY EXISTING
 FIRE SPRINKLER AND/OR FIRE ALARM SYSTEM.
  
  
  
 3) SHEET A 1.0 - THE PROPOSED PROJECT REMOVES WALLS AND
 INSTALLS NEW WALLS THAT MAY AFFECT THE THE EXISTING
 FIRE SPRINKLER COVERAGE AND FIRE ALARM SYSTEM DEVICES
 AND FUNCTION.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 PLEASE PROVIDE THE APPLICABLE NOTE.
  
  
  
 4) SHEET A 1.1 - NOTE 23 INDICATES ELECTRICAL WORK,
 WIRING AND EQUIPEMNT; HOWEVER, THERE IS NO ELECTRICAL
 DRAWING SHEET.
  
 PLEASE PROVIDE AN ELECTRICAL DRAWING SHEET SHOWING THE
 ELECTRIC SERVICE PANEL INFORMATION AND ALL APPLICABLE
 WIRING ROUTES AND EQUIPMENT LOCATIONS.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-17 Cont ID  
Sent By jpearson Date 2017-10-17 Time 07:39 Rev Time 0.00
Received By jpearson Date 2017-10-11 Time 14:10 Sent To  
Notes
2017-10-12 14:10:44B03

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-27 Cont ID  
Sent By gjohnson Date 2017-09-27 Time 12:14 Rev Time 0.00
Received By gjohnson Date 2017-09-13 Time 15:49 Sent To  
Notes
2017-09-14 15:49:40B01

Review Stop P PLUMBING
Rev No 2 Status N Date 2017-10-16 Cont ID  
Sent By gjohnson Date 2017-10-16 Time 11:33 Rev Time 0.00
Received By gjohnson Date 2017-10-16 Time 11:33 Sent To  
Notes
2017-10-16 11:34:09NO PLUMBING UNDER THIS PERMIT.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-09-27 Cont ID  
Sent By gjohnson Date 2017-09-27 Time 12:07 Rev Time 0.00
Received By gjohnson Date 2017-09-27 Time 12:07 Sent To  
Notes
2017-09-27 12:14:251ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. WHAT ARE THE NEW WATER AND SANITARY LINES SERVING
 SHOW FIXTURES ON FLOOR PLAN. PER WPB AMEND TO FBC
 107.2.1
  
 2. PROVIDE A WATER AND SANITARY ISOMETRIC DRAWING
 SHOWING NEW WORK. WPB AMEND TO FBC 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  