| 2017-09-06 14:34:10 | REVIEW CHECKLIST FOR RESIDENTIAL (R3) REVISION |
| | ADDRESSING BUILDING REVIEW PROVISO. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | |
| | 1- ENERGY CALCULATIONS SUBMITTED: |
| | A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | B) IT LOOKS LIKE THE ENERGY CALCULATIONS ARE DONE FOR |
| | THE ENTIRE HOUSE (1231 S.F.). IF DOING THE CALCULATIONS |
| | FOR THE ENTIRE HOUSE, THEN CLARIFY WHY THERE IS NOT |
| | KITCHEN SHOWN ON PAGE 2 OF 4. ALSO, CLARIFY WHY THERE |
| | IS ONLY ONE BEDROOM AND ONE PERSON SHOWN ON PAGE 2 OF |
| | 4. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH |
| | EDITION (2014). |
| | |
| | C) INSULATION R-VALUE FOR WOOD FRAMED WALL ON ITEM |
| | #9(B) DOESN'T MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | D) CEILING INSULATION R-VALUE ON ITEM #10 DOESN'T MATCH |
| | ARCHITECT'S PLANS. NOTE: INCLUDE THE NEW MASTER BEDROOM |
| | AREA AND NEW LEISURE ROOM AREA AND EXISTING HOUSE |
| | CEILING INSULATION. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | E) ITEM #10 SPECIFIES UNVENTED DECK. PERSON PREPARING |
| | THE ENERGY CALCULATIONS TO PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS SHOWING COMPLIANCE WITH THE UNVENTED |
| | ROOF AS REQUIRED BY SEC. R806.5 FBC-RESIDENTIAL, 5TH |
| | EDITION. |
| | NOTE: HOUSE WAS BUILT IN 1953. TYPICALLY ROOFS WERE |
| | VENTED. PROVIDE PROOF THAT ROOF IS NOT VENTED. |
| | |
| | F)ROOF TYPE IS MISSING THE GABLE AREA BY THE NEW MASTER |
| | BEDROOM AND THE FLAT ROOF BY THE NEW LEISURE ROOM. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | G) WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4 DOESN'T |
| | MATCH ARCHITECTURAL PLANS. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION. REVISE WINDOWS SQUARE FOOTAGE AND |
| | ORIENTATION. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | H) DOORS INFORMATION SHOWN ON PAGE 3 OF 4 DON'T MATCH |
| | ARCHITECTURAL PLANS. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION. WHERE ARE THE WOOD DOORS. ALSO, REVISE |
| | THE DOOR ORIENTATION TO MATCH PLANS. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | I) CONTRACTOR TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| | (EPL) DISPLAY CARD. |
| | |
| | 2- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR THE SWING DOOR. NOTE: NOA 15-0602.06 |
| | SUBMITTED IS FOR THE MASTER BEDROOM WINDOW. NEED |
| | PRODUCT APPROVAL FOR THE LEISURE ROOM EXTERIOR DOOR. |
| | |
| | 3- ARCHITECT TO APPROVE ABOVE PRODUCT APPROVAL. SEC. |
| | 107.3.4.1 CITY AMENDMENTS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | |