Plan Review Details - Permit 17081436
Plan Review Stops For Permit 17081436
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-11-30 Cont ID  
Sent By aclange Date 2017-11-30 Time 13:28 Rev Time 0.00
Received By aclange Date 2017-11-30 Time 13:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-11-21 Cont ID  
Sent By aclange Date 2017-11-21 Time 10:47 Rev Time 0.00
Received By aclange Date 2017-11-21 Time 09:58 Sent To E
Notes
2017-11-21 10:47:43****PLAN REVIEW COMMENTS****
  
 ART LANGE - BUILDING INSPECTOR
 561-805-6667 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA
 RESIDENTIAL CODE 2015 5TH EDITION
  
 SECOND REVIEW:
  
 EXISTING COMMENTS NOT ADDRESSED:
  
 1. BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
 2. PROVIDE TWO COMPLETE SETS OF PRODUCT APPROVALS.
 FBC 107.3.4 , FBC 107.1 - PROVIDE PRODUCT APPROVALS FOR
 THOSE PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD. SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR
 SUBMITTALS.
  
 NOTE: PRODUCT APPROVALS INCLUDED ON DOOR AND WINDOW
 SCHEDULE ARE NOW STAMPED VOID.
  
 OK - 3. DOORS AND WINDOWS ON SCHEDULE ARE NOT SHOWN ON
 THE FLOOR PLAN.
  
 OK - 4. ACCORDIAN SHUTTER SCHEDULE DOES NOT HAVE
 SHUTTERS LISTED. THERE IS A NOA FOR WINDOWS LISTED
 HERE. NOA?S PROVIDED ARE FOR IMPACT PRODUCTS. PLEASE
 CONFIRM.
  
 OK - 5. PROVIDE SIZE OF EXISTING BEDROOM WINDOW TO
 CONFIRM THAT IT MEETS THE REQUIREMENTS OF A EMERGENCY
 ESCAPE RESCUE OPENING. R310.1
  
 OK - 6. EXISTING BEAM BEING CONVERTED INTO A TIE BEAM
 CREATES A FEW CONCERNS.
  
 OK - A. BY ENCASING THE EXISTING 2 X 8 IN CONCRETE
 CREATES ISSUES WITH WOOD DECAY. R317
  
 OK - B. THE 4 - #5 BARS WILL NOT HAVE REQUIRED
 COVERAGE. R611.5.4.1 R611.5.4.2
  
 OK - C. ARE LINTELS USED OVER OPENINGS. PROVIDE A
 SCHEDULE. R611.8.2
  
 OK - D. VERTICAL BARS APPEAR TO BE GOING INTO EXISTING
 BEAM. HOOK BARS ARE NOT SHOWN. PROVIDE A DETAIL.
 FBC107.2.1
  
 OK - 7. FIELD VERIFY THAT THERE IS AN EXISTING FOOTING
 AND PROVIDE THE SIZE. FBC107.3
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-09-15 Cont ID  
Sent By aclange Date 2017-09-15 Time 15:51 Rev Time 0.00
Received By aclange Date 2017-09-15 Time 14:32 Sent To  
Notes
2017-09-15 15:52:43****PLAN REVIEW COMMENTS****
  
 ART LANGE - BUILDING INSPECTOR
 561-805-6667 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA
 RESIDENTIAL CODE 2015 5TH EDITION
  
 1. BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
 2. PROVIDE TWO COMPLETE SETS OF PRODUCT APPROVALS.
 FBC 107.3.4 , FBC 107.1 - PROVIDE PRODUCT APPROVALS FOR
 THOSE PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD. SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR
 SUBMITTALS.
  
 3. DOORS AND WINDOWS ON SCHEDULE ARE NOT SHOWN ON THE
 FLOOR PLAN.
  
 4. ACCORDIAN SHUTTER SCHEDULE DOES NOT HAVE SHUTTERS
 LISTED. THERE IS A NOA FOR WINDOWS LISTED HERE. NOA?S
 PROVIDED ARE FOR IMPACT PRODUCTS. PLEASE CONFIRM.
  
 5. PROVIDE SIZE OF EXISTING BEDROOM WINDOW TO CONFIRM
 THAT IT MEETS THE REQUIREMENTS OF A EMERGENCY ESCAPE
 RESCUE OPENING. R310.1
  
 6. EXISTING BEAM BEING CONVERTED INTO A TIE BEAM
 CREATES A FEW CONCERNS.
  
 A. BY ENCASING THE EXISTING 2 X 8 IN CONCRETE CREATES
 ISSUES WITH WOOD DECAY. R317
  
 B. THE 4 - #5 BARS WILL NOT HAVE REQUIRED COVERAGE.
 R611.5.4.1 R611.5.4.2
  
 C. ARE LINTELS USED OVER OPENINGS. PROVIDE A SCHEDULE.
 R611.8.2
  
 D. VERTICAL BARS APPEAR TO BE GOING INTO EXISTING BEAM.
 HOOK BARS ARE NOT SHOWN. PROVIDE A DETAIL. FBC107.2.1
  
 7. FIELD VERIFY THAT THERE IS AN EXISTING FOOTING AND
 PROVIDE THE SIZE. FBC107.3
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-11-21 Cont ID  
Sent By jpearson Date 2017-11-21 Time 15:53 Rev Time 0.00
Received By jpearson Date 2017-11-21 Time 15:53 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-09-22 Cont ID  
Sent By jpearson Date 2017-09-22 Time 08:22 Rev Time 0.00
Received By jpearson Date 2017-09-22 Time 08:21 Sent To  
Notes
2017-09-22 08:21:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED BY PERSON
 RESPONSIBLE FOR THE DESIGN. FS 481.229; FBC 107.2.1,
 107.3.5
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30 FBC RE3706.1, RE3608.1, RE3609.3; FBC
 107.2.1
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC
 RE3706.2, RE3902
 4. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE
 EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC
 R314.3, FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-11-30 Cont ID  
Sent By aclange Date 2017-11-30 Time 13:29 Rev Time 0.00
Received By aclange Date 2017-11-29 Time 12:45 Sent To  
Notes
2017-11-30 12:45:40RESUB ROUTED TO ACLANGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-21 Cont ID  
Sent By jpearson Date 2017-11-21 Time 15:53 Rev Time 0.00
Received By jpearson Date 2017-11-07 Time 13:51 Sent To  
Notes
2017-11-08 13:51:54R09

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-06 Cont ID  
Sent By hmoser Date 2017-10-06 Time 11:15 Rev Time 0.00
Received By hmoser Date 2017-08-30 Time 12:52 Sent To  
Notes
2017-08-31 12:52:22R03

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2017-11-30 Cont ID  
Sent By aclange Date 2017-11-30 Time 13:20 Rev Time 0.00
Received By aclange Date 2017-11-30 Time 13:20 Sent To  
Notes
2017-11-30 13:21:30IMPACT FEE APPROVED 2017-32619 11/29/17

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-11-21 Cont ID  
Sent By aclange Date 2017-11-21 Time 10:48 Rev Time 0.00
Received By aclange Date 2017-11-21 Time 10:48 Sent To  
Notes
2017-11-21 10:48:55BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-10-06 Cont ID  
Sent By hmoser Date 2017-10-06 Time 11:15 Rev Time 0.00
Received By hmoser Date 2017-10-06 Time 11:15 Sent To  
Notes
2017-10-06 11:15:05BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2017-10-06 Cont ID  
Sent By hmoser Date 2017-10-06 Time 11:03 Rev Time 0.00
Received By hmoser Date 2017-10-06 Time 11:01 Sent To  
Notes
2017-10-06 11:09:07AIR CONDITIONING CONTRACTOR IS TO PROVIDE SEPARATE
 PLANS,
 ENERGY CALCULATIONS AND PERMIT. PER NOTE ON FRONT PAGE
 OF PLANS.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2017-11-17 Time   Rev Time 0.00
Received By pgreilic Date 2017-11-17 Time 12:59 Sent To  
Notes
2017-11-17 12:59:01PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2017-09-13 Time   Rev Time 0.00
Received By pgreilic Date 2017-09-13 Time 15:12 Sent To  
Notes
2017-09-13 15:12:35PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]