Plan Review Details - Permit 17081494
Plan Review Stops For Permit 17081494
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-09-26 Cont ID  
Sent By jwitmer Date 2017-09-26 Time 06:31 Rev Time 0.00
Received By jwitmer Date 2017-09-26 Time 06:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-09-11 Cont ID  
Sent By jleahy Date 2017-09-11 Time 11:41 Rev Time 0.00
Received By jpearson Date 2017-09-11 Time 11:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2017-09-26 Cont ID  
Sent By   Date 2017-09-26 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-31 Time 11:23 Sent To  
Notes
2017-09-01 11:23:45C18

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-01-16 Cont ID  
Sent By ccole Date 2018-01-16 Time 11:02 Rev Time 0.00
Received By ccole Date 2018-01-16 Time 11:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-09-13 Cont ID  
Sent By ccole Date 2017-09-13 Time 11:57 Rev Time 0.00
Received By ccole Date 2017-09-13 Time 11:34 Sent To  
Notes
2017-09-13 12:04:291ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17081494
 9/13/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE CITY OF WPB CSD REQUIRES A SEPARATE PERMIT FOR
 REFRIGERATION WORK- SECTION 107.2.1.4 WPB AMENDMENTS TO
 THE FBC. PLEASE PROVIDE A COMPLETE SET OF PLANS AND
 SUBMITTALS UNDER SEPARATE PERMIT, OR REVISE THE
 APPROVED REFRIGERATION PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2018-01-16 Cont ID  
Sent By skennedy Date 2018-01-16 Time 11:10 Rev Time 0.00
Received By skennedy Date 2018-01-16 Time 11:10 Sent To  
Notes
2018-01-16 11:14:03SUB PERMIT HAS BEEN INSPECTEDAND PASSED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-09-20 Cont ID  
Sent By gjohnson Date 2017-09-20 Time 09:09 Rev Time 0.00
Received By tklarge Date 2017-09-20 Time 08:41 Sent To  
Notes
2017-09-20 09:09:411) SHT. P1 REFERS TO DETAILS LOCATED ON SHT. P2 BUT
 THERE IS NO P2 SHEET IN THE SET OF PLANS. SUBMIT SHT.
 P2 FOR REVIEW. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SUBMIT A NARRATIVE THAT CLEARLY DESCRIBES THE
 CHANGES BEING MADE TO THE PLUMBING SYSTEM. WPB AMEND.
 TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  