Plan Review Details - Permit 17090205
Plan Review Stops For Permit 17090205
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-06-21 Cont ID  
Sent By dbattles Date 2019-06-21 Time 15:22 Rev Time 0.00
Received By dbattles Date 2019-06-21 Time 15:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-06-06 Cont ID  
Sent By dbattles Date 2019-06-06 Time 09:21 Rev Time 0.00
Received By dbattles Date 2019-06-05 Time 13:31 Sent To  
Notes
2019-06-06 09:26:35BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 17090205
 REVIEWED: JUNE 5, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 105.1 FBC[AMENDED] PLEASE PROVIDE A REVISED PERMIT
 APPLICATION TO UPDATE THE DESCRIPTION AND VALUE OF
 PROJECT.
  
 1) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH
 ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES
 TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH
 THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND
 THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS
 ORDINANCE. PER CITY OF WEST PALM BEACH ORDINANCE NO.
 4504-14, AND CITY OF WEST PALM BEACH CODE OF
 ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST. PER CITY OF
 WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, ART IN
 PUBLIC PLACES, SECTION 78-122, RENOVATION AND NEW
 CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO THE
 ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS. SEC. 78-129. - PUBLIC ART ASSESSMENT FOR
 PRIVATE DEVELOPMENT. (A) APPLICABILITY. THE PROVISIONS
 OF THIS ARTICLE AND THE PUBLIC ART ASSESSMENT SECTION
 SHALL APPLY TO ALL PRIVATE DEVELOPMENT PROJECTS,
 INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR
 IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL
 CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000.00. ALL BUILDINGS WITHIN NEW PLANNED
 DEVELOPMENTS SHALL BE ASSESSED CUMULATIVELY TOWARDS
 THIS ART IN PUBLIC PLACES REQUIREMENT, EVEN IF THE
 BUILDINGS ARE PERMITTED SEPARATELY OR DEVELOPED IN
 PHASES. THE PROVISIONS OF THIS SECTION APPLY TO NEW
 DEVELOPMENT OR NEW CONSTRUCTION WITHIN EXISTING PLANNED
 DEVELOPMENTS.
 - THIS PROJECT MEETS THE CRITERIA TO PROVIDE AIPP.
 PLEASE CONTACT: MS. SYBILLE WELTER ART IN PUBLIC PLACES
 COORDINATOR 822-1515 E-MAIL: [email protected]
  
 2) 107.5.3 FBC[AMENDED] SHEET LS-1 STATES TYPE V-B. THE
 CODE SUMMARY ON SAME SHEET SAYS TYPE II UNPROTECTED.
 - PLEASE CHANGE OR ERASE SINCE I BELIEVE V-B IS THE
 CONSTRUCTION TYPE.
  
 3) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 WINDOWS, WINDOW MULL AND DOORS.
 - PLEASE PROVIDE DOOR AND WINDOW SCHEDULE TO SHOW SIZES
 AND DOOR TYPES (INCLUDE GLASS WALL SYSTEM). I RECEIVED
 PRODUCT APPROVAL (P.A.) FOR STOREFRONT. PLEASE CLARIFY
 WHERE THE STOREFRONT IS GOING.
  
 3A) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS.
 - I DIDN'T SEE P.A . FOR WINDOWS. ALSO, MULL IF NEEDED
 AT FRONT WINDOW.
  
 3B) 4107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS.
 - PLEASE PROVIDE 2 COPIES OF ANY NEW P.A.'S. WE WILL
 MAKE ADDITIONAL COPY OF ANY THAT ARE ALREADY SUBMITTED
 THAT GET APPROVED.
  
 4) 502.1 FBC[CE] GENERAL. ADDITIONS TO AN EXISTING
 BUILDING, BUILDING SYSTEM OR PORTION THEREOF SHALL
 CONFORM TO THE PROVISIONS OF THIS CODE AS THOSE
 PROVISIONS RELATE TO NEW CONSTRUCTION WITHOUT REQUIRING
 THE UNALTERED PORTION OF THE EXISTING BUILDING OR
 BUILDING SYSTEM TO COMPLY WITH THIS CODE. ADDITIONS
 SHALL NOT CREATE AN UNSAFE OR HAZARDOUS CONDITION OR
 OVERLOAD EXISTING BUILDING SYSTEMS. AN ADDITION SHALL
 BE DEEMED TO COMPLY WITH THIS CODE IF THE ADDITION
 ALONE COMPLIES OR IF THE EXISTING BUILDING AND ADDITION
 COMPLY WITH THIS CODE AS A SINGLE BUILDING. ADDITIONS
 SHALL COMPLY WITH SECTION C502.2. ADDITIONS COMPLYING
 WITH ANSI/ASHRAE/IESNA 90.1. NEED NOT COMPLY WITH
 SECTIONS C402, C403, C404 AND C405.
 - PLEASE PROVIDE UPDATED ENERGY CALCULATIONS TO INCLUDE
 THE ADDITION. ALSO, USE THE CODE VERSION TO MATCH A AND
 S SHEETS.
  
 5) 107.3.4.1 FBC[AMENDED] PRODUCT APPROVALS FOR ROOFING
 INSULATION ATTACHMENT. R VALUES SHOULD BE PROVIDED IN
 ENERGY CALCULATIONS.
 - PROVIDE ENHANCED ATTACHMENT FOR INSULATION PER
 LIMITATION 5.9 MECHANICALLY ATTACHED INSULATION.
 - ROOFING CAN BE DEFRRED SUBMITTAL IF REQUESTED.
  
 PROVISOS:
  
 AWNINGS TO BE DONE UNDER SEPARATE PERMIT.
  
 107.3.4.1 FBC[AMENDED] SUBMIT TRUSS SHOP DRAWINGS TO
 THE BUILDING INSPECTOR PRIOR TO INSTALLATION.
 - THE TRUSS SUBMITTAL CAN BE APPROVED NOW IF PUT IN
 SUPPORTING DOCUMENTS AS A SUBMITTAL, OR IT CAN BE
 DEFERRED. IF DEFERED THE TRUSS PACKAGE NEEDS TO BE
 REVIEWED BY BUILDING INSPECTOR PRIOR TO INSTALLATION.
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-10-25 Cont ID  
Sent By shill Date 2017-10-25 Time 15:58 Rev Time 0.00
Received By shill Date 2017-10-25 Time 07:55 Sent To  
Notes
2017-10-25 07:55:41USC-404 TYPE 437 - ALT: NON-RES, NON-HSKPG
 SQUARE FEET - 3132
  
 CONSTRUCTION TYPE: VB
 UNITS: 1
 FLOORS: 1
 BEDROOMS:
 ROOMS:
 SQ FT LIVABLE: 3132
 SQ FT FOOTPRINT: 3132
 SQ FT ROOF: 3132
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD: 32
 PROP USE: OFFICE
 SPRINKLER SYS?
 SPRK REQ'D?
 BATHRMS:
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED B
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-09-28 Cont ID  
Sent By shill Date 2017-09-28 Time 16:26 Rev Time 0.00
Received By shill Date 2017-09-28 Time 16:15 Sent To  
Notes
2017-09-28 16:26:55USC-404 TYPE 437 - ALT: NON-RES, NON-HSKPG
 SQUARE FEET - 3132
  
 CONSTRUCTION TYPE: VB
 UNITS: 1
 FLOORS: 1
 BEDROOMS:
 ROOMS:
 SQ FT LIVABLE: 3132
 SQ FT FOOTPRINT: 3132
 SQ FT ROOF: 3132
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD: 32
 PROP USE: OFFICE
 SPRINKLER SYS?
 SPRK REQ'D?
 BATHRMS:
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED B
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-06-11 Cont ID  
Sent By jpearson Date 2019-06-11 Time 14:40 Rev Time 0.00
Received By jpearson Date 2019-06-11 Time 12:15 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-09-22 Cont ID  
Sent By fgiaquin Date 2017-09-22 Time   Rev Time 0.00
Received By fgiaquin Date 2017-09-20 Time 08:26 Sent To  
Notes
2017-09-22 08:38:31THIS PLAN HAS BEEN APPROVED PROVISIONALLY:
  
 FOR ROUGH INSPECTION- PROVIDE LEGEND FOR HEXEGON
 SHAPED, LETTERED NOTES ON PLAN.
  
 FOR FINAL INPSECTION- PROVIDE ACCURATE LOAD CALCULATION
 FOR PANEL "M".
  
 PROVIDE AS-BUILT DRAWING SHOWING LOCATIONS OF PANELS "M
 AND L". PANELS CANNOT BE LOCATED IN BATHROOMS OR
 CLOSETS NEC 240.24 D&E
  
 CONFERENCE ROOM ALSO NEEDS 50% RECEPTACLE CONTROL
 FBC-CE C.401.2
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 DEVELOPMENT SERVICES DEPT.
 CELL 561-657-1653
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2019-06-20 Cont ID  
Sent By pleduc Date 2019-06-20 Time   Rev Time 0.00
Received By pleduc Date 2019-06-20 Time 14:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-05-20 Cont ID  
Sent By pleduc Date 2019-05-20 Time   Rev Time 0.00
Received By pleduc Date 2019-05-20 Time 09:27 Sent To  
Notes
2019-05-20 09:35:34THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) THERE ARE INDICATIONS OF THE LIGHTWEIGHT FROME ROOF
 TRUSSES.
  
 PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR
 STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION.
 ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES
 HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A
 MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND
 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR.
 THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO
 THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-10-19 Cont ID  
Sent By pleduc Date 2017-10-19 Time   Rev Time 0.00
Received By pleduc Date 2017-10-19 Time 15:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-09-15 Cont ID  
Sent By pleduc Date 2017-09-15 Time   Rev Time 0.00
Received By pleduc Date 2017-09-15 Time 12:03 Sent To  
Notes
2017-09-15 13:22:51THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET A 5 - THE DOOR SCHEDULE DOES NOT INDICATE
 HARDWARE OR LOCKS ON ANY DOOR.
  
 LOCKS AND HARDWARE ON EXIT DOORS SHALL COMPLY WITH THE
 REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS
 AND CHAPTER 38, NEW BUSINESS OCCUPANCIES.
  
 38.2.2 MEANS OF EGRESS COMPONENTS.
 38.2.2.1 COMPONENTS PERMITTED. MEANS OF EGRESS
 COMPONENTS SHALL BE LIMITED TO THE TYPES DESCRIBED IN
 38.2.2.2 THROUGH
 38.2.2.12.
 38.2.2.2 DOORS.
 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE
  
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED
 TO HAVE KEYOPERATED LOCKS FROM THE EGRESS SIDE,
 PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND
 THAT READS AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE
 DOOR LEAF: THIS DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS
 OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE BUILDING WHEN IT IS LOCKED.
  
 PLEASE ENSURE THE REQUIREMENTS ARE MET. A FIRE
 INSPECTOR SHALL VERIFY ON FIRE INSPECTION.
  
  
  
 2) SHEET SP 1 - CONSTRUCTION AND DEMOLITION SHALL
 COMPLY WITH NFPA 241, STANDARD FOR SAFEGUARDING
 CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS,
 2013 EDITION.
  
 NOTE # 7 WAS ADDED TO THE SHEET.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2019-06-28 Time   Rev Time 0.00
Received By lmarchan Date 2019-06-14 Time 16:42 Sent To  
Notes
2019-06-17 16:42:55C15

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-06-11 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-08 Time 11:22 Sent To  
Notes
2019-06-04 07:50:316/4 TO DB DESK
  
2019-05-17 10:42:23ROUTED FROM ZONING TO PERMIT LIBRARIAN 5/17/19 EL
2019-05-09 11:23:16C15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-25 Cont ID  
Sent By shill Date 2017-10-25 Time 15:58 Rev Time 0.00
Received By shill Date 2017-10-17 Time 15:51 Sent To  
Notes
2017-10-18 15:51:51C19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-02 Cont ID  
Sent By gjohnson Date 2017-10-02 Time 09:58 Rev Time 0.00
Received By gjohnson Date 2017-09-13 Time 15:58 Sent To  
Notes
2017-09-14 15:58:54C19

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-06-21 Cont ID  
Sent By dbattles Date 2019-06-21 Time 15:22 Rev Time 0.00
Received By dbattles Date 2019-06-21 Time 15:22 Sent To  
Notes
2019-06-21 15:23:41OK-PLANS STAMPED
 OK-RECEIPT PROVIDED
 MU-2019-018209-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-06-06 Cont ID  
Sent By dbattles Date 2019-06-06 Time 09:23 Rev Time 0.00
Received By dbattles Date 2019-06-06 Time 09:23 Sent To  
Notes
2019-06-06 09:27:30109 FBC[AMENDED] PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. ?CALL (561) 233-5025. ?UPON APPROVAL, YOU
 MAY CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. ?PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
 THE CITY OF WEST PALM BEACH
 BUILDING PLANS EXAMINER PX4191
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-06-28 Cont ID  
Sent By ccole Date 2019-06-28 Time 11:51 Rev Time 0.00
Received By ccole Date 2019-06-28 Time 11:51 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-06-03 Cont ID  
Sent By ccole Date 2019-06-03 Time 15:28 Rev Time 0.00
Received By ccole Date 2019-06-03 Time 12:47 Sent To  
Notes
2019-06-03 15:30:543RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17090205
 6/3/2019
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M-1: A SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR
 SYSTEM OF THE 5-TON AHU-1 SYSTEM PER SECTION 606.2.1.
 PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE
 MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEM IS
 NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-10-25 Cont ID  
Sent By ccole Date 2017-10-25 Time 09:41 Rev Time 0.00
Received By ccole Date 2017-10-25 Time 09:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-09-25 Cont ID  
Sent By ccole Date 2017-09-25 Time 15:23 Rev Time 0.00
Received By ccole Date 2017-09-25 Time 15:23 Sent To  
Notes
2017-09-25 15:40:541ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17090205
 9/25/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M-1: A SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR
 SYSTEM OF THE 5-TON AHU-1 SYSTEM PER SECTION 606.2.1.
 PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE
 MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEM IS
 NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
 2) M-1: THE AC CLOSET DOORS SHALL BE NON-COMBUSTIBLE IN
 COMPLIANCE WITH SECTION C403.2.7.2 FBC-14 ENERGY
 CONSERVATION AND SECTION 602 FBC-14 MECHANICAL.
  
 3) M-2: PROVIDE THE WIND LOAD DESIGN CRITERIA ON THE
 PLANS FOR INSTALLATION OF THE CONDENSERS, AND SUBMIT A
 CURRENT MIAMI-DADE NOA FOR THE ROOF STAND- NOA
 #14-1224.10 SPECIFIED ON THE PLAN HAS EXPIRED. THE
 ENGINEER OF RECORD MUST PROVIDE AN APPROVAL STAMP ON
 THE NEW NOA AND MARK OR HIGHLIGHT ALL APPLICABLE NOTES
 AND INSTALLATION DETAILS- SECTION 301.15 AND RULE 9N-3
 FAC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-05-30 Cont ID  
Sent By gjohnson Date 2019-05-30 Time 18:16 Rev Time 0.00
Received By gjohnson Date 2019-05-30 Time 17:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-10-25 Cont ID  
Sent By gjohnson Date 2017-10-25 Time 10:54 Rev Time 0.00
Received By gjohnson Date 2017-10-25 Time 10:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-10-02 Cont ID  
Sent By gjohnson Date 2017-10-02 Time 09:30 Rev Time 0.00
Received By gjohnson Date 2017-09-29 Time 13:49 Sent To  
Notes
2017-10-02 09:52:231ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW CLEAR FLOOR SPACE FOR THE
 TOILET,LAVATORY, WA6TER FOUNTAIN ANDBREAKROOM SINK. PER
 FBC ACC 604.3.1/602.2 /606.2
  
 2. PLEASE SHOW COMPLIANCE WITH ACCESSIBILITY FOR THE
 HEIGHT OF THE LAVATORY AND BREAKROOM SINK. PER FBC ACC
 606.3
  
 3. PLEASE SHOW COMPLIANCE WITH ACCESSIBILITY FOR THE
 HEIGHT OF THE MIRROR . PER FBC ACC 603.3
  
 4. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.1 SIDE
 WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM,
 LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL AND
 EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL.
  
 5. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.2 REAR
 WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM
 AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE
 OTHER SIDE.
  
 6. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES
  
 7. PROVIDE THE SQ-FT DRAINED BY SCUPPER AND DOWN SPOUTS
 INCLUDING PARAPET WALLS. PER FBC PL 1106.4 VERTICAL
 WALLS.
 IN SIZING ROOF DRAINS AND STORM DRAINAGE PIPING,
 ONE-HALF OF THE AREA OF ANY VERTICAL WALL THAT DIVERTS
 RAINWATER TO THE ROOF SHALL BE ADDED TO THE PROJECTED
 ROOF AREA FOR INCLUSION IN CALCULATING THE REQUIRED
 SIZE OF VERTICAL CONDUCTORS, LEADERS AND HORIZONTAL
 STORM DRAINAGE PIPING.
  
 8. PLEASE PROVIDE COMPLIANCE WITH FBC PL 1108.1
 SECONDARY (EMERGENCY OVERFLOW) DRAINS OR SCUPPERS.
 WHERE ROOF DRAINS ARE REQUIRED, SECONDARY (EMERGENCY
 OVERFLOW) ROOF DRAINS OR SCUPPERS SHALL BE PROVIDED
 WHERE THE ROOF PERIMETER CONSTRUCTION EXTENDS ABOVE THE
 ROOF IN SUCH A MANNER THAT WATER WILL BE ENTRAPPED IF
 THE PRIMARY DRAINS ALLOW BUILDUP FOR ANY REASON.
  
 9. THE LAVATORY FAUCETS SHALL COMPLY WITH FBC PL 416.5
 TEMPERED WATER FOR PUBLIC HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2019-06-21 Cont ID  
Sent By dbattles Date 2019-06-21 Time 15:18 Rev Time 0.00
Received By dbattles Date 2019-06-21 Time 15:18 Sent To  
Notes
2019-06-21 15:22:00APPROVED FL3915-R27 FOR FLAT ROOF.
 PROVISO:
 PROVIDE ENGINEERING FOR ENHANCED MECHANICALLY
 ATTACHMENT IF APPLICABLE TO INSULATION AND ROOFING
 SUBSTRATE.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2017-09-28 Cont ID  
Sent By shill Date 2017-09-28 Time 16:37 Rev Time 0.00
Received By shill Date 2017-09-28 Time 16:37 Sent To  
Notes
2017-09-28 16:38:19A ROOF PERMIT APPLICATION IS REQUIRED. SUBMIT PRODUCT
 APPROVAL REVIEWED BY DESIGNER OF RECORD. INDICATE WHICH
 APPROVED ASSEMBLY IS PROPOSED AND PROVIDE ENGINEERING
 FOR ENHANCED FASTENING IF APPLICABLE.
  
  

Review Stop X PERMIT EXTENSION
Rev No 1 Status P Date 2018-11-05 Cont ID  
Sent By rbrown Date 2018-11-05 Time 19:23 Rev Time 0.00
Received By rbrown Date 2018-11-05 Time 19:23 Sent To  
Notes
2018-11-05 19:24:566/22/18 TOOK PERMIT APPLICATION AND FILE SET OF PLANS
 AND DOCUMENTS TO COURT PER SUBPOENA FOR WITNESS
 TESTIMONY. RETURNED THEM TO SUSAN PALMER'S DESK FOR
 REFILING FOR PICK UP UNDER "M" BECAUSE CONTRACTOR
 PICKED UP THEIR SET TO USE IN COURT BUT HAS NOT PAID
 THE PERMIT FEE YET SO THE PERMIT HAS NOT BEEN ISSUED.
 RB

Review Stop Z ZONING
Rev No 4 Status P Date 2020-01-27 Cont ID  
Sent By elevesqu Date 2020-01-27 Time 08:51 Rev Time 0.00
Received By elevesqu Date 2020-01-27 Time 08:51 Sent To  
Notes
2020-01-27 08:51:51PROVISO: UNPERMITTED CHAIN LINK FENCE TO BE REMOVED
 PRIOR TO ISSUANCE OF SEALCOAT PERMIT
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426

Review Stop Z ZONING
Rev No 3 Status P Date 2019-05-31 Cont ID  
Sent By elevesqu Date 2019-05-31 Time 15:57 Rev Time 0.00
Received By elevesqu Date 2019-05-31 Time 15:56 Sent To  
Notes
2019-05-31 15:57:44PROVISOS:
  
 LANDSCAPE CONDITION SHALL BE INSPECTED AT TIME OF CC
 FOR ANY NECESSARY IMPROVEMENTS
 PARKING LOT SHALL BE SEALCOATED AND RETSTRIPED BY
 SEPARATE PERMIT
 UNPERMITTED CHAIN LINK FENCE SHALL BE REMOVED AT TIME
 OF CC
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2019-05-17 Cont ID  
Sent By elevesqu Date 2019-05-17 Time 10:42 Rev Time 0.00
Received By elevesqu Date 2019-05-17 Time 10:08 Sent To  
Notes
2019-05-17 10:42:00 
 1. PLEASE INDICATE PROPOSED LOCATION OF SIGN WITH
 ADDITION OF AWNING - TO ENSURE FUTURE SIGN CAN FIT AND
 THERE WILL BE NO FUTURE ISSUES WITH APPLICANT WANTING A
 SIGN.
  
 2. PLEASE EVALUATE IF PROPOSED AWNING AND BAHAMA
 SHUTTERS ARE BOTH NEEDED. STAFF WOULD LIKE TO MAINTAIN
 TRANSPARENCY WITH SIDEWALK.
  
 3. PLEASE CONSIDER EXTENDING FRONT (NORTH) WINDOWS DOWN
 TO IMPROVE TRANSPARENCY, AS PREVIOUSLY DISCUSSED WITH
 STAFF.
  
 4. COULD NOT LOCATE PERMIT FOR CHAIN LINK FENCE. PLEASE
 REMOVE AND IF REPLACING, USE HIGHER QUALITY FENCE
 MATERIAL. CHAIN LINK NOT PERMITTED IN URBAN CORE
 DISTRICTS IN DMP. FENCE REQUIRES SEPARATE PERMIT.
  
 5. DUMPSTER ENCLOSURE REQUIRED PER SECTION 94-315.
 PLEASE SHOW PROPOSED LOCATION IN PARKING LOT DETAIL.
 PLEASE PROVIDE ENCLOSURE DETAILS MEETING CODE
 REQUIREMENTS INCLUDING LANDSCAPING.
  
 PERMIT TYPE CHANGE- NO LONGER JUST RENOVATION, BUT
 EXPANSION. NEW REQUIREMENTS FOR PARKING LOT TRIGGERED:
  
 1. PARKING LOT SHALL BE BROUGHT INTOCOMPLIANCE WITH
 CURRENT CODE INCLUDING LANDSCAPE REQUIREMENTS AND
 STRIPING DETAIL.
 PARKING REGULATIONS INCLUDING SPACE SIZE REQUIREMENTS,
 AISLE WIDTH REQUIREMENTS, AND STRIPING DETAIL CAN BE
 FOUND IN ARTICLE XV OF THE ZLDRS.
  
 LANDSCAPE REQUIREMENTS FOR PARKING LOTS: SECTION 94-113
 LOTS SHALL MEET THE MINIMUM GROUND FLOOR SETBACK
 REQUIREMENTS OF SUBDISTRICT. A FIVE-FOOT LANDSCAPE
 BUFFER SHALL BE PROVIDED IN ADDITION TO THE GROUND
 FLOOR SETBACK THAT SHALL BE COMPRISED OF A HEDGE
 PLANTED AT 2-3' INTERVALS AND MAINTAINED AT A MAX
 HEIGHT OF 36 INCHES AT MATURITY. SHADE TREES SHALL BE
 PLANTED AT 30-FOOT INTERVALS. A FIVE-FOOT LANDSCAPE
 BUFFER SHALL ALSO BE PROVIDED MEETING THESE
 REQUIREMENTS FOR THE ENTIRE PERIMETER OF THE SURFACE
 LOT.
  
 EACH ROW OF PARKING SPACES SHALL BE TERMINATED BY
 LANDSCAPED ISLANDS OF NOT LESS THAN FIVE FEET IN WIDTH
 AND NOT LESS THAN THE LENGTH OF THE ADJACENT PARKING
 STALL. THE LANDSCAPED ISLAND SHALL HAVE A MINIMUM
 RADIUS OF TWO AND ONE-HALF FEET AT ITS END. SHALL
 CONTAIN AT LEAST ONE SHADE OR FLOWERING TREE.
  
 INTERIOR ISLANDS. ONE INTERIOR LANDSCAPE ISLAND SHALL
 BE PROVIDED FOR EVERY TEN PARKING SPACES OR FRACTION
 THEREOF. INTERIOR LANDSCAPE ISLANDS SHALL BE AT LEAST
 FIVE FEET WIDE AND SHALL CONTAIN AT LEAST ONE SHADE OR
 FLOWERING TREE.
  
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2017-09-28 Time   Rev Time 0.00
Received By kmartin Date 2017-09-28 Time 09:24 Sent To  
Notes
***NONE***