| 2017-09-13 13:41:55 | ****PLAN REVIEW COMMENTS**** |
| | |
| | ART LANGE - BUILDING INSPECTOR |
| | 561-805-6667 [email protected] |
| | FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA |
| | RESIDENTIAL CODE 2015 5TH EDITION |
| | |
| | SEE PLAN REVIEW COMMENTS BELOW: |
| | |
| | PROVIDE THE FOLLOWING INFORMATION FOR FLOORING |
| | SUBMITTALS: |
| | |
| | 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK. |
| | *DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC 107 * |
| | 2. TYPE OF PROPOSED FLOORING |
| | (TILE/MARBLE/LAMINATE/WOOD/OTHER). |
| | 3. STATED VALUE OF WORK SHALL INCLUDE MATERIALS AND |
| | LABOR. ADJUST PERMITTED VALUE OF WORK. |
| | 109.3 BUILDING PERMIT VALUATIONS. |
| | THE APPLICANT FOR A PERMIT SHALL PROVIDE AN ESTIMATED |
| | PERMIT VALUE AT TIME OF APPLICATION. PERMIT VALUATIONS |
| | SHALL INCLUDE TOTAL VALUE OF WORK, INCLUDING MATERIALS |
| | AND LABOR, FOR WHICH THE PERMIT IS BEING ISSUED, SUCH |
| | AS ELECTRICAL, GAS, MECHANICAL, PLUMBING EQUIPMENT AND |
| | PERMANENT SYSTEMS. IF, IN THE OPINION OF THE BUILDING |
| | OFFICIAL, THE VALUATION IS UNDERESTIMATED ON THE |
| | APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE |
| | APPLICANT CAN SHOW DETAILED ESTIMATES TO MEET THE |
| | APPROVAL OF THE BUILDING OFFICIAL. FINAL BUILDING |
| | PERMIT VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | 4. EXISTING SITE CONDITIONS: |
| | A) THICKNESS OF SLAB. B) CEILING ASSEMBLY (OPEN |
| | CONCRETE/SUSPENDED GYPSUM/ACOUSTICAL) |
| | 5. PROPOSED UNDERLAYMENT. |
| | 6. TEST REPORTS FOR PROPOSED UNDERLAYMENT BASED ON |
| | EXISTING SITE CONDITIONS. |
| | 7. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM?S, |
| | E-84, E-90 & E-492. |
| | FBC 603.1 FLAME SPREAD ? ASTM E-84-09 |
| | |
| | FBC 1207.2 AIR-BORNE SOUND. ASTM E - 90-04 |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-09 |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 8. PLEASE SUBMIT TWO SETS OF ALL DOCUMENTS. |
| | |