Plan Review Details - Permit 17090120
Plan Review Stops For Permit 17090120
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-11-15 Cont ID  
Sent By jwitmer Date 2017-11-15 Time 07:46 Rev Time 0.00
Received By aclange Date 2017-11-15 Time 07:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-02 Cont ID  
Sent By jwitmer Date 2017-10-02 Time   Rev Time  
Received By jwitmer Date 2017-10-02 Time 06:15 Sent To  
Notes
2017-10-02 09:20:532014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17090120
 W. P. B. PERMIT: 16050912
 ADD: 1451 S. OLIVE AVE.
 CONT: GILBANE
 TEL: 561-758-0437
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. OCT. 02/2017
 ACTION: DENIED
  
 1) SHEET 0100_A103 LEVEL 3 AND 0113_A123.8 LEVEL 3.8.
 THE DOORS BETWEEN CORRIDOR 301 AND GALLERY 304. THESE
 DOORS HAVE BEEN REVERSED AGAINST THE EGRESS FLOW. 2014
 1008.1.2 DOOR SWING. DOORS SHALL SWING IN THE DIRECTION
 OF EGRESS TRAVEL WHERE SERVING A ROOM OR AREA
 CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS.
 THERE IS A SAME OCCUPANT LOAD SERVED ON THE 2ND FLOOR
 LEVEL, IF NOT MORE AND THOSE DOORS WERE NOT REVERSED.
 THE ORIGINAL CONCEPT IN PRE-CONSTRUCTION MEETINGS HAD
 UNENCLOSED EXIT ACCESS STAIR CONCEPT 3-19-2015,
 6-09-2015 & 11-18-2015.
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2) SHEET 0097_A101 & 0189_A617 VESTIBULE 124 LEADS INTO
 EXIT STAIR B143. IF THIS ROOM (VESTIBULE 124) IS TRULY
 BEING DESIGNED AS A VESTIBULE TO THE VERTICAL EXIT B143
 IT CANNOT BE USED FOR ANY OTHER PURPOSE OTHER THAN TO
 GAIN ENTRY INTO THE VERTICAL EXIT STAIR AND WILL NEED
 TO MEET THE REQUIREMENTS FOUND IN FBC-B 909.20. THE
 DESIGNER CAN DESIGN TO A STRICTER STANDARD THAN THE
 MINIMUM CODE. IF THE VESTIBULE IS FOR EXITING THEN ALSO
 REVIEW 1014.2 EGRESS THROUGH INTERVENING SPACES.(4) 4.
 EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE ROOMS,
 CLOSETS OR SPACES USED FOR SIMILAR PURPOSES. THE DOOR
 INTO THE VERTICAL STAIR WOULD MAKE THE EXIT A HANDY
 PLACE TO STORE THINGS IF THE ROOM IS NOT A VESTIBULE,
 RENAME AND REMOVE THE DOOR INTO THE VERTICAL EXIT.
 DOORS INTO VERTICAL EXITS ARE ONLY TO BE USED AS ENTRY
 DOORS FROM HABITABLE/ OCCUPIED SPACES.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-11-14 Cont ID  
Sent By jpearson Date 2017-11-14 Time 13:34 Rev Time 0.00
Received By jpearson Date 2017-11-14 Time 13:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-10-11 Cont ID  
Sent By jpearson Date 2017-10-11 Time 16:10 Rev Time 0.00
Received By jpearson Date 2017-10-11 Time 16:05 Sent To  
Notes
2017-10-11 16:05:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN CHANGES ARE NOT IDENTIFIED CLEARLY. IT APPEARS
 THAT SOME SYMBOLS ARE MISSING ON SOME PAGES. PROVIDE
 CORRECTION AND CLEARLY IDENTIFY ANY REVISIONS WITH
 CLOUD. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-11-07 Cont ID  
Sent By pleduc Date 2017-11-07 Time   Rev Time 0.00
Received By pleduc Date 2017-11-07 Time 09:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-10-02 Cont ID  
Sent By pleduc Date 2017-10-02 Time   Rev Time 0.00
Received By pleduc Date 2017-10-02 Time 12:16 Sent To  
Notes
2017-10-02 13:01:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A - IT APPEARS THAT DOOR 301A IS SWINGING IN
 THE OPPISTE DIRECTION FROM PREVIOISLY APPROVED DRAWING.
  
 THE RESUBMISSION SUMMARY DOES NOT ADDRESS THESE DOORS,
 NOR DOES ANY OTHER REVISION SUBMITTAL THAT I COULD
 IDENTIFY.
  
 PLEASE REVIEW AND ENSURE THAT THIS IS NOT JUST A
 MISPRINT.
  
 THESE DOORS ARE REQUIRED TO SWING IN THE DIRECTION OF
 EGRESS AND AS APPROVED THROUGH THE MASTER PERMIT #
 16050912.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-15 Cont ID  
Sent By cpuell Date 2017-11-15 Time 15:45 Rev Time 0.00
Received By cpuell Date 2017-11-02 Time 16:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-16 Cont ID  
Sent By cpuell Date 2017-10-16 Time 16:41 Rev Time 0.00
Received By cpuell Date 2017-09-25 Time 09:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-11-15 Cont ID  
Sent By ccole Date 2017-11-15 Time 12:02 Rev Time 0.00
Received By ccole Date 2017-11-14 Time 17:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-10-13 Cont ID  
Sent By ccole Date 2017-10-13 Time 11:40 Rev Time 0.00
Received By ccole Date 2017-10-12 Time 12:32 Sent To  
Notes
2017-10-13 12:06:441ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17090120
 10/13/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M101 & M121.8: THE REVISED PLANS UNDER PERMIT
 #17080449 WERE APPROVED WITH A PROVISO THAT REVISED
 VENTILATION AND AIR BALANCE CALCULATIONS FOR THE
 ALTERED KITCHEN SYSTEMS WOULD BE PROVIDED. PLEASE
 PROVIDE THE CALCULATIONS AND A REVISED KITCHEN
 EQUIPMENT LAYOUT AND EQUIPMENT SCHEDULE. SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR ALL GAS-FIRED COOKING
 APPLIANCES AND PROVIDE COMBUSTION AIR CALCULATIONS.
 PLEASE NOTE THE FOLLOWING: A) SEPARATE PERMITS ARE
 REQUIRED FOR HOOD EXHAUST AND FIRE SUPPRESSION SYSTEMS.
 B) REFER TO SECTION 508.1.1 FOR MAKEUP AIR TEMPERATURE
 REQUIREMENT.
  
 2) M121.5, ITEM #3 IN THE NARRATIVE: PLEASE SHOW THE
 LOCATIONS OF GALLERIES 135 & 137 ON THE PLAN.
  
 3) M121.7, ITEM #2 IN THE NARRATIVE: PLEASE SHOW THE
 LOCATIONS OF GALLERIES 135 & 137 ON THE PLAN.
  
 4) M122.5: PROVIDE DUCT SIZES ON THE PLANS.
  
 5) M122.8: THERE ARE MISSING FS DAMPER SYMBOLS FOR THE
 DUCTS IN THE SHAFT BY THE ELEVATOR.
  
 6) M123.8B: IT APPEARS THE WATER HEATER FLUE AND INTAKE
 DUCT ARE NOW BEING ROUTED TO THE ROOF, HOWEVWER THE
 NOTES ON THE PLAN ARE STILL INDICATING SIDEWALL
 TERMINATIONS- PLEASE CORRECT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2017-10-16 Cont ID  
Sent By jroach Date 2017-10-16 Time 16:31 Rev Time 0.00
Received By jroach Date 2017-10-16 Time 16:31 Sent To  
Notes
***NONE***