Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-02-27 Cont ID  
Sent By aclange Date 2018-02-27 Time 14:42 Rev Time 0.00
Received By aclange Date 2018-02-27 Time 11:17 Sent To  
Notes
2018-02-27 11:40:17PROVISO:
 PRIOR TO CONCRETE POUR, A "BUILDING UNDER CONSTRUCTION"
 (FORM BOARD) ELEVATION CERTIFICATE IS REQUIRED.
 PRIOR TO FINAL INSPECTION, A "FINISHED CONSTRUCTION"
 ELEVATION CERTIFICATE IS REQUIRED. THE FINISHED
 CONSTRUCTION ELEVATION CERTIFICATE MAY BE SENT VIA
 EMAIL FOR PRELIMINARY REVIEW. A SIGNED AND SEALED
 ORIGINAL FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 TO BE SUBMITTED AT THE BUILDING DIVISION, REVIEWED AND
 APPROVED PRIOR TO FINAL INSPECTION. THIS SHOULD BE DONE
 AS EARLY AS POSSIBLE AFTER FINAL GRADE IS COMPLETE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-02-14 Cont ID  
Sent By aclange Date 2018-02-14 Time 13:51 Rev Time 0.00
Received By aclange Date 2018-02-27 Time 11:16 Sent To  
Notes
2018-02-14 13:39:33****CORRECTIONS****
  
 ART LANGE BUILDING PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 2/26/18 NEW COMMENT:
  
 THRESHOLD
  
 THRESHOLD BUILDINGS
  
 1. SPECIAL INSPECTOR AGREEMENT SHALL BE COMPLETED AND
 SUBMITTED IN TRIPLICATE.
 2. PROVIDE RESUME OF JOB INSPECTOR (P.E., ARCH. OR 468
 INSPECTOR).
 3. PROVIDE LIST OF SIMILAR PROJECTS COMPLETED BY
 CONTRACTOR.
 4. PROVIDE STRUCTURAL INSPECTION PLAN.
 5. THIS BUILDING MEETS THE DEFINITION OF: THRESHOLD
 BUILDING F.S. 553.71 (12)
  
 ?THRESHOLD BUILDING? ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND HAS AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 5A) THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS PURSUANT TO
 A STRUCTURAL INSPECTION PLAN PREPARED BY THE ENGINEER
 OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT.
  
 5B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS, A SPECIAL INSPECTOR IS REQUIRED BY F.S.
 553.79 (5) TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE
 FILLED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED AND
 RETURNED TO THIS OFFICE AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE. CONTACT KEN
 CONRAD, MANAGER OF SPECIAL INSPECTOR PROGRAM AT (561)
 805-6666 FOR FURTHER INFORMATION BEFORE THE PERMIT MAY
 BE ISSUED.
  
 5C) MISSING STATEMENT. THRESHOLD BUILDING, REQUIRED.
 W.P.B. AMENDMENT 110.3.7.4.4. ALL PLANS FOR THE
 BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, ?TO THE BEST OF THE ARCHITECT?S OR ENGINEER?S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 F.S.?
  
  
 SECOND REVIEW:
  
 PARTIALLY COMPLIED:
  
 1. ACTUAL BUILDING AREA SHOWN. INCLUDE THE BREAKDOWN OF
 THE ASSEMBLY OCCUPANCY.
  
 OCCUPANCY CLASSIFICATIONS, SF FOR EACH OCC CLASS,
 OCCUPANT LOAD PER OCCUPANCY
  
 IF ASSEMBLY OCCUPANT LOAD EXCEEDS 500 SF, THIS IS A
 THRESHOLD BUILDING PER FS553.71(12) AND THE STATEMENT
 REQUIRED BY FS553.79 IS TO BE INCLUDED ON THE PLAN.
  
  
  
 PENDING THE ABOVE ASSEMBLY CALCULATIONS
  
 2. A RESIDENT INSPECTOR MAY BE REQUIRED, FBC 110.3.9
 (IF THIS BUILDING IS NOT A THRESHOLD BUILDING). IS
 APPLICANT'S INTENT TO USE A RESIDENT INSPECTOR,
 ESPECIALLY SINCE THE OTHER TWO BUILDINGS IN THIS
 PROJECT REQUIRE A THRESHOLD INSPECTOR?
  
  
  
 COMPLIED WITH AN ADDITONAL NOTES.
  
 A. SIGNATURE NOT PROVIDED ON SEAL ON PAGE S0.0.1
 B. ONE SET MISSING PAGE S0.0.1
  
  
 FBC-107.1 GENERAL - FAC 61G1-16.004 - A TITLE BLOCK
 MUST APPEAR ON ALL ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION IDENTIFICATION SHEETS THAT
 ARE REQUIRED TO BE SIGNED AND SEALED. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
  
 3. S0.0.1, REVISE NOTE WHICH REFERS TO SOILS REPORT TO
 INCLUDE REVISION DATED 2/15/2017.
  
  
  
 NOTED, WILL BE ISSED WITH PROVISO WHEN READY.
  
 4. THIS PERMIT WILL BE ISSUED WITH PROVISO:
  
 THIS PARCEL IS LOCATED IN SFHA A5 WITH A BFE OF 7.0'
 NGVD29. PROPOSED FFE IS 9.0' NGVD29.
  
 PRIOR TO CONCRETE POUR, A "BUILDING UNDER CONSTRUCTION"
 (FORM BOARD) ELEVATION CERTIFICATE IS REQUIRED.
  
 PRIOR TO FINAL INSPECTION, A "FINISHED CONSTRUCTION"
 ELEVATION CERTIFICATE IS REQUIRED. THE FINISHED
 CONSTRUCTION ELEVATION CERTIFICATE MAY BE SENT VIA
 EMAIL FOR PRELIMINARY REVIEW. A SIGNED AND SEALED
 ORIGINAL FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 TO BE SUBMITTED AT THE BUILDING DIVISION, REVIEWED AND
 APPROVED PRIOR TO FINAL INSPECTION. THIS SHOULD BE DONE
 AS EARLY AS POSSIBLE AFTER FINAL GRADE IS COMPLETE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-09-25 Cont ID  
Sent By shill Date 2017-09-25 Time 17:00 Rev Time 0.00
Received By shill Date 2017-09-22 Time 17:54 Sent To  
Notes
2017-09-25 17:00:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. REVISE PLAN TO INCLUDE THE FOLLOWING INFORMATION,
 FBC 107:
 BUILDING CONSTRUCTION TYPE
 SQUARE FOOT AREA OF EACH STORY
 OCCUPANCY CLASSIFICATIONS, SF FOR EACH OCC CLASS,
 OCCUPANT LOAD PER OCCUPANCY
  
 IF ASSEMBLY OCCUPANT LOAD EXCEEDS 500 SF, THIS IS A
 THRESHOLD BUILDING PER FS553.71 AND THE STATEMENT
 REQUIRED BY FS553.79 IS TO BE INCLUDED ON THE PLAN.
  
 2. A RESIDENT INSPECTOR MAY BE REQUIRED, FBC 110.3.9
 (IF THIS BUILDING IS NOT A THRESHOLD BUILDING). IS
 APPLICANT'S INTENT TO USE A RESIDENT INSPECTOR,
 ESPECIALLY SINCE THE OTHER TWO BUILDINGS IN THIS
 PROJECT REQUIRE A SPECIAL INSPECTOR?
  
 3. S0.0.1, REVISE NOTE WHICH REFERS TO SOILS REPORT TO
 INCLUDE REVISION DATED 2/15/2017.
  
 4. THIS PERMIT WILL BE ISSUED WITH PROVISO:
  
 THIS PARCEL IS LOCATED IN SFHA A5 WITH A BFE OF 7.0'
 NGVD29. PROPOSED FFE IS 9.0' NGVD29.
  
 PRIOR TO CONCRETE POUR, A "BUILDING UNDER CONSTRUCTION"
 (FORM BOARD) ELEVATION CERTIFICATE IS REQUIRED.
  
 PRIOR TO FINAL INSPECTION, A "FINISHED CONSTRUCTION"
 ELEVATION CERTIFICATE IS REQUIRED. THE FINISHED
 CONSTRUCTION ELEVATION CERTIFICATE MAY BE SENT VIA
 EMAIL FOR PRELIMINARY REVIEW. A SIGNED AND SEALED
 ORIGINAL FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 TO BE SUBMITTED AT THE BUILDING DIVISION, REVIEWED AND
 APPROVED PRIOR TO FINAL INSPECTION. THIS SHOULD BE DONE
 AS EARLY AS POSSIBLE AFTER FINAL GRADE IS COMPLETE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-02-27 Cont ID  
Sent By jpearson Date 2018-02-08 Time 10:40 Rev Time 0.00
Received By jpearson Date 2018-02-08 Time 06:44 Sent To  
Notes
2018-02-27 14:11:34RECEIVED CORRECTION AND CHANGED STATUS TO PASSED.
  
  
2018-02-08 10:39:59CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 THIS REVIEW FOR FOUNDATION PERMIT ONLY.
  
 RESPONSE LETTER STATED THAT SHEET E3.0.0 WAS PROVIDED
 TO ADDRESS COMMENTS. HOWEVER, THE SHEET WAS ONLY
 PROVIDED FOR 2 OF THE 3 SETS. THIS SHEET IS REQUIRED
 FOR EACH SET. (FBC 107.2.1) THE PREVIOUS COMMENT IS
 LISTED BELOW, AND THERE IS A NEW COMMENT THAT FOLLOWS
 BASED ON THE SUBMISSION PROVIDED.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, WIRE AND BREAKER SIZES FOR SERVICE.
 SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING
 TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94,
 408.30, 695.3; FBC 107.2.1
  
 NEW COMMENT:
  
 2. PLAN STATES THAT THE FEED TO THE RETAIL WIREWAY IS 2
 SETS OF 500 KCMIL ALUMINUM, WHICH IS RATED FOR A TOTAL
 OF 620 AMPS. THIS WIRE WILL BE FUSED AT 800 AMPS, SO
 THE WIRE IS UNDERSIZED. PROVIDE CORRECTION. THIS
 COMMENT WILL NOT HOLD UP THE FOUNDATION PERMIT, BUT
 NEEDS TO BE CORRECTED. NEC 310.15(B)(16)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-09-26 Cont ID  
Sent By jpearson Date 2017-09-26 Time 08:46 Rev Time 0.00
Received By jpearson Date 2017-09-26 Time 08:46 Sent To  
Notes
2017-09-26 08:46:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 THIS REVIEW FOR FOUNDATION PERMIT ONLY.
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, WIRE AND BREAKER SIZES FOR SERVICE.
 SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING
 TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94,
 408.30, 695.3; FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2018-01-29 Cont ID  
Sent By squinone Date 2018-01-29 Time   Rev Time 0.00
Received By squinone Date 2018-01-29 Time   Sent To  
Notes
2018-01-29 10:58:441. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED FROM THE FOLLOWING WEBSITE LINK: HTTP
 ://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-
 PERMITS-APPLICATIONS
  
 2. PLEASE SUBMIT THE LATEST VERSION OF THE 'AUTO-CALC
 CERTIFIED COST ESTIMATE FORM' FOR SUBMISSION TO CITY OF
 WEST PALM BEACH PUBLIC WORKS DEPARTMENT FOR ADDITIONAL
 WORK PROPOSED. THIS FORM CAN BE DOWNLOADED FROM THE
 FOLLOWING LINK: HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-
 PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 SOFIA QUINONES-BENEJAM, EI
 PROJECT ENGINEER
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33402
 (MAILING ADDRESS: PO BOX 3366)
 P: 561.494.1108
 C: 561.459.6518
 F: 561.494.1116
 EMAIL: [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2017-11-01 Cont ID  
Sent By squinone Date 2017-11-01 Time   Rev Time 0.00
Received By squinone Date 2017-10-31 Time   Sent To I
Notes
2017-11-01 12:58:01CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 PROJECT NAME: FORMER CITY HALL & HELEN WILKES SITE
 STATUS: FAILED
 DATE: NOVEMBER 1, 2017
  
 1) ADDRESS BUILDING AND ZONING COMMENTS.
  
 SOFIA QUINONES-BENEJAM, EI
 PROJECT ENGINEER
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33402
 (MAILING ADDRESS: PO BOX 3366)
 P: 561.494.1108
 C: 561.459.6518
 F: 561.494.1116
 EMAIL: [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-01-31 Cont ID  
Sent By pleduc Date 2018-01-31 Time   Rev Time 0.00
Received By pleduc Date 2018-01-30 Time 14:17 Sent To  
Notes
2018-01-30 16:11:57THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ONE OF THE THREE SUBMITTAL SETS DID NOT HAVE SHEET
 FP1.1.1 ATTACHED TO IT AS PER THE COMMENT RESPONSE # 1
 TO WESLEY JOLIN .
  
 IN AN EFFORT TO MOVE THIS PERMIT FORWARD TIS PROVISO IS
 BEING PROVIDED.
  
 THE SUBMITTAL SHEET HAS A HAD WRIITEN NOTE ON SHEET CVR
 - S INDICATING THE SAME.
  
 PLEASE ADD THIS SHEET.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-09-20 Cont ID  
Sent By wjolin Date 2017-09-20 Time 09:16 Rev Time 0.00
Received By wjolin Date 2017-09-20 Time 09:09 Sent To  
Notes
2017-09-20 09:16:04201 NORTH FLAGLER DRIVE - RESTAURANT
 PERMIT #17090199
 REVIEW COMMENTS - FIRE DEPARTMENT
 **RETAIL/RESTAURANT FOUNDATION ONLY**
  
 FIRE PROTECTION BACKFLOW PREVENTERS: PER NFPA 24
 SECTION 6.2.1, ALL CONNECTIONS TO PRIVATE FIRE SERVICE
 MAINS FOR FIRE PROTECTION SYSTEMS SHALL BE ARRANGED IN
 ACCORDANCE WITH ONE OF THE FOLLOWING SO THAT THEY CAN
 BE ISOLATED:
 (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH SECTION 6.4
 (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A
 BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 THE CITY OF WEST PALM BEACH REQUIRES CONSTRUCTION
 TRAILERS LARGER THAN A SINGLE "DOUBLE WIDE" (OR TWO
 "SINGLE WIDE") TO EITHER BE PROTECTED BY AN AUTOMATIC
 SPRINKLER SYSTEM OR COMPLY WITH THE SEPARATION
 REQUIREMENTS OF NFPA 241. TEMPORARY CONSTRUCTION
 TRAILERS OR MODULAR BUILDINGS WILL REQUIRE A PERMIT AND
 COMPLIANCE WITH THE FOLLOWING:
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2017-10-18 Cont ID  
Sent By gjohnson Date 2017-10-18 Time 17:53 Rev Time 0.00
Received By gjohnson Date 2017-10-18 Time 17:53 Sent To ENG
Notes
2017-10-18 17:55:05GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
  
 1ST REVIEW: FBC 2014 5TH EDITION
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-02-26 Cont ID  
Sent By shill Date 2018-02-26 Time 15:15 Rev Time 0.00
Received By shill Date 2018-01-25 Time 14:16 Sent To  
Notes
2018-01-26 14:16:19C29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-01 Cont ID  
Sent By cpuell Date 2017-11-01 Time 13:16 Rev Time 0.00
Received By cpuell Date 2017-09-07 Time 10:17 Sent To  
Notes
2017-09-15 10:17:28C20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2018-02-26 Cont ID  
Sent By shill Date 2018-02-26 Time 15:16 Rev Time 0.00
Received By shill Date 2018-02-26 Time 15:16 Sent To  
Notes
2018-02-26 15:16:44IMPACT FEES TO BE PAID ON BUILDING PERMIT, OK PER EMAIL
 FROM WILLIE SWOPE
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-02-14 Cont ID  
Sent By aclange Date 2018-02-14 Time 13:44 Rev Time 0.00
Received By aclange Date 2018-02-14 Time 13:44 Sent To  
Notes
2018-02-14 13:45:01****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED.
 THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING
 THAT FEES WERE PAID IS TO BE PROVIDED; 561-233-5025 FOR
 MORE INFORMATION .
  
 IT IS POSSIBLE THAT THE COUNTY WILL ALLOW FOR IMPACT
 FEES TO BE ASSESSED AT TIME OF VERTICAL BUILDING PERMIT
 UPON REQUEST. PLEASE ADVISE IF YOU WOULD LIKE FOR ME TO
 MAKE THIS REQUEST.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-09-25 Cont ID  
Sent By shill Date 2017-09-25 Time 16:29 Rev Time 0.00
Received By shill Date 2017-09-25 Time 16:29 Sent To  
Notes
2017-09-25 16:59:56****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED.
 THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING
 THAT FEES WERE PAID IS TO BE PROVIDED; 561-233-5025 FOR
 MORE INFORMATION .
  
 IT IS POSSIBLE THAT THE COUNTY WILL ALLOW FOR IMPACT
 FEES TO BE ASSESSED AT TIME OF VERTICAL BUILDING PERMIT
 UPON REQUEST. PLEASE ADVISE IF YOU WOULD LIKE FOR ME TO
 MAKE THIS REQUEST.
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2017-09-25 Cont ID  
Sent By shill Date 2017-09-25 Time 15:06 Rev Time 0.00
Received By shill Date 2017-09-25 Time 15:03 Sent To  
Notes
2017-09-25 15:18:12THIS PARCEL IS LOCATED IN SFHA A5 WITH A BFE OF 7.0'
 NGVD29. PROPOSED FFE IS 9.0' NGVD29.
  
 PROVISO:
  
 PRIOR TO CONCRETE POUR, A "BUILDING UNDER CONSTRUCTION"
 (FORM BOARD) ELEVATION CERTIFICATE IS REQUIRED.
  
 PRIOR TO FINAL INSPECTION, A "FINISHED CONSTRUCTION"
 ELEVATION CERTIFICATE IS REQUIRED. THE FINISHED
 CONSTRUCTION ELEVATION CERTIFICATE MAY BE SENT VIA
 EMAIL FOR PRELIMINARY REVIEW. A SIGNED AND SEALED
 ORIGINAL FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 TO BE SUBMITTED AT THE BUILDING DIVISION, REVIEWED AND
 APPROVED PRIOR TO FINAL INSPECTION. THIS SHOULD BE DONE
 AS EARLY AS POSSIBLE AFTER FINAL GRADE IS COMPLETE.
  
  
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2018-02-27 Cont ID  
Sent By gjohnson Date 2018-02-27 Time 16:28 Rev Time 0.00
Received By gjohnson Date 2018-02-27 Time 16:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-02-26 Cont ID  
Sent By gjohnson Date 2018-02-26 Time 14:53 Rev Time 0.00
Received By gjohnson Date 2018-02-26 Time 14:53 Sent To  
Notes
2018-02-26 14:54:22PROVISO: PERMIT # 17090199
 PLUMBING COMMENTS TO BE CORRECTED AND APPROVED REVISED
 PLAN SHEETS ON JOBSITE FOR FIRST ROUGH INSPECTION.
 1. THE SANITARY ISOMETRIC DOES NOT MATCH THE FLOOR PLAN
 IT SHOWS 2 SOIL STACKS NEAR THE ELEVATOR SUMP THAT ARE
 NOT SHOWN ON THE FLOOR PLAN PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
 2. THE FIRST TWO SECTIONS OF 8" PIPE ON THE STORM
 ISOMETRIC ARE UNDERSIZED THEY SHOULD BE 10". PER FBC PL
 TABLE 1006.3 1/8' PFT
 3. THE NEW SHEETS P3.2.1 AND P3.3.1 ARE MISSING FROM
 ONE OF THE PLAN SETS. PER WPB AMEND TO FBC 107.2.1
 4. IF THE GREASE INTERCEPTORS ARE TO BE APPROVED UNDER
 THIS PLAN SET PLEASE PROVIDE THE FOLLOWING.
 A) PROVIDE SIZING CALCULATIONS FROM SCHEIR
 MANUFACTURING FOR THE GREASE INTERCEPTORS. PER WPB
 AMEND TO FBC 107.2.1
 B) SHT. PF2.1.1 A DOUBLE SANITARY TEE CANNOT BE USED AS
 A SAMPLING PORT A PRE MANUFACTURED SAMPLING PORT OR A
 TWO WAY CLEANOUT CAN BE USED PER WPB UTILITIES DEPT.
 SEE STANDARD DETAIL GS 7 OR GS 7.1
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-02-13 Cont ID  
Sent By gjohnson Date 2018-02-13 Time 11:28 Rev Time 0.00
Received By gjohnson Date 2018-02-13 Time 08:09 Sent To  
Notes
2018-02-13 11:45:572ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE SANITARY ISOMETRIC DOES NOT MATCH THE FLOOR PLAN
 IT SHOWS 2 SOIL STACKS NEAR THE ELEVATOR SUMP THAT ARE
 NOT SHOWN ON THE FLOOR PLAN PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 2. THE FIRST TWO SECTIONS OF 8" PIPE ON THE STORM
 ISOMETRIC ARE UNDERSIZED THEY SHOULD BE 10". PER FBC PL
 TABLE 1006.3 1/8' PFT
  
 3. THE NEW SHEETS P3.2.1 AND P3.3.1 ARE MISSING FROM
 ONE OF THE PLAN SETS. PER WPB AMEND TO FBC 107.2.1
  
 4. IF THE GREASE INTERCEPTORS ARE TO BE APPROVED UNDER
 THIS PLAN SET PLEASE PROVIDE THE FOLLOWING.
  
 A) PROVIDE SIZING CALCULATIONS FROM SCHEIR
 MANUFACTURING FOR THE GREASE INTERCEPTORS. PER WPB
 AMEND TO FBC 107.2.1
  
 B) SHT. PF2.1.1 A DOUBLE SANITARY TEE CAN NOT BE USED
 AS A SAMPLING PORT A PRE MANUFACTURED SAMPLING PORT OR
 A TWO WAY CLEANOUT CAN BE USED PER WPB UTILITIES DEPT.
 SEE STANDARD DETAIL GS 7 OR GS 7.1
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-10-18 Cont ID  
Sent By gjohnson Date 2017-10-18 Time 17:55 Rev Time 0.00
Received By gjohnson Date 2017-10-18 Time 17:53 Sent To  
Notes
2017-10-18 17:53:331ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE A SANITARY COLLECTION ISOMETRIC DRAWING
 INCLUDING DFU LOAD. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 2. PROVIDE A STORM DRAIN COLLECTION ISOMETRIC DRAWING
 INCLUDING SQFT THAT IS BEING DRAINED. PER WPB AMEND TO
 FBC 107.3.5.1.3(13)
  
 3. PLEASE PLACE NOTE ON PLAN SEPARATE PERMITS ARE
 REQUIRED FOR DOMESTIC WATER BACKFLOW AND FIRE LINE
 BACKFLOW. PER WPB UTILITIES DEPT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2018-02-26 Cont ID  
Sent By shill Date 2018-02-26 Time 15:14 Rev Time 0.00
Received By shill Date 2018-02-26 Time 15:14 Sent To  
Notes
2018-02-26 15:15:08SHEETS S0.0.4, S0.0.5, S1.1.1 DIGITALLY SIGNED AND
 SEALED ROUTED TO RECORDS
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status P Date 2018-03-02 Cont ID  
Sent By aclange Date 2018-03-02 Time 16:06 Rev Time 0.00
Received By aclange Date 2018-02-27 Time 08:08 Sent To  
Notes
2018-03-02 16:07:40THRESHOLD AGREEMENT REVIEWED AND APPROVED. DELIVERED
 COPIES TO KEN CONRAD AND RICHARD GATHRIGHT.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2018-02-14 Cont ID  
Sent By aclange Date 2018-02-14 Time 13:42 Rev Time 0.00
Received By aclange Date 2018-02-14 Time 13:42 Sent To  
Notes
2018-02-14 13:43:17SEE BUILDING REVIEW NOTES.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2017-09-25 Cont ID  
Sent By shill Date 2017-09-25 Time 17:00 Rev Time 0.00
Received By shill Date 2017-09-25 Time 17:00 Sent To  
Notes
2017-09-25 17:00:40SEE BUILDING REVIEW
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-02-26 Cont ID  
Sent By AA Date 2018-02-26 Time 11:41 Rev Time 0.00
Received By aaponte Date 2018-02-26 Time 11:37 Sent To  
Notes
2018-02-26 11:57:35PROVISO: 1. A MINIMUM OF 8 FOOT WIDE SIDEWALK SHALL BE
 PROVIDED AROUND THE SITE (CONTINUOUS PATH OF TRAVEL).
  

Review Stop Z ZONING
Rev No 1 Status F Date 2017-10-17 Cont ID  
Sent By aaponte Date 2017-10-17 Time 15:22 Rev Time 0.00
Received By aaponte Date 2017-10-17 Time 15:22 Sent To  
Notes
2017-10-17 15:24:04FOR FOUNDATION PERMIT ONLY, PLEASE SUBMIT A CLEAR SITE
 PLAN WITH DIMENSIONS FOR SETBACKS TO CONFIRM COMPLIANCE
 WITH APPROVED SITE PLAN.