Plan Review Details - Permit 17090013
Plan Review Stops For Permit 17090013
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-10-10 Cont ID  
Sent By ccole Date 2017-10-10 Time 14:20 Rev Time 0.00
Received By ccole Date 2017-10-10 Time 14:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-09-01 Cont ID  
Sent By ccole Date 2017-09-01 Time 16:05 Rev Time 0.00
Received By ccole Date 2017-09-01 Time 16:05 Sent To  
Notes
2017-09-01 16:19:571ST REVIEW FBC-2014 BUILDING
 PERMIT #17090013
 9/1/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED ENGINEERING FROM FEDERAL ENGINEERING &
 TESTING INDICATES A 4' PARAPET ON THE BUILDING WHICH
 ALLOWS ZONE 3 (CORNERS) TO BE TREATED AS ZONE 2 (
 PERIMETER) IN TERMS OF FASTENER DENSITIES, HOWEVER THE
 BUILDING DOES NOT HAVE A PARAPET SO THE THE FASTENER
 DENSITIES SHALL BE INCREASED FOR THE CORNERS. PLEASE
 PROVIDE CORRECTED ENGINEERING.
  
 2) PLEASE INDICATE IN THE NOA WHICH OF THE THREE TPO
 SYSTEMS WILL BE INSTALLED.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-10-10 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-06 Time 11:28 Sent To  
Notes
2017-10-10 11:28:36RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-09-01 Time   Rev Time 0.00
Received By lmarchan Date 2017-09-01 Time 12:09 Sent To  
Notes
2017-09-01 12:09:18CCOLE