Plan Review Details - Permit 17090002
Plan Review Stops For Permit 17090002
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-11-22 Cont ID  
Sent By skennedy Date 2017-11-22 Time 15:44 Rev Time 0.00
Received By skennedy Date 2017-11-22 Time 15:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-17 Cont ID  
Sent By cthroop Date 2017-10-17 Time 11:36 Rev Time 0.00
Received By cthroop Date 2017-10-17 Time 09:59 Sent To M
Notes
2017-10-17 11:54:50BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. OWNER/AGENT TO SIGN ENERGY SUBMITTAL.
 2. PROVIDE ICYNENE ICC/ES REPORT FOR PROPOSED
 INSULATION. INDICATE WHICH PRODUCT WILL BE INSTALLED.
 PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS AT TIME
 OF INSPECTION PER ES REPORT REQUIREMENTS.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-11-15 Cont ID  
Sent By jpearson Date 2017-11-15 Time 11:24 Rev Time 0.00
Received By jpearson Date 2017-11-15 Time 11:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-09-26 Cont ID  
Sent By jpearson Date 2017-09-26 Time 11:19 Rev Time 0.00
Received By jpearson Date 2017-09-26 Time 11:19 Sent To  
Notes
2017-09-26 11:19:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. NEC 210.63; FBC RE3901.12
 2. LIGHTING IN MASTER CLOSETS SHOWS STANDARD RECESS
 LIGHTS. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS". PROVIDE
 CORRECTION. NEC 410.16; FBC RE4003.12
 3. PANEL SCHEDULE SHOWS A 50 AMP BREAKER FOR THE NEW
 AHU AND A 30 AMP BREAKER FOR THE NEW CU. SPECS ON THE
 MECHANICAL SHEETS REQUIRE A 30 AMP BREAKER FOR THE AHU
 AND A 25 AMP BREAKER FOR THE CU. PROVIDE CORRECTION.
 THE BRANCH CIRCUIT OVERCURRENT PROTECTION DEVICE RATING
 SHALL BE THE SIZE AND TYPE MARKED ON THE EQUIPMENT. NEC
 440.22(C); FBC RE3702.11
 4. PROVIDE PANEL SCHEDULE FOR PANEL A, INDICATING ANY
 NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR
 THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12,
 215.5, 408.4; FBC RE3706.2, RE3902
 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
 6. A GFCI PROTECTED OUTLET ON A 20 AMP CIRCUIT IS
 REQUIRED WITHIN 3 FEET OF EACH BASIN IN MASTER BATH.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE
 3703.4, 3901.6
 7. PROVIDE COMPLIANCE: ALL 120-VOLT, SINGLE PHASE, 15
 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN
 DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS
 OR ROOMS, SHALL HAVE AFCI PROTECTION. A NOTE WILL
 SUFFICE. NEC 210.12; FBC RE3902.12
 8. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC CE R404.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-11-21 Cont ID  
Sent By tklarge Date 2017-11-21 Time 12:46 Rev Time 0.00
Received By tklarge Date 2017-11-21 Time 12:45 Sent To  
Notes
2017-11-21 12:47:14A SEPARATE PERMIT IS REQUIRED FOR THE GAS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-09-29 Cont ID  
Sent By lcrespo Date 2017-09-29 Time 15:50 Rev Time 0.00
Received By lcrespo Date 2017-09-29 Time 15:50 Sent To  
Notes
2017-09-29 15:56:14FAILED 9/29/17 LAC
  
 1. NEED SEPARATE PERMIT FOR GAS IS REQUIRED FBC A 105.3
  
 2. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1.
  
 3. INDICATE ON BOTH GAS DRAWINGS HOW THE PIPING THOUGH
 THE EXTERIOR WILL BE PROTECTED. WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1.
  
 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH FBC-2014 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2014 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1.
  
 5. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS
 APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. FGC
 SEC.304.9.3 OR FBCR G2407.9.3.
  
 6. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3.
  
 7. THE BTU LOAD OF THE GAS SYSTEM MUST BE ADDED INTO
 THE TOTAL BTU LOAD ON THE FUTURE GAS SYSTEM TO ENSURE
 THE EXISTING SYSTEM IS PROPERLY SIZED. THE LOAD OF THE
 FUTURE RANGE IN NOT CALCULATED ON THE GAS PIPING
 ISOMETRIC PAGE P-1. IF UNDERSIZED, THE EXISTING SYSTEM
 MUST BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. FGC
 SEC. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 8. NEED A SHUTOFF VALVE AND HARD CAP FOR FUTURE RANGE
 SHOW ON GAS ISOMERIC P-1 APPLIANCE SHUTOFF IFGC 409.5,
 APPLIANCE CONNECTION IFGC 404.15, 411.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-09-07 Cont ID  
Sent By fmittner Date 2017-09-07 Time 14:06 Rev Time 0.00
Received By fmittner Date 2017-09-07 Time 14:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-22 Cont ID  
Sent By skennedy Date 2017-11-22 Time 15:45 Rev Time 0.00
Received By skennedy Date 2017-10-24 Time 13:26 Sent To  
Notes
2017-10-26 13:26:31R36

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-18 Cont ID  
Sent By hmoser Date 2017-10-18 Time 15:11 Rev Time 0.00
Received By hmoser Date 2017-09-01 Time 13:01 Sent To  
Notes
2017-09-05 13:01:12R36

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2017-12-08 Cont ID  
Sent By jgomez Date 2017-12-08 Time 11:13 Rev Time 0.00
Received By jgomez Date 2017-12-08 Time 11:11 Sent To  
Notes
2017-12-08 11:13:49$236.59 PAID. MU-2017-032597.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-11-28 Cont ID  
Sent By shill Date 2017-11-22 Time 08:56 Rev Time 0.00
Received By shill Date 2017-11-22 Time 08:56 Sent To  
Notes
2017-11-28 08:57:22BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-10-17 Cont ID  
Sent By cthroop Date 2017-10-17 Time 11:35 Rev Time 0.00
Received By cthroop Date 2017-10-17 Time 09:59 Sent To  
Notes
2017-10-17 11:36:30BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-11-22 Cont ID  
Sent By skennedy Date 2017-11-22 Time 15:34 Rev Time 0.00
Received By skennedy Date 2017-11-22 Time 15:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-10-18 Cont ID  
Sent By hmoser Date 2017-10-18 Time 15:11 Rev Time 0.00
Received By hmoser Date 2017-10-18 Time 14:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-11-21 Cont ID  
Sent By tklarge Date 2017-11-21 Time 12:45 Rev Time 0.00
Received By tklarge Date 2017-11-21 Time 11:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-09-29 Cont ID  
Sent By lcrespo Date 2017-09-29 Time 15:46 Rev Time 0.00
Received By lcrespo Date 2017-09-29 Time 15:46 Sent To  
Notes
2017-09-29 15:47:30DENIED 9/29/17 LAC
  
 1. THE SHOWER IS SIZED AS A 3? PER CODE A 2? IS THE
 MINIMUM, HOW MANY DFU?S (GPM) IS THE SHOWER HEAD TO
 DRAIN TO THE SHOWER. FBC P3004.1, P3201.7
  
 2. PLANS CALL FOR A STEAM SHOWER PLEASE PROVIDE
 LOCATION AND SPECIFICATION FOR STEAM GENERATOR, PLEASE
 PROVIDE MANUFACTURE SPECIFICATION. IF THE STEAM UNIT IS
 UNDER A THE SHOWER SEAT. HOW IS THE STEAM ENTERING THE
 SHOWER? PLEASE CLARIFY WHAT TYPE OF PROTECTION IS BEING
 USED AND SHOW WHERE IT GOING IN THE SHOWER. FBC
 AMENDMENTS 107.2.1A-2
  
 3. SHOWER PAN IS NOT RECEDED IT WILL REQUIRE LINING FBC
 P2709.2
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2017-10-17 Cont ID  
Sent By cthroop Date 2017-10-17 Time 11:35 Rev Time 0.00
Received By cthroop Date 2017-10-17 Time 10:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-09-07 Cont ID  
Sent By fmittner Date 2017-09-07 Time 14:06 Rev Time 0.00
Received By fmittner Date 2017-09-07 Time 14:06 Sent To  
Notes
***NONE***