| Plan Review Stops For Permit 17090205 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2019-06-21 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-06-21 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-06-21 |
Time |
15:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2019-06-06 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-06-06 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-06-05 |
Time |
13:31 |
Sent To |
|
|
| Notes |
| 2019-06-06 09:26:35 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 17090205 | | | REVIEWED: JUNE 5, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC[B] = FBC BUILDING | | | FBC[EXISTING] = FBC EXISTING BUILDING | | | FBC[A] = FBC ACCESSIBILITY | | | FBC[E] = FBC ENERGY CONSERVATION | | | | | | 105.1 FBC[AMENDED] PLEASE PROVIDE A REVISED PERMIT | | | APPLICATION TO UPDATE THE DESCRIPTION AND VALUE OF | | | PROJECT. | | | | | | 1) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH | | | ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES | | | TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH | | | THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND | | | THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR | | | GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS | | | ORDINANCE. PER CITY OF WEST PALM BEACH ORDINANCE NO. | | | 4504-14, AND CITY OF WEST PALM BEACH CODE OF | | | ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION | | | 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS | | | 1% OF THE TOTAL PROJECT CONSTRUCTION COST. PER CITY OF | | | WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, ART IN | | | PUBLIC PLACES, SECTION 78-122, RENOVATION AND NEW | | | CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO THE | | | ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE | | | PROJECTS. SEC. 78-129. - PUBLIC ART ASSESSMENT FOR | | | PRIVATE DEVELOPMENT. (A) APPLICABILITY. THE PROVISIONS | | | OF THIS ARTICLE AND THE PUBLIC ART ASSESSMENT SECTION | | | SHALL APPLY TO ALL PRIVATE DEVELOPMENT PROJECTS, | | | INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR | | | IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL | | | CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN | | | $750,000.00. ALL BUILDINGS WITHIN NEW PLANNED | | | DEVELOPMENTS SHALL BE ASSESSED CUMULATIVELY TOWARDS | | | THIS ART IN PUBLIC PLACES REQUIREMENT, EVEN IF THE | | | BUILDINGS ARE PERMITTED SEPARATELY OR DEVELOPED IN | | | PHASES. THE PROVISIONS OF THIS SECTION APPLY TO NEW | | | DEVELOPMENT OR NEW CONSTRUCTION WITHIN EXISTING PLANNED | | | DEVELOPMENTS. | | | - THIS PROJECT MEETS THE CRITERIA TO PROVIDE AIPP. | | | PLEASE CONTACT: MS. SYBILLE WELTER ART IN PUBLIC PLACES | | | COORDINATOR 822-1515 E-MAIL: [email protected] | | | | | | 2) 107.5.3 FBC[AMENDED] SHEET LS-1 STATES TYPE V-B. THE | | | CODE SUMMARY ON SAME SHEET SAYS TYPE II UNPROTECTED. | | | - PLEASE CHANGE OR ERASE SINCE I BELIEVE V-B IS THE | | | CONSTRUCTION TYPE. | | | | | | 3) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR | | | WINDOWS, WINDOW MULL AND DOORS. | | | - PLEASE PROVIDE DOOR AND WINDOW SCHEDULE TO SHOW SIZES | | | AND DOOR TYPES (INCLUDE GLASS WALL SYSTEM). I RECEIVED | | | PRODUCT APPROVAL (P.A.) FOR STOREFRONT. PLEASE CLARIFY | | | WHERE THE STOREFRONT IS GOING. | | | | | | 3A) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS. | | | - I DIDN'T SEE P.A . FOR WINDOWS. ALSO, MULL IF NEEDED | | | AT FRONT WINDOW. | | | | | | 3B) 4107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS. | | | - PLEASE PROVIDE 2 COPIES OF ANY NEW P.A.'S. WE WILL | | | MAKE ADDITIONAL COPY OF ANY THAT ARE ALREADY SUBMITTED | | | THAT GET APPROVED. | | | | | | 4) 502.1 FBC[CE] GENERAL. ADDITIONS TO AN EXISTING | | | BUILDING, BUILDING SYSTEM OR PORTION THEREOF SHALL | | | CONFORM TO THE PROVISIONS OF THIS CODE AS THOSE | | | PROVISIONS RELATE TO NEW CONSTRUCTION WITHOUT REQUIRING | | | THE UNALTERED PORTION OF THE EXISTING BUILDING OR | | | BUILDING SYSTEM TO COMPLY WITH THIS CODE. ADDITIONS | | | SHALL NOT CREATE AN UNSAFE OR HAZARDOUS CONDITION OR | | | OVERLOAD EXISTING BUILDING SYSTEMS. AN ADDITION SHALL | | | BE DEEMED TO COMPLY WITH THIS CODE IF THE ADDITION | | | ALONE COMPLIES OR IF THE EXISTING BUILDING AND ADDITION | | | COMPLY WITH THIS CODE AS A SINGLE BUILDING. ADDITIONS | | | SHALL COMPLY WITH SECTION C502.2. ADDITIONS COMPLYING | | | WITH ANSI/ASHRAE/IESNA 90.1. NEED NOT COMPLY WITH | | | SECTIONS C402, C403, C404 AND C405. | | | - PLEASE PROVIDE UPDATED ENERGY CALCULATIONS TO INCLUDE | | | THE ADDITION. ALSO, USE THE CODE VERSION TO MATCH A AND | | | S SHEETS. | | | | | | 5) 107.3.4.1 FBC[AMENDED] PRODUCT APPROVALS FOR ROOFING | | | INSULATION ATTACHMENT. R VALUES SHOULD BE PROVIDED IN | | | ENERGY CALCULATIONS. | | | - PROVIDE ENHANCED ATTACHMENT FOR INSULATION PER | | | LIMITATION 5.9 MECHANICALLY ATTACHED INSULATION. | | | - ROOFING CAN BE DEFRRED SUBMITTAL IF REQUESTED. | | | | | | PROVISOS: | | | | | | AWNINGS TO BE DONE UNDER SEPARATE PERMIT. | | | | | | 107.3.4.1 FBC[AMENDED] SUBMIT TRUSS SHOP DRAWINGS TO | | | THE BUILDING INSPECTOR PRIOR TO INSTALLATION. | | | - THE TRUSS SUBMITTAL CAN BE APPROVED NOW IF PUT IN | | | SUPPORTING DOCUMENTS AS A SUBMITTAL, OR IT CAN BE | | | DEFERRED. IF DEFERED THE TRUSS PACKAGE NEEDS TO BE | | | REVIEWED BY BUILDING INSPECTOR PRIOR TO INSTALLATION. | | | | | | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | | | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | | OF MATERIALS REQUESTED. | | | | | | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2017-10-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-10-25 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-10-25 |
Time |
07:55 |
Sent To |
|
|
| Notes |
| 2017-10-25 07:55:41 | USC-404 TYPE 437 - ALT: NON-RES, NON-HSKPG | | | SQUARE FEET - 3132 | | | | | | CONSTRUCTION TYPE: VB | | | UNITS: 1 | | | FLOORS: 1 | | | BEDROOMS: | | | ROOMS: | | | SQ FT LIVABLE: 3132 | | | SQ FT FOOTPRINT: 3132 | | | SQ FT ROOF: 3132 | | | | | | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF | | | KNOWN): | | | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): | | | XX.XX | | | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: | | | XX.XX | | | OCC LOAD: 32 | | | PROP USE: OFFICE | | | SPRINKLER SYS? | | | SPRK REQ'D? | | | BATHRMS: | | | | | | BLDG CODE: FL 2014 | | | OCC CLASS: 5TH ED B | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2017-09-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-09-28 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-09-28 |
Time |
16:15 |
Sent To |
|
|
| Notes |
| 2017-09-28 16:26:55 | USC-404 TYPE 437 - ALT: NON-RES, NON-HSKPG | | | SQUARE FEET - 3132 | | | | | | CONSTRUCTION TYPE: VB | | | UNITS: 1 | | | FLOORS: 1 | | | BEDROOMS: | | | ROOMS: | | | SQ FT LIVABLE: 3132 | | | SQ FT FOOTPRINT: 3132 | | | SQ FT ROOF: 3132 | | | | | | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF | | | KNOWN): | | | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): | | | XX.XX | | | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: | | | XX.XX | | | OCC LOAD: 32 | | | PROP USE: OFFICE | | | SPRINKLER SYS? | | | SPRK REQ'D? | | | BATHRMS: | | | | | | BLDG CODE: FL 2014 | | | OCC CLASS: 5TH ED B | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-06-11 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-06-11 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-06-11 |
Time |
12:15 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2017-09-22 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2017-09-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2017-09-20 |
Time |
08:26 |
Sent To |
|
|
| Notes |
| 2017-09-22 08:38:31 | THIS PLAN HAS BEEN APPROVED PROVISIONALLY: | | | | | | FOR ROUGH INSPECTION- PROVIDE LEGEND FOR HEXEGON | | | SHAPED, LETTERED NOTES ON PLAN. | | | | | | FOR FINAL INPSECTION- PROVIDE ACCURATE LOAD CALCULATION | | | FOR PANEL "M". | | | | | | PROVIDE AS-BUILT DRAWING SHOWING LOCATIONS OF PANELS "M | | | AND L". PANELS CANNOT BE LOCATED IN BATHROOMS OR | | | CLOSETS NEC 240.24 D&E | | | | | | CONFERENCE ROOM ALSO NEEDS 50% RECEPTACLE CONTROL | | | FBC-CE C.401.2 | | | | | | PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | | NEC 110.9, 110.10 | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | FRANK GIAQUINTO | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WPB | | | DEVELOPMENT SERVICES DEPT. | | | CELL 561-657-1653 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2019-06-20 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-06-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-06-20 |
Time |
14:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2019-05-20 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-05-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-05-20 |
Time |
09:27 |
Sent To |
|
|
| Notes |
| 2019-05-20 09:35:34 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) THERE ARE INDICATIONS OF THE LIGHTWEIGHT FROME ROOF | | | TRUSSES. | | | | | | PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR | | | STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION. | | | ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT | | | RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES | | | HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE | | | CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A | | | MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND | | | 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR. | | | THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO | | | THE LEFT OF THE MAIN ENTRY DOOR. | | | 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE | | | MARKED WITH THE LETTER "R". | | | 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS | | | SHALL BE MARKED WITH THE LETTER "F". | | | 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF | | | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-10-19 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-10-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-10-19 |
Time |
15:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2017-09-15 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-09-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-09-15 |
Time |
12:03 |
Sent To |
|
|
| Notes |
| 2017-09-15 13:22:51 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) SHEET A 5 - THE DOOR SCHEDULE DOES NOT INDICATE | | | HARDWARE OR LOCKS ON ANY DOOR. | | | | | | LOCKS AND HARDWARE ON EXIT DOORS SHALL COMPLY WITH THE | | | REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS | | | AND CHAPTER 38, NEW BUSINESS OCCUPANCIES. | | | | | | 38.2.2 MEANS OF EGRESS COMPONENTS. | | | 38.2.2.1 COMPONENTS PERMITTED. MEANS OF EGRESS | | | COMPONENTS SHALL BE LIMITED TO THE TYPES DESCRIBED IN | | | 38.2.2.2 THROUGH | | | 38.2.2.12. | | | 38.2.2.2 DOORS. | | | 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE | | | PERMITTED. | | | 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE | | | PERMITTED ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS. | | | | | | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE | | | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR | | | OPERATION FROM THE EGRESS SIDE | | | | | | 7.2.1.5.5 KEY-OPERATED LOCKS. | | | 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED | | | TO HAVE KEYOPERATED LOCKS FROM THE EGRESS SIDE, | | | PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET: | | | (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 | | | THROUGH 43 FOR THE SPECIFIC OCCUPANCY. | | | (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS | | | THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND | | | THAT READS AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE | | | DOOR LEAF: THIS DOOR TO REMAIN UNLOCKED WHEN THE | | | BUILDING IS | | | OCCUPIED. | | | (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY | | | DISTINGUISHABLE AS LOCKED. | | | (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT | | | INSIDE THE BUILDING WHEN IT IS LOCKED. | | | | | | PLEASE ENSURE THE REQUIREMENTS ARE MET. A FIRE | | | INSPECTOR SHALL VERIFY ON FIRE INSPECTION. | | | | | | | | | | | | 2) SHEET SP 1 - CONSTRUCTION AND DEMOLITION SHALL | | | COMPLY WITH NFPA 241, STANDARD FOR SAFEGUARDING | | | CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS, | | | 2013 EDITION. | | | | | | NOTE # 7 WAS ADDED TO THE SHEET. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-06-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-06-14 |
Time |
16:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-06-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-05-08 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2019-06-04 07:50:31 | 6/4 TO DB DESK | | | | | 2019-05-17 10:42:23 | ROUTED FROM ZONING TO PERMIT LIBRARIAN 5/17/19 EL | | 2019-05-09 11:23:16 | C15 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-10-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-10-25 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-10-17 |
Time |
15:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-10-02 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-10-02 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-09-13 |
Time |
15:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2019-06-21 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-06-21 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-06-21 |
Time |
15:22 |
Sent To |
|
|
| Notes |
| 2019-06-21 15:23:41 | OK-PLANS STAMPED | | | OK-RECEIPT PROVIDED | | | MU-2019-018209-0000 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2019-06-06 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-06-06 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-06-06 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2019-06-06 09:27:30 | 109 FBC[AMENDED] PLANS REQUIRE REVIEW BY THE PBC IMPACT | | | FEE OFFICE. ?CALL (561) 233-5025. ?UPON APPROVAL, YOU | | | MAY CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR | | | REVIEW. ?PLEASE RETURNED STAMPED AND WITH A COPY OF THE | | | RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE | | | OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO | | | V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN | | | AIRE.PDF | | | | | | DYLAN BATTLES | | | 561-805-6718 | | | [email protected] | | | | | | THE CITY OF WEST PALM BEACH | | | BUILDING PLANS EXAMINER PX4191 | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2019-06-28 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-06-28 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-06-28 |
Time |
11:51 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2019-06-03 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-06-03 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-06-03 |
Time |
12:47 |
Sent To |
|
|
| Notes |
| 2019-06-03 15:30:54 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #17090205 | | | 6/3/2019 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) M-1: A SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR | | | SYSTEM OF THE 5-TON AHU-1 SYSTEM PER SECTION 606.2.1. | | | PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE | | | MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEM IS | | | NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2017-10-25 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-10-25 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-10-25 |
Time |
09:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2017-09-25 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-09-25 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-09-25 |
Time |
15:23 |
Sent To |
|
|
| Notes |
| 2017-09-25 15:40:54 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17090205 | | | 9/25/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) M-1: A SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR | | | SYSTEM OF THE 5-TON AHU-1 SYSTEM PER SECTION 606.2.1. | | | PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE | | | MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEM IS | | | NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR. | | | | | | 2) M-1: THE AC CLOSET DOORS SHALL BE NON-COMBUSTIBLE IN | | | COMPLIANCE WITH SECTION C403.2.7.2 FBC-14 ENERGY | | | CONSERVATION AND SECTION 602 FBC-14 MECHANICAL. | | | | | | 3) M-2: PROVIDE THE WIND LOAD DESIGN CRITERIA ON THE | | | PLANS FOR INSTALLATION OF THE CONDENSERS, AND SUBMIT A | | | CURRENT MIAMI-DADE NOA FOR THE ROOF STAND- NOA | | | #14-1224.10 SPECIFIED ON THE PLAN HAS EXPIRED. THE | | | ENGINEER OF RECORD MUST PROVIDE AN APPROVAL STAMP ON | | | THE NEW NOA AND MARK OR HIGHLIGHT ALL APPLICABLE NOTES | | | AND INSTALLATION DETAILS- SECTION 301.15 AND RULE 9N-3 | | | FAC. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2019-05-30 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-05-30 |
Time |
18:16 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-05-30 |
Time |
17:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2017-10-25 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-10-25 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-10-25 |
Time |
10:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2017-10-02 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-10-02 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-09-29 |
Time |
13:49 |
Sent To |
|
|
| Notes |
| 2017-10-02 09:52:23 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PLEASE SHOW CLEAR FLOOR SPACE FOR THE | | | TOILET,LAVATORY, WA6TER FOUNTAIN ANDBREAKROOM SINK. PER | | | FBC ACC 604.3.1/602.2 /606.2 | | | | | | 2. PLEASE SHOW COMPLIANCE WITH ACCESSIBILITY FOR THE | | | HEIGHT OF THE LAVATORY AND BREAKROOM SINK. PER FBC ACC | | | 606.3 | | | | | | 3. PLEASE SHOW COMPLIANCE WITH ACCESSIBILITY FOR THE | | | HEIGHT OF THE MIRROR . PER FBC ACC 603.3 | | | | | | 4. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.1 SIDE | | | WALL. | | | THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM, | | | LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL AND | | | EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. | | | | | | 5. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.2 REAR | | | WALL. | | | THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM | | | AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12 | | | INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE | | | OTHER SIDE. | | | | | | 6. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.2 LOCATION. | | | THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR | | | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE | | | OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM | | | TO 18 INCHES | | | | | | 7. PROVIDE THE SQ-FT DRAINED BY SCUPPER AND DOWN SPOUTS | | | INCLUDING PARAPET WALLS. PER FBC PL 1106.4 VERTICAL | | | WALLS. | | | IN SIZING ROOF DRAINS AND STORM DRAINAGE PIPING, | | | ONE-HALF OF THE AREA OF ANY VERTICAL WALL THAT DIVERTS | | | RAINWATER TO THE ROOF SHALL BE ADDED TO THE PROJECTED | | | ROOF AREA FOR INCLUSION IN CALCULATING THE REQUIRED | | | SIZE OF VERTICAL CONDUCTORS, LEADERS AND HORIZONTAL | | | STORM DRAINAGE PIPING. | | | | | | 8. PLEASE PROVIDE COMPLIANCE WITH FBC PL 1108.1 | | | SECONDARY (EMERGENCY OVERFLOW) DRAINS OR SCUPPERS. | | | WHERE ROOF DRAINS ARE REQUIRED, SECONDARY (EMERGENCY | | | OVERFLOW) ROOF DRAINS OR SCUPPERS SHALL BE PROVIDED | | | WHERE THE ROOF PERIMETER CONSTRUCTION EXTENDS ABOVE THE | | | ROOF IN SUCH A MANNER THAT WATER WILL BE ENTRAPPED IF | | | THE PRIMARY DRAINS ALLOW BUILDUP FOR ANY REASON. | | | | | | 9. THE LAVATORY FAUCETS SHALL COMPLY WITH FBC PL 416.5 | | | TEMPERED WATER FOR PUBLIC HAND-WASHING FACILITIES. | | | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND | | | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES | | | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED | | | WATER SHALL BE DELIVERED THROUGH AN APPROVED | | | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE | | | 1070 OR CSA B125.3. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2019-06-21 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-06-21 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-06-21 |
Time |
15:18 |
Sent To |
|
|
| Notes |
| 2019-06-21 15:22:00 | APPROVED FL3915-R27 FOR FLAT ROOF. | | | PROVISO: | | | PROVIDE ENGINEERING FOR ENHANCED MECHANICALLY | | | ATTACHMENT IF APPLICABLE TO INSULATION AND ROOFING | | | SUBSTRATE. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2017-09-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-09-28 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-09-28 |
Time |
16:37 |
Sent To |
|
|
| Notes |
| 2017-09-28 16:38:19 | A ROOF PERMIT APPLICATION IS REQUIRED. SUBMIT PRODUCT | | | APPROVAL REVIEWED BY DESIGNER OF RECORD. INDICATE WHICH | | | APPROVED ASSEMBLY IS PROPOSED AND PROVIDE ENGINEERING | | | FOR ENHANCED FASTENING IF APPLICABLE. | | | | | | |
|
|
| Review Stop |
X |
PERMIT EXTENSION |
| Rev No |
1 |
Status |
P |
Date |
2018-11-05 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2018-11-05 |
Time |
19:23 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2018-11-05 |
Time |
19:23 |
Sent To |
|
|
| Notes |
| 2018-11-05 19:24:56 | 6/22/18 TOOK PERMIT APPLICATION AND FILE SET OF PLANS | | | AND DOCUMENTS TO COURT PER SUBPOENA FOR WITNESS | | | TESTIMONY. RETURNED THEM TO SUSAN PALMER'S DESK FOR | | | REFILING FOR PICK UP UNDER "M" BECAUSE CONTRACTOR | | | PICKED UP THEIR SET TO USE IN COURT BUT HAS NOT PAID | | | THE PERMIT FEE YET SO THE PERMIT HAS NOT BEEN ISSUED. | | | RB |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2020-01-27 |
|
|
Cont ID |
|
| Sent By |
elevesqu |
Date |
2020-01-27 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
elevesqu |
Date |
2020-01-27 |
Time |
08:51 |
Sent To |
|
|
| Notes |
| 2020-01-27 08:51:51 | PROVISO: UNPERMITTED CHAIN LINK FENCE TO BE REMOVED | | | PRIOR TO ISSUANCE OF SEALCOAT PERMIT | | | | | | LIZ LEVESQUE, URBAN DESIGN PLANNER | | | [email protected] | | | 561 822 1426 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2019-05-31 |
|
|
Cont ID |
|
| Sent By |
elevesqu |
Date |
2019-05-31 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
elevesqu |
Date |
2019-05-31 |
Time |
15:56 |
Sent To |
|
|
| Notes |
| 2019-05-31 15:57:44 | PROVISOS: | | | | | | LANDSCAPE CONDITION SHALL BE INSPECTED AT TIME OF CC | | | FOR ANY NECESSARY IMPROVEMENTS | | | PARKING LOT SHALL BE SEALCOATED AND RETSTRIPED BY | | | SEPARATE PERMIT | | | UNPERMITTED CHAIN LINK FENCE SHALL BE REMOVED AT TIME | | | OF CC | | | | | | LIZ LEVESQUE, URBAN DESIGN PLANNER | | | 561 822 1426 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2019-05-17 |
|
|
Cont ID |
|
| Sent By |
elevesqu |
Date |
2019-05-17 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
elevesqu |
Date |
2019-05-17 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2019-05-17 10:42:00 | | | | 1. PLEASE INDICATE PROPOSED LOCATION OF SIGN WITH | | | ADDITION OF AWNING - TO ENSURE FUTURE SIGN CAN FIT AND | | | THERE WILL BE NO FUTURE ISSUES WITH APPLICANT WANTING A | | | SIGN. | | | | | | 2. PLEASE EVALUATE IF PROPOSED AWNING AND BAHAMA | | | SHUTTERS ARE BOTH NEEDED. STAFF WOULD LIKE TO MAINTAIN | | | TRANSPARENCY WITH SIDEWALK. | | | | | | 3. PLEASE CONSIDER EXTENDING FRONT (NORTH) WINDOWS DOWN | | | TO IMPROVE TRANSPARENCY, AS PREVIOUSLY DISCUSSED WITH | | | STAFF. | | | | | | 4. COULD NOT LOCATE PERMIT FOR CHAIN LINK FENCE. PLEASE | | | REMOVE AND IF REPLACING, USE HIGHER QUALITY FENCE | | | MATERIAL. CHAIN LINK NOT PERMITTED IN URBAN CORE | | | DISTRICTS IN DMP. FENCE REQUIRES SEPARATE PERMIT. | | | | | | 5. DUMPSTER ENCLOSURE REQUIRED PER SECTION 94-315. | | | PLEASE SHOW PROPOSED LOCATION IN PARKING LOT DETAIL. | | | PLEASE PROVIDE ENCLOSURE DETAILS MEETING CODE | | | REQUIREMENTS INCLUDING LANDSCAPING. | | | | | | PERMIT TYPE CHANGE- NO LONGER JUST RENOVATION, BUT | | | EXPANSION. NEW REQUIREMENTS FOR PARKING LOT TRIGGERED: | | | | | | 1. PARKING LOT SHALL BE BROUGHT INTOCOMPLIANCE WITH | | | CURRENT CODE INCLUDING LANDSCAPE REQUIREMENTS AND | | | STRIPING DETAIL. | | | PARKING REGULATIONS INCLUDING SPACE SIZE REQUIREMENTS, | | | AISLE WIDTH REQUIREMENTS, AND STRIPING DETAIL CAN BE | | | FOUND IN ARTICLE XV OF THE ZLDRS. | | | | | | LANDSCAPE REQUIREMENTS FOR PARKING LOTS: SECTION 94-113 | | | LOTS SHALL MEET THE MINIMUM GROUND FLOOR SETBACK | | | REQUIREMENTS OF SUBDISTRICT. A FIVE-FOOT LANDSCAPE | | | BUFFER SHALL BE PROVIDED IN ADDITION TO THE GROUND | | | FLOOR SETBACK THAT SHALL BE COMPRISED OF A HEDGE | | | PLANTED AT 2-3' INTERVALS AND MAINTAINED AT A MAX | | | HEIGHT OF 36 INCHES AT MATURITY. SHADE TREES SHALL BE | | | PLANTED AT 30-FOOT INTERVALS. A FIVE-FOOT LANDSCAPE | | | BUFFER SHALL ALSO BE PROVIDED MEETING THESE | | | REQUIREMENTS FOR THE ENTIRE PERIMETER OF THE SURFACE | | | LOT. | | | | | | EACH ROW OF PARKING SPACES SHALL BE TERMINATED BY | | | LANDSCAPED ISLANDS OF NOT LESS THAN FIVE FEET IN WIDTH | | | AND NOT LESS THAN THE LENGTH OF THE ADJACENT PARKING | | | STALL. THE LANDSCAPED ISLAND SHALL HAVE A MINIMUM | | | RADIUS OF TWO AND ONE-HALF FEET AT ITS END. SHALL | | | CONTAIN AT LEAST ONE SHADE OR FLOWERING TREE. | | | | | | INTERIOR ISLANDS. ONE INTERIOR LANDSCAPE ISLAND SHALL | | | BE PROVIDED FOR EVERY TEN PARKING SPACES OR FRACTION | | | THEREOF. INTERIOR LANDSCAPE ISLANDS SHALL BE AT LEAST | | | FIVE FEET WIDE AND SHALL CONTAIN AT LEAST ONE SHADE OR | | | FLOWERING TREE. | | | | | | | | | LIZ LEVESQUE, URBAN DESIGN PLANNER | | | 561 822 1426 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2017-09-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
kmartin |
Date |
2017-09-28 |
Time |
09:24 |
Sent To |
|
|
| Notes |
|
|