| 2017-09-13 14:18:18 | ****PLAN REVIEW COMMENTS**** |
| | |
| | ART LANGE - BUILDING INSPECTOR |
| | 561-805-6667 [email protected] |
| | FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA |
| | RESIDENTIAL CODE 2015 5TH EDITION |
| | SEE PLAN REVIEW COMMENTS BELOW: |
| | |
| | PROVIDE THE FOLLOWING INFORMATION FOR FLOORING |
| | SUBMITTALS: |
| | |
| | |
| | 1. PROVIDE SOUND PROOFING MATERIAL USED FOR LAMINATE |
| | AND CERAMIC TILE WITH THE FOLLOWING TEST REPORTS. |
| | |
| | 2. TEST REPORTS FOR PROPOSED UNDERLAYMENT BASED ON |
| | EXISTING SITE CONDITIONS. |
| | TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM?S, |
| | E-84, E-90 & E-492. |
| | FBC 603.1 FLAME SPREAD ? ASTM E-84-09 |
| | |
| | FBC 1207.2 AIR-BORNE SOUND. ASTM E - 90-04 |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-09 |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 3. EXISTING SITE CONDITIONS: PLEASE PROVIDE THE |
| | FOLLOWING INFORMATION. |
| | |
| | A) THICKNESS OF SLAB. B) CEILING ASSEMBLY (OPEN |
| | CONCRETE/SUSPENDED GYPSUM/ACOUSTICAL) |
| | |
| | 4. PLEASE SUBMIT TWO SETS OF ALL DOCUMENTS. |
| | |