Plan Review Details - Permit 17090153
Plan Review Stops For Permit 17090153
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-09-20 Cont ID  
Sent By shill Date 2017-09-20 Time 17:10 Rev Time 0.00
Received By shill Date 2017-09-20 Time 17:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-09-18 Cont ID  
Sent By jpearson Date 2017-09-18 Time 13:26 Rev Time 0.00
Received By jpearson Date 2017-09-18 Time 13:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-09-14 Cont ID  
Sent By scaldero Date 2017-09-14 Time 11:27 Rev Time 0.00
Received By scaldero Date 2017-09-14 Time 11:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-10-20 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-18 Time 15:02 Sent To  
Notes
2017-10-19 15:02:21RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-10-10 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-04 Time 14:44 Sent To  
Notes
2017-10-05 14:44:11RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-20 Cont ID  
Sent By shill Date 2017-09-20 Time 17:10 Rev Time 0.00
Received By shill Date 2017-09-06 Time 12:05 Sent To  
Notes
2017-09-07 12:05:59B03

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-10-20 Cont ID  
Sent By ccole Date 2017-10-20 Time 08:07 Rev Time 0.00
Received By ccole Date 2017-10-20 Time 07:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-10-10 Cont ID  
Sent By ccole Date 2017-10-10 Time 15:08 Rev Time 0.00
Received By ccole Date 2017-10-10 Time 15:08 Sent To  
Notes
2017-10-10 15:17:112ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17090153
 10/10/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M-1, M-2, & ST-1: THE PLANS DON'T CLEARLY
 INDICATE HOW THE FIRE DAMPERS IN THE LOBBY AND CORRIDOR
 WALLS WILL FUNCTION IN A FIRE OR SMOKE EVENT. PLEASE
 INCLUDE THEIR FUNCTIONS IN THE SMOKE CONTROL SEQUENCE
 OF OPERATION NARRATIVE ON ST-1. PLEASE NOTE THAT IF THE
 FIRE-RATED LOBBY AND CORRIDOR WALLS ARE ALSO SMOKE
 WALLS THEN THE DUCTS PENETRATING THE WALLS MUST BE
 PROTECED BY FIRE/SMOKE DAMPERS ( THE CURRENT PLAN IS
 INDICATING FIRE DAMPERS AT THE LOBBY/MECH RM WALL AND
 THE CORRIDOR/MEN'S BATH WALL). IN ADDITION PLEASE SEE
 SECTIONS 607.5.2 AND 607.5.7 WHICH EACH LIST EXCEPTIONS
 FOR FIRE AND SMOKE DAMPERS FOR FOR DUCTS THAT ARE PART
 OF A SMOKE CONTROL SYSTEM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-09-19 Cont ID  
Sent By ccole Date 2017-09-19 Time 08:26 Rev Time 0.00
Received By ccole Date 2017-09-18 Time 17:21 Sent To  
Notes
2017-09-19 09:20:541ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17090153
 9/19/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A LIFE SAFETY PLAN THAT IDENTIFIES THE
 LOCATIONS OF ALL NEW OR EXISTING FIRE-RATED WALLS AND
 ASSEMBLIES, AND THE TYPES AND HOURLY RATINGS OF EACH.
 IF THE MEN'S BATHROOM/CORRIDOR WALL AND THE MECHANICAL
 EQUIPMENT ROOM WALL ARE FIRE/SMOKE BARRIERS THEN THE
 DUCTS PENETRATING THEM SHALL BE PROTECTED BY FIRE/SMOKE
 DAMPERS THAT ARE LISTED AND LABELED IN ACDCORDANCE WITH
 UL 555 AND 555S- SECTION 607.3.1.
  
 2) SHEET ST-1: THE PLAN INDICATES THE BUILDING HAS AN
 EXISTING SMOKE CONTROL/SMOKE EXHAUST SYSTEM. CLARIFY IF
 THERE IS AN EXISTING RATIONAL ANALYSIS REPORT THAT
 DETAILS THE DESIGN OF THE SYSTEM, AND THE INSTALLATION
 AND ACCEPTANCE TESTING PROCEDURES. THE PROPOSED
 ALTERATIONS TO THE SYSTEM MUST BE IN COMPLIANCE WITH
 THE ORIGINAL DESIGN OR A NEW RATIONAL ANALYSIS SHALL BE
 SUBMITTED. PLEASE NOTE THAT ALL NEW DUCTS AND DAMPERS
 THAT ARE PART OF THE SYSTEM SHALL BE IN COMPLIANCE WITH
 SECTION 513.10.2. PLEASE ADD DUCT LEAK TESTING TO THE
 SMOKE TEST PROCEDURE.
  
 3) ST-1: PLEASE ENLARGE THE PRINT IDENTIFYING MOTORIZED
 DAMPERS #1 & 2 AND PROVIDE EQUIPMENT SCHEDULES ON THE
 PLAN FOR EACH. PLEASE NOTE THAT THESE DAMPERS SHALL BE
 LISTED AND LABELED FOR THEIR INTENDED USE IN ACCORDANCE
 WITH SECTION 513.10.4.
  
 4) ST-1: PROVIDE EQUIPMENT SCHEDULES ON THE PLANS FOR
 THE SMOKE EXHAUST AND SUPPLY FANS. THE SMOKE EXHAUST
 FAN SHALL BE RATED CERTIFIED BY THE MANUFACTURER FOR
 THE PROBABLE TEMPERATURE RISE PER SECTION 513.10.1 AND
 AND SHALL BE UL LISTED AND LABELED FOR IT'S INTENDED
 USE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  