| 2017-09-29 16:52:21 | ****CORRECTIONS**** |
| | |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | FBC A FAIR HOUSING CHAPTER, THIS PROJECT IS SUBJECT TO |
| | FAIR HOUSING REQUIREMENTS. |
| | |
| | 1. SHEET A2-90-15B. REVISE PLAN TO CLARIFY CLEAR |
| | OPENING WIDTH FOR THE NEW DOORS. FAIR HOUSING REQUIRES |
| | A CLEAR WIDTH OF 32 INCHES. 2014 FBC- ACCESSIBILITY/ |
| | FAIR HOUSING SECTION 100.205.(C)(2)(2). |
| | |
| | FOR POCKET DOORS - IF THE CLEAR OPENING WIDTH IS 32" OR |
| | LESS WITH THE DOOR IN THE FULLY RECESSED POSITION, IT |
| | APPEARS THAT THIS DOES NOT PROVIDE SOMEONE WHO NEEDS |
| | ACCESSIBLE HARDWARE THE ABILITY TO USE THE DOOR AND |
| | MAINTAIN THE 32" CLEARANCE (SEE USABLE DOORS, FIGURE |
| | 1). IF SUCH HARDWARE IS AVAILABLE AND USABLE WITH THE |
| | DOOR IN THE FULLY OPEN POSITION, PLEASE SEND |
| | INFORMATION VIA EMAIL FOR PRELIMINARY REVIEW. |
| | |
| | PER BUILDING OFFICIAL: IF A POCKET DOOR CAN BE |
| | RETROFITTED WITH A SWING DOOR WHICH COMPLIES WITH THE |
| | 32" CLEARANCE, AND A SWING DOOR CAN BE INSTALLED IN THE |
| | FUTURE IN THAT LOCATION (ENOUGH SPACE), THAT OPTION |
| | WOULD BE ACCEPTED. THE INTENT IS THAT AN OCCUPANT HAS |
| | AN ACCESSIBLE ROUTE THROUGHOUT THE UNIT WITHOUT MAJOR |
| | CONSTRUCTION (MOVING WALLS, REFRAMING DOOR OPENINGS). |
| | IF A POCKET DOOR CAN BE ADAPTED WITH A DOOR CHANGE, |
| | THAT IS ACCEPTABLE. IF YOU WISH TO DISCUSS, PLEASE FEEL |
| | FREE TO CONTACT ME. |
| | |
| | IT APPEARS THAT THE DOORS AT THE SHOE CLOSET AND CLOSET |
| | MEET THE 32" CLEARANCE REQUIREMENT, BUT DOOR U05V |
| | APPEARS TO BE 32". |
| | |
| | 2. PROVIDE THE FOLLOWING TEST REPORTS FOR THE FLOORING |
| | UNDERLAYMENT: |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | |